Defence Statutory Bodies & Commissions/Committees Closing in 27 days TDR #57942188

Tender For Provision Of Technical Infrastructure And Associated Works For Technical Simulator Mh-60R At Niat, Kochi

Issued by Statutory Bodies & Commissions/Committees · Ernakulam, Kerala
Tender Value
26.60 Crore
Estimated cost
Bid Submission
05 Nov 2026
27 days left
EMD
15 Lakhs
Bank guarantee accepted
Document Fee
3000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Ernakulam → Kerala
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Provision Of Technical Infrastructure And Associated Works For Technical Simulator Mh-60R At Niat, Kochi

BOQ

Name of Work:- PROVISION OF TECHNICAL INFRASTRUCTURE AND ASSOCIATED WORKS FOR TECHNICAL SIMULATOR MH-60R AT NIAT, KOCHI
Sl. No. Item Description
1Total amount of Sch 'A' part-I (Buildings/ Structures)
2Total amount of Sch 'A' part-II (Excavation, Earthwork, Site Clearance & Development)
3Total amount of Sch 'A' part-III (Internal water supply)
4Total amount of Sch 'A' part-IV (Internal Electric Supply)
5Total amount of Sch 'A' part- V (External Water Supply)
6Total amount of Sch 'A' part-VI (External Electric Supply)
7Total amount of Sch 'A' part-VII (Lightning Protection)
8Total amount of Sch 'A' part-VIII (Area Drainage)
9Total amount of Sch 'A' part-IX (Sewage Disposal)
10Total amount of Sch 'A' part-X (Road/ Culvert/ Hardstanding)
11Total amount of Sch 'A' part-XI (Compound Wall, Gate & Arboriculture)
12Total amount of Sch 'A' part-XII (Demolition)
13SCH. 'A' PART -XIII (Miscellaneous B/R & E/M Items )Note :- This schedule is not pre priced by MES and the pre priced rate indicated as \\"Rs. 0.00\\" under Col.5 signifies this fact only.
14PILEBoring for cast in situ piles 600mm dia 42 m depth through any type of soil/ strata by DMC method using bentonite slurry including removal of bored materials out side MD land complete all as specified.
15M&L for Cement concrete in foundations, filling and mass concrete Type D-2 1:4:8 (40 mm graded aggregate) complete all as specified and as directed.
16RCC M30 Design Mix as per IS- 456 with using 20mm graded stone aggregate as in cast in situ bored pile of 600mm dia all as specified and as shown in drg.
17RCC M30 Design Mix as per IS- 456 with using 20mm graded stone aggregate as in pile cap and grade beam all as specified and as shown in drg.
18S & F Mild steel TMT bars 10mm dia and over, cut to length, bent to shape reqired including cranking, bending spirally for hooping for columns hooking ends and binding with mild steel wire (annealed) not less than 0.9 mm dia or securing with clips complete all as specified and as directed.
19S & F Mild steel TMT bars 8mm &10mm dia and over, cut to length, bent to shape reqired , bending spirally and binding with mild steel wire (annealed) not less than 0.9 mm dia or securing with clips complete all as specified and as directed.
20S&F of Formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work; vertical or to batter on Rough finished surfaces of concrete complete all as specified and as directed.
21Testing of pile all as specified and as directed.
22ARBORICULTURESupply only approved red earth without pebble brought from out side MD land for planting of grass all as specified and directed.
23Mixing, spreading, levelling watering, and well ramming of approved earth in required proportion as directed for planting of grass in layers not exceeding 25cm thick incl supply and mixing of 1/2 Kg/Sq of cow dung 0.25 Kg/Sqm of bone meal, 0.25 kg/Sqm of cocopeat and compost complete all as specified and directed at site.
24M&L for grassing of bermuda grass free from weeds having proper roots in green incl watering and maint of lawn for 30 days or more till grass forms a thick lawn free from weeds and fit for moring in rows 7.5 cm centre to centre in both direction by dibbling method all as spd and directed by Eng in Charge.
25Excavating in post holes or similar holes for planting of sapplings each n exc 0.5 Cum getting out, returning filling in and ramming with approved earth in layers not exceeding 25 cm all as spd and directed by Eng in Charge (Returning filling to be done with earth mixed with cow dung, bone meal, cocopeat and compost in equal proportions in the ratio of 2:1 in volume) etc. complete all as specified and as directed.
26M&L complete maint of entire lawn garden area incl gap filling. watering, mowing of lawn, grass cutting, removing garden waste, applying insecticides and fertilizers, top dressing of lawn with good earth and manure and maint of other garden related works and all as directed by Engr in charge for one year.
27Supply and planting furcaria leaf Plant having 30 cm height and shall have minimum height of 45 cm after 6 months etc. complete all as specified and as directed.
28Supply and planting Ixora in different colour plants like red, pink,orange, white etc having 15 cm to 30 cm height after 6 months shall bc 40 cm etc. complete all as specified and as directed.
29Supply and planting Acalypha hispida (leaf plants) having 30 cm to 60 cm height, minimum height after 6 months shall be 90 cm etc. complete all as specified and as directed.
30Supply and planting Allamanda flower plants (in packets) having 15 cm to 30 cm height, minimum height after 6 months shall be 90 cm etc. complete all as specified and as directed.
31Supply and planting Duranta (Border plants) in yellow colour having 15 cm height and shall have minimum 45 cm height after 6 months etc. complete all as specified and as directed.
32Supply and planting Tabernae Montana (low edge plants) in white and green colours having 30 cm height (in packets) and shall have minimum of 45 cm height after 6 months etc. complete all as specified and as directed.
33Supply and planting red palm sappling having 45 cm height etc. complete all as specified and as directed.
34Supply and planting champagne paim 30 cm height and shall have a minimum height of 45 cm after 6 months etc. complete all as specified and as directed.
35Supply and planting Coleus (leaf plants) in different colour (in packets) having 15 to 30 cm height and shall have minimum of 45 cm height after 6 months etc. complete all as specified and as directed.
36Supply and planting butterfly bush (border plant) in white colour etc. complete all as specified and as directed.
37Supply and planting Schefflera leaf plant in different colours having up to 30 cm height etc. complete all as specified and as directed.
38EXTERNAL WATER SUPPLYSupply, installation, testing, and commissioning of a 3-Phase Monoblock Centrifugal Pumping Set, designed for heavy-duty operation. The pump shall feature a robust Cast Iron (C.I.) Volute Casing, a corrosion-resistant Bronze Impeller, and a high-quality Mechanical Seal to prevent leakage. The pump set shall be rated for a minimum discharge of 90 LPM at 36 meter head (or higher standard size), driven by a TEFC (Totally Enclosed Fan Cooled) Induction Motor suitable for 400/440 Volts, 3-Phase, 50 Hz A.C. supply. The assembly shall include suction and delivery sizes compatible with a 40 mm dia pipeline, complete with necessary GI/CI reducers, vibration-eliminating Double-Sphere Flexible Bellows, and specialized vibration-dampening pads/mounts complete all as specified and as directed and including the following:(a) Fabrication and supply of a heavy-duty MS Base Frame(b) Construction of a 1:2:4 Plain Cement Concrete (PCC) Foundation of suitable height in the existing Pump house as directed.(c) Installation of one 50 mm dia Pressure Gauge with isolation cock.(d) All necessary GI fittings required for priming arrangements, structural supports, clamps, SS-304/GI bolts, nuts, and washers.(e) Submission of detailed Technical Specifications and GA (General Arrangement) Drawings showing suction and discharge pipelines for approval of the GE.
39Supply and fixing of 50 mm outer dia CPVC Non-Return Valve (NRV), suitable for CPVC piping systems. The valve shall be of the Swing Check or Ball Check design, manufactured from high-grade CPVC compound conforming to ASTM D2846 or IS: 15778. Including True Union to allow for easy maintenance and cleaning of the internal flap/ball without cutting the pipeline and solvent welding using heavy-duty CPVC solvent cement complete as specified and directed by the Engineer-in-Charge.
40Supply, installation, testing and commissioning of cubical type pump control panel indoor type made out of CRCA sheet 2.0 mm thick with powder coated painting duly compartmentalised and four Nos of 100 amps Aluminium strips / bars duly insulated mounted on insulators / suitable size conforming to IP 65 classification, CPRI approved bakelite sheet and including panel meter with selector switches as under, PVC insulated copper cable for control wiring, Double Compression steel cable glands of suitable size, base frame made up of MS angle of suitable size to maintian minimu height of 450mm from Ground level and comprising of the following incoming / outgoing complete all as specified and as directed :- (i) MCB FP 32 Amps - 01 No Incoming (ii) MCB TP 16 Amps - 02 Nos outgoing for pumps (iii) Indicating lamp set of 3 - 03 Set (iv) Single phase preventer - 01 No (v) Suitable DOL Starter fully automatic 415 volts-2Nos (vi) LED Multi functional panel meter alognwith connected CTs programmable with indications of parameters V, A, F, PF -03 No complete all as specified and as directed.
41M & L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure all as specified and as directed.
42INTERNAL ELECTRIC SUPPLYSupply and Fixing rugged LED highbay luminaire with aluminium reflector 200 watts fitting complete with switchgear control unit and lamp,3 core flexible wire of suitable size,etc for fire hazard free operation including testing all as directed by the Engr-in-Charge.
43Supply and Fixing wall mountimng air circulator 600mm sweep, single phase,1400 RPM complete with switchgear control unit, suitable length and size of 3 core flexible wire with plug, all necessary fixing materials,etc for fire hazard free operation including testing all as directed by the Engr-in-Charge.
44S & F Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed with and including 3 nos. 8mm dia 25mm long hex. head screw and necessary connected accessories complete all as specified and directed.
45S & F Single pole and neutral enclosure with a two pin & earth plug and socket complete with one two pole MCB 20 Amps comlete all as specified and as directed.
46S & Fix Triple pole and earth encolsure with a three pin and earth plug with socket complete with one triple pole MCB 32 Amps complete all as specified and as directed.
47S & F Triple pole and earth encolsure with a three pin and earth plug with socket complete with one triple pole MCB 40/63 Amps complete all as specified and as directed.
48S & F single pole & neutral double door, modular type, metallic distribution board, conforming to IEC 61439-3, suitable for flush / surface mounting with provision for RCBO / MCB as incomer and SP/TP MCBs as outgoing, reversible metal door, suitable size copper busbar, fully shrouded neutral bar, earth bar, wire set & cable ties for cable management, pre fitted masking sheet, etc. having IK 09 & IP 43 protection for complete all as specified in IS 732: 2019 and directed by the engineer-in-charge.Notes : FP RCCB / RCBO / Isolator / MCB & SP/TP MCBs shall be measured and paid separately.
49All as per item No 48 above but for Single pole & neutral DB, 8 way 240V (Gen supply at 2nd Floor-01, Lt and skt distribution at First floor)
50All as per item No 48 above but for Single pole & neutral DB, 12 way 240V( Lt and Power skts distribution at First floor)
51S & F TPN 6 WAY double door, modular type, metallic distribution board, conforming to IEC 61439-3, suitable for flush / surface mounting with provision for RCBO as incomer and SP/TP MCBs as outgoing, reversible metal door, suitable size copper busbar, fully shrouded neutral bars, earth bar, wire set & cable ties for cable management, pre fitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified in IS 732: 2019 and directed by the engineer-in-charge. Note : Incomer MCCB & Outgoing MCBs shall be measured and paid separately (For First floor main distribution DB).
52S & F VTPN 4 WAY double door, modular type, metallic distribution board, conforming to IEC 61439-3, suitable for flush / surface mounting with provision for MCCB FP as incomer and SP/TP MCBs as outgoing, reversible metal door, suitable size copper busbar, fully shrouded neutral bars, earth bar, wire set & cable ties for cable management, pre fitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified in IS 732: 2019 and directed by the engineer-in-charge. Note : Incomer MCCB & Outgoing MCBs shall be measured and paid separately.(Panel Room GF, Main distribution DB at First floor).
53S & F VTPN 8 WAY double door, modular type, metallic distribution board, conforming to IEC 61439-3, suitable for flush / surface mounting with provision for MCCB FP as incomer and SP/TP MCBs as outgoing, reversible metal door, suitable size copper busbar, fully shrouded neutral bars, earth bar, wire set & cable ties for cable management, pre fitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified in IS 732: 2019 and directed by the engineer-in-charge. Note : Incomer MCCB & Outgoing MCBs shall be measured and paid separately (AMWLT and VMT).
54S & F TPN 4 WAY (8 + 12) double door, modular type, metallic distribution board, conforming to IEC 61439-3, suitable for flush / surface mounting with provision for FP RCBO as incomer and SP/TP MCBs as outgoing, reversible metal door, suitable size copper busbar, fully shrouded neutral bars, earth bar, wire set & cable ties for cable management, pre fitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified in IS 732: 2019 and directed by the engineer-in-charge. Note : Incomer MCCB & Outgoing MCBs shall be measured and paid separately.(For Lift Machine room).
55Supply and fix MCB SP 6 to 32A, 240 V, C-Curve 10KA in the DBs all as directed by the engineer-in-charge.
56Supply and fix MCB SP 40A, 240 V, C-Curve 10KA in the DBs all as directed by the engineer-in-charge.
57Supply and fix MCCB 160A 36KA, 415V, FP, Adjustable type all as directed by the engineer-in-charge.
58Supply and fix MCCB 100A 16KA, 415V, FP, Adjustable type all as directed by the engineer-in-charge.
59Supply and fix MCB 63A 16KA, 415V, TP, Adjustable type all as directed by the engineer-in-charge.
60Supply and fix MCB 40A 16KA, 415V, TP, Adjustable type all as directed by the engineer-in-charge.
61Supply and fix MCB 32A 16KA, 415V, TP, Adjustable type all as directed by the engineer-in-charge.
62Supply and fix MCB SPN 16A, 240 V, C-Curve 10KA all as directed by the engineer-in-charge.
63Supply and fix RCBO DP 6-32 Amps, 30 mA, 240V all as directed by the engineer-in-charge.
64Supply and fix RCBO DP 40 Amps 30 mA, 240V all as directed by the engineer-in-charge.
65Supply and fix RCBO FP 40 Amps 30 mA, 415V all as directed by the engineer-in-charge.
66M & L for following Point wiring with PVC insulated unsheathed FRLS stranded copper conductor cable of size 1.5 Sq mm, drawn through stove enameled steel rigid conduit with one No stranded copper conductor cable of size 1.5 Sq mm for earth continuity wire, with and incl suitable dia stove enameled steel rigid conduit concealed in walls/roof, all accessories such as sunken steel boxes, bends, elbows, junction boxes, cover plates of suitable no of modules, screws etc One light point controlled by one, one way switch required as per site requirement complete all as specified and as directed.
67All as per item No 66 above but for One ceiling /exhaust fan point controlled by one, one way switch
68All as per item No 66 above but for One 3 pin socket outlet, 5 amps, independent, with cables 1.5 sq. mm size
69All as per item No 66 above but for One light point controlled by two 2-way switches
70All as per item No 66 above but for One socket outlet 16 Amp on independent board with 2.5 Sq mm cable and 2.5 Sq mm earth wire. ( power point 16 Amps sockets)
71M&L for Submain wiring with 2 x 2.5 sqmm size along with earth wire of size 1x 2.5 sq mm of FRLS PVC insulated copper conductor, single core multistranded in and including steel conduit of suitable size in surface/recessed/concealed all as reqd at site/directed.
72M&L for Submain wiring with 2 x 10 sqmm size along with earth wire of size 1x 10 sq mm of FRLS PVC insulated copper conductor, single core multistranded in and including steel conduit of suitable size in surface/recessed/concealed all as reqd at site/directed.
73M&L for Submain wiring with 4 x 16 sqmm size along with earth wire of size 1 x 16 sq mm of FRLS PVC insulated copper conductor, single core multistranded in and including steel conduit of suitable size in surface/recessed/concealed all as reqd at site/directed.
74M&L for Submain wiring with 2 x 4.0 sqmm size along with earth wire of size 1x 4.0 sq mm of FRLS PVC insulated copper conductor, single core multistranded in and including steel conduit of suitable size in surface/recessed/concealed all as reqd at site/directed.
75M&L for Submain wiring with 4 x 10.0 sqmm size along with earth wire of size 1x 10.0 sq mm of FRLS PVC insulated copper conductor, single core multistranded in and including steel conduit of suitable size in surface/recessed/concealed all as reqd at site/directed.
76EXTERNAL ELECTRIC SUPPLYSupply, Installation, Testing, and Commissioning of 11kV, 630 Amps, 50Hz, 3-Phase Outdoor Type SF6 Insulated RMU (Single Way VCB Module), designed for lateral extension to the existing HT panel. The unit shall be housed in a weather-proof, salt-spray resistant stainless steel / CRCA enclosure (IP-54 for outdoor) with a minimum thickness of 2mm, finished in Siemens Grey (RAL 7032) with future extension. Vacuum Circuit Breaker (VCB) rated at 630A, 21kA for 3 seconds, housed within an SF6 gas-insulated tank. The VCB shall include a spring-charged manual/motorized mechanism with trip-free functionality. High-conductivity Busbar 630 Amps electrolytic grade copper busbars, fully insulated and arranged for modular extension and terminals for future extension. Self-powered Microprocessor-based IDMT Overcurrent and Earth Fault Relay with associated 11kV Current Transformers (CTs) of suitable ratio and class.Including a specialized Lateral Coupling Kit (Busbar connectors, shrouds, right angle boots, and bellows) specifically compatible with the existing RMU make and model for seamless extension complete all as specified and as directed incluing following:
77(a) Construction of a reinforced RCC Foundation as per approved GA drawings, including cable trenches and MS channels as required.(b) Supply of SS-304 hardware/fasteners and earth-continuity strips(c) Installation of outgoing cable termination boots suitable for 3C x 185 sq.mm XLPE cable.(d) Bottom Cable entry with necessary gland plate and proper sealing.(e) Submission of GA drawings and foundation details before placing order for approval of Accepting Officer.
78Supply and and Laying of 11 kV Grade Power Cable, XLPE insulated, screened, PVC bedded, Galvanized Steel Strip or Wire Armoured, featuring stranded Aluminium Conductors of cross-sectional area 120 sq. mm, 3-Core, conforming to IS: 7098 (Part 2) including laying in trench, fixed to wall/ floor/ceiling using heavy-duty G.I. spacers and saddles/clamps at intervals not exceeding 600 mm, Drawn through Protection pipe, etc complete all as specified and as directed.
79Supply, Installation, Testing, and Commissioning (SITC) of 500 kVA, 11kV/0.433kV Outdoor Type Distribution Transformer, Oil Immersed Naturally Cooled (ONAN). The unit shall be Energy Efficiency Level-III as per IS: 1180 (Part-1: 2022) with the latest amendments.The transformer shall feature high-conductivity Copper Winding, Delta connection on the HT side, and Star connection on the LT side with Vector Group Dyn11. It shall be equipped with an Off-Load Tap Changer (OLTC) providing a range of +7.5% to - 7.5% in steps of 2.5 % The transformer must be supplied with the first filling of fresh insulating oil conforming to IS: 335, Provided with Cable End Boxes on both HT and LT sides; the LT side shall have the neutral bushing brought out for system earthing, including the construction of a robust Masonry/RCC Platform, HT/LT cable ducts/gruves, and all structural modifications required for a flush and secure installation as per OEM recommendations with Conservator tank, Buchholz relay, Oil/Winding Temperature Indicators (OTI/WTI) with alarm/trip contacts, Marshalling box, and Silica Gel Breather.etc complete all as specified and as directed including the following:(a) Lifting lug for transformer and tank.(b) Earthing terminal rating and diagram plate.(c ) Air release device.(d) Oil filling inlet pipe with plug.(e) Drain outlet pipe with brass gate valve.
80(f) Conservator tank with oil level indicator(g) Silica jel breather(h) First fill of oil upto level including conservator tank with fresh new oil conforming to IS335.(i) Type of connection Delta/Star(j) Type of cooling: Oil and Natural Air.(k) Vector group:DYN 11.(l) Suitabel for Temperature rise over an ambient of 50 °C maximum.(m) Cable end box on both side for HT/LT cables of suitable size.(n) Provision of thermometer with pocket.(o) Provision of oil and winding temperature gauge.(p) Bucholz Relay(q) Marshalling Box with all Oil and winding Temperature gauges and terminals of relays and guages complete with locking arragements madeup of transprant glass door along with necessary connecting to VCB.(r) Submission of GA drawings and foundation details before placing order for approval of Accepting Officer.
81Supply and fixing of 11 kV (Earthed) Grade Indoor Termination Kit, Heat-Shrinkable type, suitable for 3-Core, 120 sq.mm XLPE insulated, armoured aluminium conductor cable. The kit shall conform to IS: 13573 and include all necessary components for a high-performance electrical stress control and moisture seal, Solderless earth connection assembly including tinned copper braid, constant pressure springs (roll springs), and lugs for connecting the cable armour and metallic screen to the system earth, Heavy-duty, long-barrel Aluminium Crimping Lugs suitable for 120 sq.mm conductor, Mastic sealants, cleaning solvent, abrasive strips, etc complete all as specified and as directed.
82Supply, laying, and testing of 1100 Volts grade XLPE insulated, PVC bedded, Galvanized Steel Strip/Wire Armoured heavy-duty electric power cable with stranded Aluminium conductor of size 6 sq.mm, 2.0 Core conforming to IS: 7098 (Part 1), laying in excavated trenches (on a sand bed with protective bricks) or through GI/PVC pipes or clamped on walls/trays etc., providing cable tags at every 5 meters for the cable laid above ground level, and making end-terminations with heavy-duty brass compression glands and aluminium lugs complete all as specified and directed by the Engineer-in-Charge.
83Supply, laying, and testing of 2.0 core 10 sqmm 1100 Volts grade XLPE insulated, PVC bedded, Galvanized Steel Strip/Wire Armoured heavy-duty electric power cable with stranded Aluminium conductor conforming to IS: 7098 (Part 1), laying in excavated trenches (on a sand bed with protective bricks) or through GI/PVC pipes or clamped on walls/trays etc., providing cable tags at every 5 meters for the cable laid above ground level, and making end-terminations with heavy-duty brass compression glands and aluminium lugs complete all as specified and directed by the Engineer-in-Charge.
84Supply, laying, and testing of 4.0 core 25 sqmm 1100 Volts grade XLPE insulated, PVC bedded, Galvanized Steel Strip/Wire Armoured heavy-duty electric power cable with stranded Aluminium conductor conforming to IS: 7098 (Part 1), laying in excavated trenches (on a sand bed with protective bricks) or through GI/PVC pipes or clamped on walls/trays etc., providing cable tags at every 5 meters for the cable laid above ground level, and making end-terminations with heavy-duty brass compression glands and aluminium lugs complete all as specified and directed by the Engineer-in-Charge.
85Supply, laying, and testing of 3.5 core 35 sqmm 1100 Volts grade XLPE insulated, PVC bedded, Galvanized Steel Strip/Wire Armoured heavy-duty electric power cable with stranded Aluminium conductor conforming to IS: 7098 (Part 1), laying in excavated trenches (on a sand bed with protective bricks) or through GI/PVC pipes or clamped on walls/trays etc., providing cable tags at every 5 meters for the cable laid above ground level, and making end-terminations with heavy-duty brass compression glands and aluminium lugs complete all as specified and directed by the Engineer-in-Charge.
86Supply, laying, and testing of 3.5 core 50 sqmm 1100 Volts grade XLPE insulated, PVC bedded, Galvanized Steel Strip/Wire Armoured heavy-duty electric power cable with stranded Aluminium conductor conforming to IS: 7098 (Part 1), laying in excavated trenches (on a sand bed with protective bricks) or through GI/PVC pipes or clamped on walls/trays etc., providing cable tags at every 5 meters for the cable laid above ground level, and making end-terminations with heavy-duty brass compression glands and aluminium lugs complete all as specified and directed by the Engineer-in-Charge.
87Supply, laying, and testing of 3.5 core 70 sqmm 1100 Volts grade XLPE insulated, PVC bedded, Galvanized Steel Strip/Wire Armoured heavy-duty electric power cable with stranded Aluminium conductor conforming to IS: 7098 (Part 1), laying in excavated trenches (on a sand bed with protective bricks) or through GI/PVC pipes or clamped on walls/trays etc., providing cable tags at every 5 meters for the cable laid above ground level, and making end-terminations with heavy-duty brass compression glands and aluminium lugs complete all as specified and directed by the Engineer-in-Charge.
88Supply, laying, and testing of 3.5 core 95 sqmm 1100 Volts grade XLPE insulated, PVC bedded, Galvanized Steel Strip/Wire Armoured heavy-duty electric power cable with stranded Aluminium conductor conforming to IS: 7098 (Part 1), laying in excavated trenches (on a sand bed with protective bricks) or through GI/PVC pipes or clamped on walls/trays etc., providing cable tags at every 5 meters for the cable laid above ground level, and making end-terminations with heavy-duty brass compression glands and aluminium lugs complete all as specified and directed by the Engineer-in-Charge.
89Supply, laying, and testing of 3.5 core 120 sqmm 1100 Volts grade XLPE insulated, PVC bedded, Galvanized Steel Strip/Wire Armoured heavy-duty electric power cable with stranded Aluminium conductor conforming to IS: 7098 (Part 1), laying in excavated trenches (on a sand bed with protective bricks) or through GI/PVC pipes or clamped on walls/trays etc., providing cable tags at every 5 meters for the cable laid above ground level, and making end-terminations with heavy-duty brass compression glands and aluminium lugs complete all as specified and directed by the Engineer-in-Charge.
90Supply, laying, and testing of 3.5 core 240 sqmm 1100 Volts grade XLPE insulated, PVC bedded, Galvanized Steel Strip/Wire Armoured heavy-duty electric power cable with stranded Aluminium conductor conforming to IS: 7098 (Part 1), laying in excavated trenches (on a sand bed with protective bricks) or through GI/PVC pipes or clamped on walls/trays etc., providing cable tags at every 5 meters for the cable laid above ground level, and making end-terminations with heavy-duty brass compression glands and aluminium lugs complete all as specified and directed by the Engineer-in-Charge.
91Supply, laying, and testing of 3.5 core 300 sqmm 1100 Volts grade XLPE insulated, PVC bedded, Galvanized Steel Strip/Wire Armoured heavy-duty electric power cable with stranded Aluminium conductor conforming to IS: 7098 (Part 1), laying in excavated trenches (on a sand bed with protective bricks) or through GI/PVC pipes or clamped on walls/trays etc., providing cable tags at every 5 meters for the cable laid above ground level, and making end-terminations with heavy-duty brass compression glands and aluminium lugs complete all as specified and directed by the Engineer-in-Charge.
92Supply and fixing of LED Street Light Luminaire, 70 Watt rating, suitable for 230V AC, 50Hz supply. The light shall have a high-pressure pressure die-cast aluminum (ADC12) housing with integrated high-efficiency heat-sink fins for superior thermal management. The luminaire shall be equipped with multiple secondary optics (Lenses) to provide a professional 'Batwing' light distribution, ensuring uniform illumination across the road surface. The light must have IP66 ingress protection and a minimum IK08 impact resistance rating with toughened glass or UV-stabilized polycarbonate cover. The internal driver shall be high-power factor (>0.95), with integrated surge protection (minimum 10 kV). The housing must be treated with a salt-spray resistant, anti-corrosive powder coating (Signal Grey/Dark Grey). inclduing the supply of a G.I. mounting bracket/arm, all necessary SS-304 hardware, and electrical connections complete all as specified and directed by the Engineer-in-Charge.
93Supply and erection of Steel Tubular Swaged Pole, Type 410-SP-31, having a total length of 9.0 meters, conforming to IS: 2713. The pole shall be manufactured from high-tensile steel tubes, swaged together with seamless joints to ensure structural integrity with Cast Iron (C.I.) Base Plate (300 x 300 x 10 mm minimum), a C.I. Finial Taper Plug, and a weather-proof cap. All assembly hardware shall be of high-quality Mild Steel bolts and screws. Application of two coats of Black Bituminous paint both internally and externally from the bottom up to the planting depth (plus 150 mm above GL) and Application of one coat of high-quality Aluminium Primer followed by two coats of Aluminium Paint (externally from the top of the PCC coping to the pole top). Writing of 'MES' and Pole Number using first-grade synthetic enamel paint in a legible font as per standard MES markings complete all as specified and as directed.Note:(a) Earthwork and PCC will be measured and paid under appropriate items in of Schedule 'A'/BOQ (b) Volume occupied by Steel Pole shall be deducted to derive the quantity of PCC.
94M&L and spreading of Riddled sand for cable protection/ cushioning, in trenches complete all as specified and directed.Note : Consolidated (punned) thickness of sand shall only be measured.
95Supply and fix cable route indicator oval shaped of size 200x150x6mm thick made out of Cast Iron with letter embossed as \\"LT UG Cable\\" fixed to 25x25x6mm mild steel angle iron 450mm long embedded in PCC block of size 200x200x200mm in PCC 1:3:6 type C1 using 20mm graded stone aggregate and including painting two coats of synthetic enamel paint over a coat of redoxide zinc chrome premier on exposed steel surfaces complete all as specified and as directed.
96Supply, installation, testing and commissioning factory made Main LT panel board suitable for working on 3 phase, 4 wire, 415V AC, 50HZ, outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation with IP-54 protection fabricated out of 3.15 mm thick CRCA sheet powder coated painting, CPRI approved, separate compartment for ACB/MCCB/metering equipment's/cable gallay etc front and rear hinged door with locking arrangement, copper bus bar duly covered with heat shrinkable sleeves colour coaded fixed on DMC/SMC insulators bottom cable entry holes for incoming and outgoing cables with copper glands and connecting the outgoing MCCBs/switch gears with main bus bar by using aluminium bus links or copper conductor cable of suitable rating and connecting with terminal blocks of appropriate rating terminated by cable lugs, thimbles etc, earthing terminals, affixing danger notice plate, control wiring with flexible copper conductor cables of suitablesize and adequate length, control fuses/MCBs and PCC foundation as per site requirement. Angle iron stand made of size 50x50x6mm for mounting of LT panel 40cm above floor level complete all as specified and directed by Engineer-in-Charge comprising of following:- INCOMER(i) 800A, 415V, Ics= 100%Icu(1sec)50kA, 50Hz, manual type FP ACB, conforming to IS/IEC 60947-2 & 3, having fully rated neutral with inbuilt protection, microprocessor based overload, short-circuit, instanteneous & earth-fault protections, pre-trip alarm & individual fault indicating LEDs, no derating up to 50°C, zone selective interlocking - 01 No
97OUTGOING(i) 630A, 415V, Ics= 100%Icu(1sec) 36kA, 50Hz, manual type FP MCCB, conforming to IS/IEC 60947-2 & 3, having fully rated neutral with inbuilt protection, microprocessor based overload, short-circuit, instanteneous & earth-fault protections, pre-trip alarm & individual fault indicating LEDs, no derating up to 50°C, zone selective interlocking - 02 Nos (One for 500 KVA DG AMF and one spare)(ii)125A, 415V, Ics= 100%Icu(1sec)25kA, 50Hz, manual type FP MCCB, conforming to IS/IEC 60947-2 & 3, having fully rated neutral with inbuilt protection, microprocessor based overload, short-circuit, instanteneous & earth-fault protections, pre-trip alarm & individual fault indicating LEDs, no derating up to 50°C, zone selective interlocking - 01 No for 100 KVA DG AMF(iii)100A, 415V, Ics= 100%Icu(1sec)25kA, 50Hz, manual type FP MCCB, conforming to IS/IEC 60947-2 & 3, having fully rated neutral with inbuilt protection, microprocessor based overload, short-circuit, instanteneous & earth-fault protections, pre-trip alarm & individual fault indicating LEDs, no derating up to 50°C, zone selective interlocking - 01 No for first floor VTPN 4 way DB in coming light load(iv) 1200A rated Copper bus bar with colour code heat shrinkable sleeve.-1JOB(v) LED Multi functional panel meter flush mounting 96 x 96 cm 4400 series, CT and PT site programmable with indications of parameters V, A, F, PF, KW, KVA, energy, load hrs and site selectable KWH/KWAH -01 No
98(vi) CTs -03 Nos(vii) LED R-Y-B PHASE indicating lamp-01 sets.(viii) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled.(ix) PCC 1:4:8 type D2 using 240mm graded aggregate for Foundation / mounting the LT panel as directed.
99Supply, installation, testing and commissioning Building LT panel board factory made suitable for working on 3 phase, 4 wire, 415V AC, 50HZ, indoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation with IP-54 protection fabricated out of 2mm thick CRCA sheet powder coated painting, CPRI approved, separate compartment for ACB/MCCB/metering equipments/cable gallay etc front and rear hinged door with locking arrangement, copper bus bar duly covered with heat shrinkable sleeves colour coaded fixed on DMC/SMC insulators bottom cable entry holes for incoming and outgoing cables and connecting the outgoing MCCBs/switch gears with main bus bar by using aluminium bus links or copper conductor cable of suitable rating and connectING with terminal blocks of appropriate rating terminated by cable lugs, thimbles etc, earthing terminals, affixing danger notice plate, control wiring with flexible copper conductor cables of suitablesize and adequate length, control fuses/MCBs and PCC foundation as per site requirement. Angle iron of size 50x50x6mm for mounting of LT panel 40cm above floor level complete including necessary PCC foundation all as specified and directed by Engineer-in-Charge comprising of following:-(for 400 KVA DG LT Panel)INCOMER (i) 630A, 415V, Ics= 100%Icu(1sec) 36kA, 50Hz, manual type FP MCCB, conforming to IS/IEC 60947-2 & 3, having fully rated neutral with inbuilt protection, microprocessor based overload, short-circuit, instanteneous & earth-fault protections, pre-trip alarm & individual fault indicating LEDs, no derating up to 50°C, zone selective interlocking - 01 Nos.
100OUTGOINGOUTGOING and other fitments(i) MCCB 4 pole adjustable thermal & fixed magnetic type 500A,415V,50HZ,25KA with extended terminals-02 Nos.(AC panel, Spare)(ii) MCCB 4 pole adjustable thermal & fixed magnetic type 160A,415V,50HZ,25KA with extended terminals-01 Nos.(VMT TPN 8 Way DB)(iii) MCCB 4 pole adjustable thermal & fixed magnetic type 100A,415V,50HZ,25KA with extended terminals-01 Nos (Amwlt Room TPN 8 Way DB)(iv) MCCB 4 pole adjustable thermal & fixed magnetic type 40A,415V,50HZ,25KA with extended terminals-02 Nos for (EOT Crane panel) and CRAC Panel(v) 800A rated copper/Almn bus bar with colour code heat shrinkable sleeve.(vi) LED Multi functional panel meter flush mounting 96 x 96 cm 4400 series, CT and PT site programmable with indications of parameters V, A, F, PF, KW, KVA, energy, load hrs and site selectable KWH/KWAH -01 No(vii) Suitable PTs for Panel meter -01set(viii) LED R-Y-B PHASE indicating lamp-01 sets.(ix) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled.
101Supply, installation, testing and commissioning 100 KVA DG panel board (utility panel)suitable for working on 3 phase, 4 wire, 415V AC, 50HZ, indoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation with IP-54 protection fabricated out of 2mm thick CRCA sheet powder coated painting, CPRI approved, separate compartment for ACB/MCCB/metering equipments/cable gallay etc front and rear hinged door with locking arrangement, copper bus bar duly covered with heat shrinkable sleeves colour coaded fixed on DMC/SMC insulators bottom cable entry holes for incoming and outgoing cables and connecting the outgoing MCCBs/switch gears with main bus bar by using aluminium bus links or copper conductor cable of suitable rating and connectING with terminal blocks of appropriate rating terminated by cable lugs, thimbles etc, earthing terminals, affixing danger notice plate, control wiring with flexible copper conductor cables of suitablesize and adequate length, control fuses/MCBs and PCC foundation as per site requirement. Angle iron of size 50x50x6mm for mounting of LT panel 40cm above floor level complete all as specified and directed by Engineer-in-Charge comprising of following:- INCOMER(i) MCCB 4 pole adjustable thermal & fixed magnetic type 125 A, 415V, 50HZ, 36KA
102OUTGOING(i)MCCB 4 pole 63A,415V,50HZ,16KA with extended terminals-03 Nos (Cago lift, passenger lifts and Spare)(ii)MCCB 4 pole 40A,415V,50HZ,16KA with extended terminals for VTPN 4 Way in panel room(iii)MCCB 4 pole 32A,415V,50HZ,16KA with extended terminals for Booster pump panelBUSBAR200A rated Copper bus bar with colour code heat shrinkable sleeve.METER & INDICATION(i) LED Multi functional panel meter flush mounting 96 x 96 cm 4400 series, CT and PT site programmable with indications of parameters V, A, F, PF, KW, KVA, energy, load hrs and site selectable KWH/KWAH -01 No(ii) Digital Time switch three phase with suitable contactor 32A TP and controling MCB 32A TP for street lights.(iii) Digital Light sensitive Time switch single phase with MCB 16A SP for Aviation light.(iv) Suitable PTs for Panel meter -01sets(v) LED R-Y-B PHASE indicating lamp-01 sets.(vi) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled.
103Supply and fixing of Perforated Hot-Dip Galvanized (HDG) MS Cable Tray, fabricated from heavy-duty 12 SWG (2.5 mm) thick Mild Steel sheet. The tray shall have a nominal width of 150 mm and a flange height of 50 mm, with factory-punched slots for ventilation and cable ties. The entire assembly, including the matching 12 SWG removable top cover, shall be hot-dip galvanized after fabrication with a minimum coating thickness of 80–86 microns in accordance with IS: 2629, including Coupler Plates (Splice Plates) and hardware (GI bolts, nuts, and spring washers), 90-degree horizontal bends, vertical internal/external bends, and tees as required, wall-mounted cantilever brackets or ceiling-suspended threaded rod hangers, connecting to nearest earth terminal, complete all as specified and as directed.
104Supply, erection, testing, and commissioning of a 15-Meter High Mast Lighting System, fabricated from hot-dip galvanized high-tensile steel (conforming to IS: 2062/IS: 5986). The mast shall be a continuously tapered, polygonal cross-section (typically 20-sided), telescopically jointed, and designed to withstand wind speeds as per IS: 875 (Part 3), with specialized head-frame assembly suitable for mounting 6 to 9 LED lanterns in an asymmetrical configuration, Double-drum winch assembly, self-lubricating winch with a gear ratio of approximately 50:1, featuring a self-sustaining mechanism to prevent accidental descent, wire rope of Two-point suspension system using 6 mm dia Stainless Steel (SS) wire ropes (7/19 construction), ensuring high flexibility and corrosion resistance. Non-corrosive, large-diameter aluminum/nylon pulleys with stainless steel axles. with Non-corrosive, large-diameter aluminum/nylon pulleys with stainless steel axles and the the winch shall be operated on motorised mode with manual control. Including Integrated power tool for motorized operation (where specified) and a feeder pillar with timer-based controls, One LED Aviation Obstruction Light (Red) and a Single Spike Lightning Arrester at the top, connected to the mast body, Construction of a reinforced RCC Foundation (M30 grade) including anchor (J type) bolts, template, and all civil works to with stand an wind pressure of 150 km/Hr as per the manufacturer's structural design, heavy-duty trailing cable EPR/PCP sheathed flexible copper cables for the vertical run complete all as specified and as directed. Note: Submission of Site plan duly poisting Hight mast for approval of User through GE and submission of GA drawings and foundation details before placing order for approval of GE
105Supply and installation of LED Floodlight Luminaire, minimum 210 Watts, designed for heavy-duty outdoor applications. The fixture shall have a high-pressure die-cast aluminum housing with integrated advanced thermal management fins to ensure a long service life minimum 50,000 burning hours. The luminaire must be equipped with IP66 ingress protection and high-impact resistant toughened glass (minimum IK08 rating). It shall have multiple optics (asymmetrical or symmetrical beam angles) to provide uniform illumination without glare. The internal high-efficiency LED Driver shall be rated for 230V AC, with integrated surge protection (minimum 10 kV) and short-circuit protection. The housing must be treated with a salt-spray resistant, anti-corrosive powder coating including mounting on high-mast carriages using a heavy-duty MS 'U' bracket, stainless steel hardware, and all necessary electrical connections complete as specified and directed by the Engineer-in-Charge.
106LAN NETWORK CONDUIT AND SOCKETSSupply and fixing of RJ-45 (LAN) I/O Socket Outlet (1 Module), conforming to Category 6 (Cat 6) standards for high-speed data transmission up to 1000 Mbps. The outlet shall feature a high-impact, flame-retardant polycarbonate body and gold-plated (50-micron) phosphor bronze contacts to ensure low contact resistance and protection against atmospheric corrosion. The module shall include a clear labeling strip for identification. The rear shall feature tool-less or punch-down IDC (Insulation Displacement Contact) terminals color-coded for both T568A and T568B wiring standards. including mounting within a modular faceplate, complete as specified and directed by the Engineer-in-Charge.
107WATER COOLERSupply, installation, testing, and commissioning of an Industrial-grade Storage Water Cooler, fully constructed from Stainless Steel (SS 304) for both the external body and the internal storage tank to ensure hygiene and corrosion resistance. The unit shall have a storage capacity of approximately 80 Liters and a nominal cooling capacity of 40 Liters per hour (at ambient temperature). The system shall have high-efficiency, hermetically sealed compressor operating on Single Phase, 230V AC, 50Hz supply, using eco-friendly refrigerant (R-134a or equivalent), and an adjustable cold-water thermostat, brass chrome-plated taps, and a heavy-duty stainless steel drip tray with a flexible drainage outlet alongwith connection to the water supply using flexible SS braided hoses, and connecting to the electrical point at stabilizer with a 3-pin plug top as required complete all as specified and as directed by the Engineer-in-Charge.
108Supply and fixing of 1.0 kVA Automatic Voltage Stabilizer, single-phase, designed for indoor installation with Natural Air Cooling (Dry Type) with microprocessor-controlled or relay-operated, capable of handling an input voltage variation from 170V to 250V AC, and delivering a stabilized output of 230V AC with an accuracy of ±2.5%. The stabilizer shall be made up of high-grade copper-wound toroidal or E-I core transformers for low-loss operation. Protection features must include High-Voltage Cut-off, Low-Voltage Cut-off, and Thermal Overload Protection. The front panel shall be equipped with LED indicators for 'Mains On', 'Output On', and 'High/Low Cut-off' status alognwith 3-pin plug-top for input, and a 15A/5A socket for output connection complete all as specified and directed by the Engineer-in-Charge
109Supply and fixing of LED Aviation Obstruction Light (Type A/B Low Intensity), featuring an integral design with a weather-proof Die-cast Aluminum Housing (IP-65/66 rated) and a UV-stabilized polycarbonate lens. The light source shall consist of high-intensity, long-life LEDs with a luminous intensity conforming to ICAO (International Civil Aviation Organization) Annex 14 standards. The system shall be controlled by a dedicated SPN DB 4-Way Double Door type. The DB shall be pre-wired and fitted with one 10A DP MCB and one 24-hour Analog Timer Switch (1 Module) for automatic dusk-to-dawn operation inclduing the supply of mounting brackets, G.I. conduit/pipe for cable protection, and all necessary electrical connections from the DB to the aviation light using 2.5 sq.mm FRLS copper cable complete as specified and directed by the Engineer-in-Charge.
110FIRE FIGHTINGSupply, installation, testing, and commissioning (SITC) of a 2-Loop Analog Addressable Fire Alarm Control Panel (FACP), fully complying with BS EN 54-2 and BS EN 54-4 standards. The panel shall be equipped with an integrated Switch Mode Power Supply (SMPS), automatic battery charger, and 24-hour battery backup (VRLA type). The FACP shall support up to 200 devices per loop (any combination of detectors and modules) with a total capacity of 99 detectors and 99 modules per loop. The user interface shall feature a high-resolution 160 to 240 character LCD display and tactile touch keys for system navigation. Advanced features include networking capability via RS-485 or TCP/IP for multiple panels or repeater/mimic connectivity, and a minimum USB 2.0 interface for PC-based configuration and diagnostics. Critically, the panel must support a degraded redundancy operating mode, ensuring basic fire detection and alarm functionality even in the event of a main CPU failure along with necessary fixing arrangements, internal wiring, and programming of the cause, addressing of all detectors and effect matrix and Display instruction manual duly laminated in A3 size complete all as specified and directed.
111Supply, installation, testing, and commissioning of an Analog Addressable Repeater Panel, fully compatible with the 2-loop Main Fire Alarm Control Panel. The panel shall be powered by an integrated Switch Mode Power Supply (SMPS) with an automatic battery charger and VRLA battery backup. The interface shall have a large 6x40 character backlit LCD display, providing real-time status updates of the entire network. The panel shall include dedicated tactile controls for System Reset, Mute, Accept, Silence Alarms, and Self-Test, along with additional user-programmable function keys and Connectivity shall be established via 2 core copper cable or RS-485 or TCP/IP for seamless networking. Crucially, the panel must support degraded redundancy operating mode to maintain local functionality during a main CPU failure. The equipment shall be UL Listed or FM Approved and shall be installed at near fire station with all necessary fixing arrangements and making good disturbed areas complete all as specified and as directed.
112Supply, installation, testing, and commissioning of an Intelligent Addressable Manual Call Point, with an integrated Short Circuit Isolator (inbuilt isolator/turbo) for loop protection. The unit shall be designed for both flush and surface mounting, constructed from high-impact, flame-retardant ABS plastic in red. The MCP shall feature a 'Resettable' element or break-glass with a Test Key feature. The device shall have an ingress protection rating of IP44. ISI Marked (conforming to IS: 2189 / IS: 15908) and compatible with the analog addressable loop protocol including all mounting accessories, backboxes, and programming complete all as specified and directed by the Engineer-in-Charge.
113Supply, installation, testing, and commissioning of an Electronic Sounder cum Strobe (Horn-Strobe) unit, designed to provide both high-decibel audible and high-intensity visual notification during fire or emergency conditions. The Sounder shall be constructed from flame-retardant FR-ABS Plastic and finished in red. The strobe shall feature a high-intensity xenon or LED flash with a synchronized rate of 60 flashes per minute (1Hz) maintained over the entire operating voltage range. The sounder/horn shall provide a field-selectable sound output ranging between 80 dB to 100 dB at 1 meter. The unit shall operate on a nominal 24V DC supply and be designed for wall or ceiling mounting as per site complete all as specified and directed by the Engineer-in-Charge.
114Supply, installation, testing, and commissioning of an Intelligent Analog Addressable Multi-Sensor Detector, featuring a dual-chamber design for combined Optical Smoke and Heat detection. The detector shall be housed in a flame-retardant FR-ABS Plastic enclosure and must be type-certified to EN 54-5 and EN 54-7. The thermal element shall trigger an alarm upon reaching a Fixed Temperature of 59°C or when sensing a Rate-of-Rise (RoR) exceeding 7°C per minute. The detector shall include a sophisticated algorithm to analyze both signals to reduce false alarms.Including the supply of an Addressable Isolation Base to ensure loop integrity and shall bebe provided with Permanent Label Marking using a weather-resistant adhesive tag or engraved plate, clearly indicating the Loop Number, Zone Number, and unique Device Address for easy identification, The unit shall feature dual LEDs for 360° visual status indication complete as specified and directed by the Engineer-in-charge.
115Supply, installation, testing, and commissioning of an Intelligent Analog Addressable Heat Detector, featuring a high-sensitivity thermistor sensing circuit for early fire warning. The detector shall be housed in a low-profile, flame-retardant FR-ABS Plastic enclosure and must be type-certified to EN 54-5 (Class A1R). The detector shall provide dual-mode sensing, triggering an alarm upon reaching a Fixed Temperature of 59°C or when the temperature rise exceeds a Rate-of-Rise (RoR) of 7°C per minute including the supply and installation of an Addressable Isolation Base (conforming to EN 54-17) to ensure that a localized short circuit does not disable the entire loop and shall be provided with Permanent Label Marking using a weather-resistant adhesive tag or engraved plate, clearly indicating the Loop Number, Zone Number, and unique Device Address. The unit shall feature dual LEDs for 360° visual status indication complete as specified and directed by the Engineer-in-charge. Please Enable Macros to View BoQ information
116Supply, installation, testing, and commissioning of an Intelligent Analog Addressable Heat Detector, featuring a high-sensitivity thermistor sensing circuit for early fire warning. The detector shall be housed in a low-profile, flame-retardant FR-ABS Plastic enclosure and must be type-certified to EN 54-5 (Class A1R). The detector shall provide dual-mode sensing, triggering an alarm upon reaching a Fixed Temperature of 59°C or when the temperature rise exceeds a Rate-of-Rise (RoR) of 7°C per minute including the supply and installation of an Addressable Isolation Base (conforming to EN 54-17) to ensure that a localized short circuit does not disable the entire loop and shall be provided with Permanent Label Marking using a weather-resistant adhesive tag or engraved plate, clearly indicating the Loop Number, Zone Number, and unique Device Address. The unit shall feature dual LEDs for 360° visual status indication complete as specified and directed by the Engineer-in-charge. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57942188
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 26.60 Crore
LAST DATE 05-11-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Provision Of Technical Infrastructure And Associated Works For Technical Simulator Mh-60R At Niat, Kochi
Basic Detail
Tender No 891118
Bidding Type Tender
Location
City Ernakulam
State Kerala
Key Dates
Publish Date 09 Oct 2026
Submission Date 05 Nov 2026
Open Date 12 Nov 2026
Finance
Tender Value 26.60 Crore
Tender Fee 3000
EMD 15 Lakhs
Exemption Available
Document List
BOQ_889269.xls
c04ca14a-389e-4862-b227-27d91b0abc92.html
Dwg_merged.pdf
Prepriced_Sch.pdf
Tendernotice_1.pdf
Tender_2.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 09, 2026
11:30 IST

Tender Published

Tender notice published.

Today
Nov 05, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 27 days
Nov 12, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 34 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_889269.xls

html

c04ca14a-389e-4862-b227-27d91b0abc92.html

pdf

Dwg_merged.pdf

pdf

Prepriced_Sch.pdf

pdf

Tendernotice_1.pdf

pdf

Tender_2.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders