Tender For Provn Of Split Acs With Connected Items For Ol Confrence Hall At Hqsc Under Ge (North) Pune
Tender Value
4.79 Lakhs
Estimated cost
Bid Submission
29 Oct 2026
15 days left
EMD
9580
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Pune → Maharashtra
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provn Of Split Acs With Connected Items For Ol Confrence Hall At Hqsc Under Ge (North) Pune
BOQ
| Sl. No. | Item Description |
| 1 | Supply and Installation, commissioning of Inverter type wall mounting air cooled split type unit air conditioner electric driven single phase indoor unit and outdoor unit with cordless remote control unit and with in built airioniser and plasma filter for better indoor air quality cutting,brazing and connecting the copper pipe of size 1/2 inch and 1/4 inch size of pipe and making holes as for passing of copper pipes and electric cables and pressure testing with nitrogen and freon gas vacumising the system and charging the Non CFC refrigerent and testing the complete system for smooth functioning of split AC up to satisfactioning, above 3 star rating, confirming to IS-1391 Para II 1992 herimatically sealed air compressor working with Non CFC refrigerent suitable for wall mounting 4500 K cal/ hrs 2 Ton complete with stand for fixing on wall/ground all as specified and directed. |
| 2 | S & F for copper tubing of size 3/8” for discharge line any make of split AC of capacity 2 ton with insulation sheet of pipe tube type insulation including removal of old existing unsv one complete all as specified and directed. |
| 3 | S & F for copper tubing of size 5/8” for discharge line any make of split AC of capacity 2 ton with insulation sheet of pipe tube type insulation including removal of old existing unsv one complete all as specified and directed. |
| 4 | Supply and fixing copper cable 2.5 sqmm x 4 core for out door to indoor connection of split Acs complete all as specified and directed. |
| 5 | S & F for flexible PVC pipe 15mm dia heavy duty from outdoor unit to indoor unit for drain of water including clamping to the wall and brought down up to ground level (-1 Mtr) complete all as specified and directed. |
| 6 | S & F for new powder coated Mild Steel fabricated stand suitable for outdoor unit of Split AC of 1.5/ 2 TR to install outdoor unit on wall/ floor as required on site with legs and bracing complete all as specified and directed. |
| 7 | Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, CPRI Approved as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (50 x 10 mm ) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: Note : CPRI approved of makes approved by CEPZ. |
| 8 | Incoming |
| 9 | (a) MCCB, 4 Pole, 415 Volts, 250 Amp, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu -01 No |
| 10 | (b) Alum bus bar (50 x 10 mm) 500 Amps TPN -01 Set |
| 11 | (c) Digital Voltemeter 0-500 volts with selector switch - 01 No |
| 12 | (d) Digital Amp meter 0-200 Amp with selector switch - 01 No |
| 13 | (e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set |
| 14 | Outgoing |
| 15 | (a) MCCB 3 pole, 100 Amp,adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos |
| 16 | (b) MCCB 3 pole, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 01 Nos |
| 17 | (c) Provision for space to be kept blank for fixing of MCCB - 01 No |
| 18 | Note :- Installation, testing, commissioning and connecting of incoming and outgoing cables connections LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Glands, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts. |
| 19 | Note : 1. Performance security:- Refer Condition 22 of Special Conditions. 2. Quoted Contract Sum shall be arrived at after deducting the amount of Credit Schedule (refer Schedule of Credit in pdf form for quantity, rate and amount etc.) for old unserviceable materials retrieved from site. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 08, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 29, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 15 daysNov 05, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 22 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender