Tender For Work Of Erecton Of New 200Kva Transformer For Releasing Lt Connection Of Ronald Fernandes In Sy No 68/1-F At Cacnamoddi Cuncolim,Salcete-Margao
Tender Value
53.63 Lakhs
Estimated cost
Bid Submission
28 Oct 2026
10 days left
EMD
1.07 Lakhs
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
goa → Goa
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Work Of Erecton Of New 200Kva Transformer For Releasing Lt Connection Of Ronald Fernandes In Sy No 68/1-F At Cacnamoddi Cuncolim,Salcete-Margao
BOQ
| Sl. No. | Item Description |
| 1 | COST OF MATERIAL |
| 2 | Supply of 3 core, 300 sq.mm. aluminium, XLPE insulated, Flat Type armoured, 11KV (Earthed) Cable, type A2XFY conforming I.S. 7098 PART 2 and carrying ISI MARK (for the Ring Main System) by Open Trenching Method. |
| 3 | Supply of 3 core, 95sq.mm. aluminium, XLPE insulated, Flat Type armoured, 11KV (Earthed) Cable, type A2XFY conforming I.S. 7098 PART 2 and carrying ISI MARK (for the Ring Main Unit to Distr. Transformer)(Double Run) |
| 4 | Supply of 3 WAY RMU 11KV, 630A, 21 KA 3 Sec, SF6 Outdoor RMU- 2LBS + 1CB Extensible/Non Extensible Two (2) motor operated load break switches (LBSs) with manual operated earthing switches in SF6 and One (1) vacuum circuit breaker with Electrical closing and tripping along with disconnector and earthing switches SCADA Compatible and base channel. Battery charger along with bstteries required for Electrical operations of RMU is in the scope of the bidder. Each module shall consist of VPIS, FPI in LBS Module (N-1) but not less than 1 no's per RMU. Suitable arrangement for mounting FRTU, modem or Ethernet Switch/LIU along with battery, battery charger shall be provided in RMU. |
| 5 | Supply of 11KV, three phase, Heat shrinkable, Straight Through Jointing Kit complete for XLPE cable of size 3 core 300sq.mm.Make:- Raychem |
| 6 | Supply of Indoor type, heat shrinkable, three phase, end termination kit complete, for 11KV XLPE cable of size 3 x 300sq.mm including sockets /lugs / connectors etc.Make:- Raychem |
| 7 | Supply of Outdoor type, heat shrinkable, three phase, end termination kit complete, for 11KV XLPE cable of size 3 x 95sq.mm including sockets /lugs / connectors etc. Make:- Raychem |
| 8 | Supply of Indoor type, heat shrinkable, three phase, end termination kit complete, for 11KV XLPE cable of size 3 x 95sq.mm including sockets /lugs / connectors etc.Make:- Raychem |
| 9 | Supply of Cable route Markers (for entire route length) as per technical specification and drawing. |
| 10 | Supply, Laying of Warning Tapes (for entire route length) as per technical specification and drawing. |
| 11 | Design, Supply & Erection of RCC Hume pipes for road crossings, nullah crossings, small river crossings, culverts of 150 mm inner diameter, alongwith required no. of collars, PCC and Masonary work as per technical specifications. |
| 12 | Design, Supply of Medium duty, HDGI Class B pipe of nominal diameter 150 mm (alongwith HDGI bends wherever required) for bridge crossing, riser pipe for 95Sq.mm & 300Sq.mm XLPE Cable etc., as per technical specifications including supporting arrangement for the pipe. |
| 13 | Supply of 3 phase, 50Hz, 11/0.433KV, 200KVA, Distribution Transformer complete, suitable for outdoor use and for plinth mounting. |
| 14 | GI Tubular Fencing complete with gate side dismantling system as per the specfication of Distribution Transformer and Feeder Panels ( size 4Mx 3Mx 2M) with conctreting of GI Fencing supports with Plinth (0.3 x 0.3 x 0.5) Cu mt x 12 Nos. Eaxg ratio 1:3:6 and brick masonary. (Galvanising should be hot dipped Galvanised as per IS2629/66, minimum Zinc coating of 1000 gms/sq. mtrs, 140 Microns DFT, suitable for high salinity coastal areas). |
| 15 | Supply of Distribution Transformer metering unit. |
| 16 | Supply and fixing of CAMR Modem as per technical specification. |
| 17 | Supply of 3½ core, 185 sq.mm. aluminium, XLPE insulated, Flat Type armoured, 1.1KV (Earthed) Cable, and carrying ISI MARK |
| 18 | Supply of 3½ core, 120 sq.mm. aluminium, XLPE insulated, Flat Type armoured, 1.1KV (Earthed) Cable, and carrying ISI MARK |
| 19 | 185 lugs |
| 20 | 120 Lugs |
| 21 | 200KVA LV Panel fuse type (Double Front MS) |
| 22 | Supply of RCC protective covers of size 600mm long x 250mm width & 50mm thick capable of bearing load of 135kg & covered with earth/sand upto depth of 0.15mts. Confirming to IS 1255-1967 at non-road crossing. |
| 23 | Supply and laying of fine river sand of approved quality (except sandy soil) for cushioning of 11KV/LT underground cables. |
| 24 | Supply and laying of burnt clay wire cut bricks of 75 Kgs class.Wire cut bricks. |
| 25 | Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded granitic or basaltic stone aggregate 40 m nominal size for foundation of Ring Main Unit, Load Break Switch, Transformer & LV SwitchBoard |
| 26 | Centering and shuttering including struttings, propping etc and removal of form work for Ring Main Unit, Load Break Switch, Transformer & LV SwitchBoard. |
| 27 | Providing of 12 mm cement plaster 1:4 (1- cement: 4-fine sand ) for foundations of Ring Main Unit, Load Break Switch, Transformer & LV SwitchBoard. |
| 28 | Brick work using common burnt clay building bricks in cement mortar 1:4 ( 1 cement; 4 coarse sand) in foundation and Plinth(b) with bricks of class designation 75 kgs/sq.cm ( wire cut bricks) for TRANSFORMER foundations. |
| 29 | Earthing complete with 40mm GI pipe, 2.5mts long alongwith Batonite complete with brick masonary. |
| 30 | Supply of HDGI flat of size 50mm x 6 mm including supply and fixing of required quantity of HDGI nut bolts for earthing of all euipment. |
| 31 | COST OF ERECTION |
| 32 | Testing and Comissioning of 3 core, 300 sq.mm. aluminium, XLPE insulated, Flat Type armoured, 11KV (Earthed) Cable, type A2XFY conforming I.S. 7098 PART 2 and carrying ISI MARK (for the Ring Main System) by Open Trenching Method. |
| 33 | Erection, Testing and Comissioning of 3 core, 95sq.mm. aluminium, XLPE insulated, Flat Type armoured, 11KV (Earthed) Cable, type A2XFY conforming I.S. 7098 PART 2 and carrying ISI MARK (for the Ring Main Unit to Distr. Transformer)(Double Run) |
| 34 | Erection & Commissioning of 3 WAY RMU 11KV, 630A, 21 KA 3 Sec, SF6 Outdoor RMU- 2LBS + 1CB Extensible/Non Extensible Two (2) motor operated load break switches (LBSs) with manual operated earthing switches in SF6 and One (1) vacuum circuit breaker with Electrical closing and tripping along with disconnector and earthing switches SCADA Compatible and base channel. Battery charger along with bstteries required for Electrical operations of RMU is in the scope of the bidder. Each module shall consist of VPIS, FPI in LBS Module (N-1) but not less than 1 no's per RMU. Suitable arrangement for mounting FRTU, modem or Ethernet Switch/LIU along with battery, battery charger shall be provided in RMU. |
| 35 | Erection, Testing & comissioning of 11KV, three phase, Heat shrinkable, Straight Through Jointing Kit complete for XLPE cable of size 3 core 300sq.mm.Make:- Raychem |
| 36 | Erection, Testing and Comissioning of Indoor type, heat shrinkable, three phase, end termination kit complete, for 11KV XLPE cable of size 3 x 300sq.mm including sockets /lugs / connectors etc.Make:- Raychem |
| 37 | Erection, Testing and Comissioning of Outdoor type, heat shrinkable, three phase, end termination kit complete, for 11KV XLPE cable of size 3 x 95sq.mm including sockets /lugs / connectors etc. Make:- Raychem |
| 38 | Erection, Testing and Comissioning of Indoor type, heat shrinkable, three phase, end termination kit complete, for 11KV XLPE cable of size 3 x 95sq.mm including sockets /lugs / connectors etc.Make:- Raychem |
| 39 | Erection and Comissioning of Cable route Markers (for entire route length) as per technical specification and drawing. |
| 40 | Erection of RCC Hume pipes for road crossings, nullah crossings, small river crossings, culverts of 150 mm inner diameter, alongwith required no. of collars, PCC and Masonary work as per technical specifications. |
| 41 | Erection of Medium duty, HDGI Class B pipe of nominal diameter 150 mm (alongwith HDGI bends wherever required) for bridge crossing, riser pipe for 95Sq.mm & 300Sq.mm XLPE Cable etc., as per technical specifications including supporting arrangement for the pipe. |
| 42 | Erection, Testing and Comissioning of 3 phase, 50Hz, 11/0.433KV, 200KVA, Distribution Transformer complete, suitable for outdoor use and for plinth mounting. |
| 43 | GI Tubular Fencing complete with gate side dismantling system as per the specfication of Distribution Transformer and Feeder Panels ( size 4Mx 3Mx 2M) with conctreting of GI Fencing supports with Plinth (0.3 x 0.3 x 0.5) Cu mt x 12 Nos. Eaxg ratio 1:3:6 and brick masonary. (Galvanising should be hot dipped Galvanised as per IS2629/66, minimum Zinc coating of 1000 gms/sq. mtrs, 140 Microns DFT, suitable for high salinity coastal areas). |
| 44 | Erection of Distribution Transformer metering unit. |
| 45 | Testing and Comissioning of 3½ core, 185 sq.mm. aluminium, XLPE insulated, Flat Type armoured, 1.1KV (Earthed) Cable, and carrying ISI MARK |
| 46 | Testing and Comissioning of 3½ core, 120 sq.mm. aluminium, XLPE insulated, Flat Type armoured, 1.1KV (Earthed) Cable, and carrying ISI MARK |
| 47 | 185 lugs |
| 48 | 120 Lugs |
| 49 | 200KVA LV Panel fuse type (Double Front MS) |
| 50 | Earthwork in excavation by mechanical means (hydraulic excavator)/ manual means in foundation pipeline trenches drain (not exceeding 1.5 mt in width or 10 sq.m on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 m(a) for laying of HT/LT cables of various sizes in all kinds of soil, hard rock , providing barricading, danger lighting guarding etc. The trench lengths are as follows:All kinds of soil/rocks/laterite stone1. Size 1.1 x 0.6 x HT cable length mts for laying of 2 run. |
| 51 | Filling of available excavated earth (excluding rock/stones) in trench in layer not exceeding 0.2mts. Depth, consolidating each deposited layer by ramming and watering lead up to 40mts. |
| 52 | laying of RCC protective covers of size 600mm long x 250mm width & 50mm thick capable of bearing load of 135kg & covered with earth/sand upto depth of 0.15mts. Confirming to IS 1255-1967 at non-road crossing. |
| 53 | Earthing complete with 40mm GI pipe, 2.5mts long alongwith Batonite complete with brick masonary. |
| 54 | Erection of HDGI flat of size 50mm x 6 mm including supply and fixing of required quantity of HDGI nut bolts for earthing of all euipment. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 09, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 28, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysOct 29, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓
Disclaimer