Tender For Repair/Maint And Replacement Of Lt Ug Cables, Acbs/Mccbs, Repair/ Maintenance Of Lt Panel Boards/ Feeder Pillar, Apfc Panels Etc. Incl Comprehensive Maintenance Of Apfc Panel And Connected Works At Sma Rameswaram Under Ge Fort Kochi
Tender Overview
Project Description
Tender for Repair/Maint And Replacement Of Lt Ug Cables, Acbs/Mccbs, Repair/ Maintenance Of Lt Panel Boards/ Feeder Pillar, Apfc Panels Etc. Incl Comprehensive Maintenance Of Apfc Panel And Connected Works At Sma Rameswaram Under Ge Fort Kochi
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 29-Oct-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 05-Nov-2026 |
| 2 | 05-Nov-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 10-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Material and Labour for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.3 mm thick buried directly in ground earth pit not less than 2.25 M deep below ground level with top edge of the plate not less than 1.5 M below normal ground level connected to galvanised strip of 25x4 mm by means of nuts, bolts, check nuts, washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part I of 2009 connected to earthing test point or disconnecting / testing link including excavation/ earth work in any strata, removal of surplus earth, GI pipe medium grade 20 mm for watering and funnel, GI Pipe light grade 40mm dia for earth lead protection, PCC 1:3:6 type C1 chamber with chamber cover in RCC 1:2:4 type B1 and taking down of existing earthing, complete all as specified and as directed. |
| 2 | Excavation in trenches not exceeding 1.50m wide and not exc 1.5m depth for foundation, laying of UG cables etc or for shafts, wells, cesspits, manholes, pier holes etc not excluding 10 Sqm on plan in hard/dense soil and getting out, complete all as specified and as directed. |
| 3 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25cm in any type of soil complete all as specified and as directed. |
| 4 | Removing surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point. complete all as specified and as directed. |
| 5 | Material and labour for sand cushioning to the full width of trenches for protection of cables including spreading and punning down including watering consolidation complete all as specified and as directed. Note: Punned thickness of riddled earth shall be measured and paid after cushioning. |
| 6 | Supply and lay sub class B burnt bricks as in cable protection, laid length of brick perpendicular to length of cable complete, all as specified and as directed. |
| 7 | Disconnecting and taking out old defective LT UG cable/ aluminium conductor of any size/type from trenches/ walls/ poles/ pipes complete, all as specified and as directed. |
| 8 | Supply, laying, jointing, connecting, testing underground XLPE insulated, PVC sheathed, armoured heavy duty electric LT cable,1100volts grade with aluminium stranded conductor,10sqmm 4 core, laid in trenches/fixed to poles/drawn through pipes with suitable size cable glands, crimping type cable lugs, sockets etc. and taking down the existing cable complete all as specified and as directed. |
| 9 | `-Ditto- all as per item No 8 but cable of size 16 Sqmm 4 Core all as specified and as directed. |
| 10 | `-Ditto- all as per item No 8 but cable of size 25 Sqmm 4 Core all as specified and as directed. |
| 11 | `-Ditto- all as per item No 8 but cable of size 35 Sqmm 3.5 Core all as specified and as directed. |
| 12 | `-Ditto- all as per item No 8 but cable of size 50 Sqmm 3.5 Core all as specified and as directed. |
| 13 | `-Ditto- all as per item No 8 but cable of size 70 Sqmm 3.5 Core all as specified and as directed. |
| 14 | `-Ditto- all as per item No 8 but cable of size 95 Sqmm 3.5 Core all as specified and as directed. |
| 15 | `-Ditto- all as per item No 8 but cable of size 10 Sqmm 2 Core all as specified and as directed. |
| 16 | `-Ditto- all as per item No 8 but cable of size 120 Sqmm 3.5 Core all as specified and as directed. |
| 17 | `-Ditto- all as per item No 8 but cable of size 150 Sqmm 3.5 Core all as specified and as directed. |
| 18 | `-Ditto- all as per item No 8 but cable of size 185 Sqmm 3.5 Core all as specified and as directed. |
| 19 | `-Ditto- all as per item No 8 but cable of size 240 Sqmm 3.5 Core all as specified and as directed. |
| 20 | Supply and laying PVC insulated and FR PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volt, conforming to IS 694 of size 2.5 Sqmm 2 Core complete including taking down old cable complete all as specified and as directed. |
| 21 | Supply, laying and fixing in replacement 100mm bore GI pipe light grade for necessary road crossing, culverts etc for cable protection complete all as specified and as directed. |
| 22 | Supply, laying and fixing in replacement 50mm bore GI pipe light grade for necessary road crossing, culverts etc for cable protection complete all as specified and as directed. |
| 23 | Supply, laying and fixing 40mm bore in replacement GI light grade for necessary road crossing, culverts etc for cable protection complete all as specified and as directed. |
| 24 | Supply and fix in replacement outdoor type FRP junction box of size 300x200x105mm, light weight suitable for pole mounting using clamps/bolts and nuts including MCB SP 6 Amps single pole including necessary connector for loop in loop out cable connection complete all as specified and as directed. |
| 25 | Supply and fix in replacement outdoor type FRP junction box of size 140x140x105 mm, light weight suitable for pole mounting using clamps/bolts and nuts including MCB SP 6 Amps single pole including necessary connector for loop in loop out cable connection complete all as specified and as directed. |
| 26 | Supply and fix in replacement 25 x 4 mm GI strip as earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required complete all as specified and as directed. |
| 27 | Material and labour for painting on old surfaces of LT panel any type any size by spray paint after cleaning strains and grease/oil spots with sand paper & thinner and painting the cleaned surface with synthetic enamel paint of existing colour to achieve good finish by applying two coats of paints by spray painting machine carefully after disconnection the power supply and covering the meters, indicators and switches to prevent from fall of paint drop on them all as specified and as directed. |
| 28 | Supply and jointing as in repairs straight through joint, outdoor type 1100 volts grade, heat shrinkable type suitable for 3.5 core, 240 Sqmm to 300 sqmm LT, XLPE cable and testing after jointing complete all as specified and as directed. |
| 29 | `-Ditto- all as per item No.28 above but straight through joint suitable for size of 3.5 core, 150 Sqmm to 185 sqmm LT, XLPE cable. |
| 30 | `-Ditto- all as per item No.28 but straight through joint suitable for size of 3.5 core, 70 Sqmm to 120 sqmm LT, XLPE cable. |
| 31 | `-Ditto- all as per item No.28 but straight through joint suitable for size of 3.5 core, 25 Sqmm to 50 sqmm LT, XLPE cable. |
| 32 | `-Ditto- all as per item No.28 but straight through joint suitable for size of 2/4 core, 10 to 16 Sqmm LT XLPE cable. |
| 33 | Supply and jointing in repairs end termination, outdoor type 1100-volts grade heat shrinkable type suitable for 70 to 120 Sqmm LT XLPE 3.5 core cable and testing after jointing complete all as specified and as directed. |
| 34 | Supply and jointing in repair end termination, outdoor type 1100-volts grade heat shrinkable type suitable for 240 to 300 Sqmm LT XLPE 3.5 core cable and testing after jointing complete all as specified and as directed. |
| 35 | Supply and fix in replacement of aluminium crimping type lugs of size 10 Sqmm to 25 sqmm complete all as specified and as directed. |
| 36 | Supply and fix in replacement of aluminium crimping type lugs of size 35 sqmm to 50 sqmm complete all as specified and as directed. |
| 37 | Supply and fix in replacement of aluminium crimping type lugs of size 70 sqmm to 95 sqmm complete all as specified and as directed. |
| 38 | Supply and fix in replacement of aluminium crimping type lugs of size 120/150/180 sqmm complete all as specified and as directed. |
| 39 | Supply and fix in replacement of aluminium crimping type lugs of size 240/300 sqmm complete all as specified and as directed. |
| 40 | Material and labour for detecting cable fault of size up to 240Sqmm LT, XLPE cable by means of fault-finding machine/ manual including excavation or earth work if required at site complete, all as specified and as directed. |
| 41 | Material and labour for PCC (1:3:6), Type C-1, (using 20 mm graded stone aggregate) as in coping and the like including weathering, slightly rounded or chamfered angles and throating including formwork [straight or curved] complete all as specified and directed. |
| 42 | Material and labour for repairing the existing LT Panel/ feeder Pillar Box any type or size by taking proper shutdown, disconnecting and reconnecting cables, welding/drilling for smooth functioning of panel door, locking arrangement complete all as specified and as directed. |
| 43 | Supply and fix in replacement 3 phase VAF + PF meter type having accuracy class 1, range up to 50-400 Amps with selectable CT secondary site 1A/5A, complete, all as specified and as directed. |
| 44 | Supply and fix in replacement indicating lamps LED type set (R, Y, B) complete, all as specified and as directed. |
| 45 | Supply and fix in replacement selector switch complete, all as specified and as directed |
| 46 | Supply and fix in replacement CT Coil suitable 250/5A for different load all complete, as specified and as directed. |
| 47 | Supply and fix in replacement spreader terminals suitable for MCCB of capacity 200A to 250A complete, all as specified and as directed. |
| 48 | Supply and fix in replacement of Analog timer switch programmable with 16A current carrying capacity suitable for mounting on DIN rail complete all as specified and as directed. |
| 49 | Supply and fix in replacement of 4 pole contactor 250 A 2 NO +2 NC complete all as specified and as directed. |
| 50 | Disconnecting the existing unserviceable MCCB from panel board after disconnecting cable and supply & fix new MCCB 63A, 4 Pole, 16 KA, adjustable, fixed in existing panel including modification of existing frame and panel board door for proper installation of MCCB and connecting with existing cable including thimble, nut bolt and washers etc. complete, all as specified and as directed. |
| 51 | `-Ditto- all as per item No 50 above but of 100A, 4 Pole, 16 KA all as directed and as specified. |
| 52 | `-Ditto- all as per item No 50 above but of 100A, 3 Pole, 16 KA all as directed and as specified. |
| 53 | `-Ditto- all as per item No 50 above but of 125A, 4 Pole, 16 KA all as directed and as specified. |
| 54 | `-Ditto- all as per item No 50 above but of 160A, 3 Pole, 16 KA all as directed and as specified. |
| 55 | Disconnecting the existing unserviceable MCCB from panel board after disconnecting cable and Supply & fixing new MCCB 200A, 25 KA 4 Pole fixed in existing panel including modification of existing frame and panel board door for proper installation of MCCB and connecting with existing cable including thimble, nut bolt and washers etc complete, all as specified and as directed. |
| 56 | `-Ditto- all as per item No 55 above but of 250A, 4 Pole 25 KA all as directed and as specified. |
| 57 | `-Ditto- all as per item No 55 above but of 400A, 4 Pole 25 KA all as directed and as specified. |
| 58 | Cleaning and maintaining of surrounding areas of LT panel by cutting bushes/plants including internal cleaning throughout the contract, etc all as specified and as directed. |
| 59 | Supply and fix in repairs Rotary handle suitable for MCCBs of capacity up to 630 Amps all as specified and as directed |
| 60 | Material and labour for replacement of all internal wiring in 290 KVAR capacity APFC panel board of Make: ABB using colour-coded FRLS copper wires, properly linking all contactors, capacitors, voltmeters, ammeters, MCCBs, indicators, and incoming/ outgoing power supply, including neat arrangement, secure fixing, and testing for proper operation, all as specified and as directed. Note: Power contactors, capacitors, ammeters, and voltmeters shall be measured and paid separately. |
| 61 | Material and labour for comprehensive maintenance of 08 Nos Automatic Power Factor correction capacitor banks, 40 to 290 KVAR including repair/replacement of defective/un-serviceable parts during maintenance period, attending to breakdown as and when it occurs, necessary periodical checking twice in a month and testing of capacitor banks as per manufacture's instruction for smooth and efficient functioning of capacitor panels, installed at various Sub Stations and Power Houses. Note: - Spare parts shall be measured and paid separately. |
| 62 | Notes: -(i) The Power Factor should always be maintained more than 0.95.(ii) If the Power Factor comes below 0.95 up to 0.90, a penalty of Rs.1000.00 per HT connection will be recovered from the payment.(iii) If KSEB imposes any penalty due to low power factor than 0.90 then double the amount will be recovered from the contractor as penalty for non-functioning of panel.(iv) The rate quoted shall be deemed to be included the charge for taking out defective spares & fixing of new spares and tightening of cables & accessories etc.(v) Cost of spares required for replacing shall be measured and paid separately.(vi) 2 jobs x 11 Months = 22 Jobs (The above job shall be carried out and measured 2 times per month for entire installation at SMA Rameswaram |
| 63 | Supply only 10 KVAR Capacitor, HD Gas filled cylindrical, 3 phase, 440 Volt AC having low watt loss of not less than 0.5 W/KVAR all as specified and as directed. |
| 64 | Supply only 25 KVAR Capacitor HD Gas filled cylindrical, 3 phase, 440 Volt AC having low watt loss of not less than 0.5 W/KVAR all as specified and as directed. Make L&T Cat Part: - LTCCN325B2/ equivalent as approved by GE. |
| 65 | Supply only 12.5 KVAR Capacitor box type Heavy Duty, 3 phase, 440 Volt AC having low watt loss of not less than 0.5 W/KVAR, all as specified and as directed.Make- ABB/ equivalent as approved by GE |
| 66 | Supply only volt meter suitable for 290 KVAR APFC Panel board, Voltage Range Up to 750V AC, accuracy Class 1.5 suitable for existing make MECO-G S196 all as specified and as directed. |
| 67 | Supply only Contactor for 12.5KVAR Rating capacitor switching, all as specified and as directed. Make: ABB Cat part No. UA16-30-10RA / equivalent as approved by GE. |
| 68 | Supply only Contactor for 20 KVAR Rating capacitor switching, all as specified and as directed. Make: ABB Cat part No. UA26-30-10RA / equivalent as approved by GE. |
| 69 | Supply only Contactor for 25 KVAR Rating capacitor switching, all as specified and as directed. Make: ABB Cat part No. UA30-30-10RA / equivalent as approved by GE. |
| 70 | Supply only Microprocessor based APFC relay, 14/12 stage, all as specified and as directed. Make: L&T / Siemens / ABB / Shneider |
| 71 | Supply only flush head 230 Volt AC Push Button, all as specified and as directed. |
| 72 | Supply only Amp Meter suitable for 290 KVAR APFC Panel, all as specified and as directed. Make: - Schneider Electric Conzerv DM1110 / equivalent as approved by GE. |
| 73 | Supply only MCCB 630Amps, 3 pole, 35kA at 415Volt, all as specified and as directed. Make ABB, SACE S5N / equivalent as approved by GE Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 1 dayBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender