Tender For Augmentation Of Electricity Supply At Md Accn (Jcos/Or) Of Mil Stn Haldwani Under Ge Ranikhet
Tender Value
43.65 Lakhs
Estimated cost
Bid Submission
29 Oct 2026
12 days left
EMD
87300
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Nainital → Uttarakhand
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Augmentation Of Electricity Supply At Md Accn (Jcos/Or) Of Mil Stn Haldwani Under Ge Ranikhet
BOQ
| Sl. No. | Item Description |
| 1 | Supply, installation, testing and commissioning of transformer suitable for 250 KVA step down floor mounted out door type, 11/0.433 KV, 3 phase, 50 Hz AC double wound core type, with energy efficiency level -3 as per IS 1180 : 2014 (Part I ), copper wound, oil immersed, air naturally cooled with external cooling tubes, transformer delta connection on HV side and star connected on LV side in accordance with vector symbol Dyn-11 (vector group 4) with neutral brought out on LV side with earthing and having tapping on HV side for constant out put so as to alter/vary secondary voltage by + 7.5% in equal sep of 2.5% changed by means of manually operated \\"Off Load\\" taps changing gear. The voltage regulation shall be as per IS including first fill of transformer oil as per IS-335 and including all fittings/accessories as specified in SSR Part-I and IS-1180. The limit of temperature rise after continuous full load run as specified in IS-1180 shall be suitably adjusted to suite the maximum ambient temperature of Haldwani. The transformer shall be complete with the following fittings and accessories :- (a) Oil conservator tank with fillings holes and cap filter type drain valve and oil level gauge.(b) Silica gel breather with connecting pipe, first fill of dehydrating agent.(c) Explosion relief mounted on tank with double diaphragm and equalizer pipe connected to conservatore air tank (pressure release valve).(d) Air release valve plug.(e) One cable box on LV side (Secondary) consisting of 04 Nos porcelain bushing with nuts, washers & bushing rods with 01 cable gland suitable for reception of taking out suitable size cable, including gland joints complete all as specified.(f) Explosive vent.(g) 01 No 100 mm dial type thermometer vapour pressure type having range 0-120 degree centigrade with max temp indicator and resetting device incl, max reading pointer washer etc.(h) Thermometer pocket on tank cover(j) 04 Nos plain solid CI detachable rollers.(k) Two Nos earthing terminals marking plate.(l) Rating plate and terminal marking plate (m) Extra bushing for neutral outside the cable box brought on LV side.(n) First filling of oil conforming to IS and tested up to 60 KV dielectric strength.(o) Lifting lugs(p) Oil drain valve with plug. (q) One cable box on HV side (Primary) consisting of 01 cable gland suitable for reception of taking in HT cable including gland joints complete all as specified.(r) Dehydrating breather with first filling of dehydrating agent.(s) Two earthing terminal on tank body to facilitate fixing of 32x6mm GI Strip.(t) Rating plate with terminal marking plate.(u) Inspection cover.(v) Extra bushing for neutral out side the LV side.(w) Hand hole of sufficient size to access interior of tank.Note :- Transformer shall be fixed on PCC platform with including PCC 1:3:6 type C 2 with 40mm graded stone aggregate of size 2.80x2.80x1.20 mtrs high or including necessary foundation work of appropriate size as directed or as per manufactures recommendation. Concrete to be deemed its above said items. |
| 2 | Supply, laying, jointing, commissioning and testing XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured electric cable in trenches on poles/through duct, (Heavy duty) with std aluminium conductor, 11/6.35KV (UE) grade of size 95 Sqmm 3 Core. |
| 3 | S&F cable jointing kit for 11 KV (Earthed) grade cable for out door termination heat shrincable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete. |
| 4 | Supply and laying cable PVC insulated PVC sheathed, galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 core. |
| 5 | -do- but 185 Sqmm 3.5 core. |
| 6 | -do- but 240 Sqmm 3.5 core. |
| 7 | -do- but 70 Sqmm 3.5 core. |
| 8 | -do- but 16Sqmm 4 core. |
| 9 | -do- but 25Sqmm 4 core. |
| 10 | -do- but 10Sqmm 4 core. |
| 11 | Excavation in trenches not exceeding 1.5 mtr wide, depth exceeding 1.5 mtr and getting out in hard/dense soil complete all as specified and directed by Engineer-in-charge |
| 12 | Returning, filling incl spreading, levelling, watering and well ramming in layers not exc 25 cm in hard/dense soil all as specified and directed. |
| 13 | Removing excavated material (soil) not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed. |
| 14 | M&L for dry clean sand filling in trenches below and around under ground cable cushioning complete all as specified and directed.. Note :- Thickness of sand cushioning shall be measured after punning. |
| 15 | M&L for brick sub class 'B' for protection of cable comlete all as specified and directed. |
| 16 | Supply and fix unreinforced PCC cable cover class LV type I of size 0.25x0.15x0.04mm |
| 17 | M&L earthing complete as per electrical plate No. 3 of MES SSR Part-I with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, buried directly vertically in ground in a pit of depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less then 1.5 metre below normal ground level connected to and including galvanised iron earth strip 32mm x 6mm by means of bolts, nuts check nuts and washers of galvanised iron. Earthing strip shall be protected by galvanised iron or steel pipe 40 mm bore light grade and connected to continuous earth strip on test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & directed followed by painting the earth test result at appropriate place. |
| 18 | Supply, install, testing and commissioning and testing factory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compartmantalised and IP-65 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openiable hinged double door shuters with aprons for cable entry and locking arrangement complete: Incoming- (a) MCCB 400 amps, 4 pole, 50Hz ,415 V with rupturing capacity 35 KA-01 No (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 800Amp, 4 pole, not less than 30cm long mounted on insulators for incomming supply 01 No. (c) Digital Load manager multy functional energy meter having facility to measure true RMS value, KWH, neutral current, for quadrant energy, max demand (KW, KVA, Kvar & Amp), CT operated 415 volts, 50 Hz AC supply including CTs. -01 set. Make : L&T Cat Part No WDM303FDN B1 (d) Neon indicating lamps (R, Y & B) -01 Set. (e) On load Change over Switch 400 amps, 4 pole,-01 No. Outgoing- (a) MCCB 315 amps, 4 pole,35 KA (Icu = 100% Ics), with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 03 Nos. (b) MCCB 100amps, 4 pole, 25 KA , with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 No. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation and connected earth work. (ii) Panels shall be placed above 0.6 mtr of ground level (iii) Outgoing MCCBs shall be fed with solid busbar connectors. (iii) Cables shall be terminated using through Cable end Joints as per Cap or size of cable. |
| 19 | M&L for plinth of transformer with,PCC Foundation commissioning and testing including connection with arranging vechicle ,necessary crane or chain pulleys arrangements etc , making good the damages etc as reqd and installation, including connecting up electrically, commissioning at site all as directed by Engineer-in-Charge. |
| 20 | M & L PCC (1:3:6) type C-2 using 40 mm graded stone aggregate for foundation of as in transformer plinth complete all as specified and directed. |
| 21 | M & L for PCC (1:2:4) type B-1 using 20 mm graded stone aggregate as in transformer plinth as per site requirment including necessary form work complete all as specified and directed. |
| 22 | M&L for brick work with fly ash bricks one brick thick honey comb walling built in cement mortar 1:4 complete all as specified and directed at site. |
| 23 | M& L for Rendering 10mm thick on fair faces of brick work or concrete surfaces plaster 1:3 Cement plaster complete all as specified and directed at site. |
| 24 | M& L for Hard core, broken stone/ boulders to gauge n exc 63 mm complete all as specified and directed at site. |
| 25 | M& L white wash in new walls surfaces with two coat white wash all as specified and directed at site |
| 26 | Taking down old unserviceable ACSR conductor from LT pole all as specified and directed by Engr-in- Charge |
| 27 | Dismantling cross - arms of MS channel or angle sections etc complete and stacking all as specified and directed by Engr-in- Charge |
| 28 | Supply S/F pole mounting box / junction box made out of 1.66mm thick MS CRCA sheet of size 200 x150 x 100mm complete suitable for three phase connection with clamps of flat iron/GI off size 25 x 4 mm including suitable size nut, bolts, washer etc to fix on ole and provide with hinged door and locking system all painted with two coats of synthetic enamel paints over one coated red oxide paint all as specified and directed by Engr-in- Charge |
| 29 | S/F connecting and testing cable PVC insulated unarmoured and PVC sheathed 1100V grade with copper conductor of size 1.5 Sqmm 3 core from looping box to street light fitting complete all as specified and directed. |
| 30 | S&F LT cable route indicator |
| 31 | M&L for Cutting road for laying cable and making good the same after laying cable |
| 32 | S/F heat shringable Straight through LT epoxy based Cable joint Suitable for LT U/G Cable of size 3 1/2 Core X 50 Sqm to 3 1/2 core X 95 sqmm. |
| 33 | S/F heat shringable Straight through LT epoxy based Cable joint Suitable for LT U/G Cable of size 3 1/2 Core X16 to 35 Sqmm to 3 1/2 Core |
| 34 | Supply and lay GI pipe light grade with all fittings required for protection of under ground cable including suitable size of FI clamp. (a) 50mm dia |
| 35 | (b) 40mm dia |
| 36 | supply, install, test and commission outdoor busbar box, type cubical panel board outer shell, made out of 3.15mm thick MS sheet and inner shell made out of 2mm thick MS sheet and MS angle section 50x50x6mm fixed on transformer front door openable, lockable with keys, louvers and air vent gasket for natural flow of air 'U' type. Gasket shall be used to make the outer shell completely vermin proof, suitable for 3 phase 4 wire 415 volts, 50 Hz with modern fabrication and painting with two coats of synthetic enamel paint over a coat of primer, fixed on transformer by welding or with the help of nut, bolts as per site requirement complete with consisting of the following :- (a) TPN Aluminium bus bar 300 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insualtors including M & L for aluminium bus bar for taking connection from transformer bush rod to main bus of panel including nut bolt and washers etc.(b) MCCB 100 Amps 25 KA, 415 Volts, 50 Hz, TP - 01 No(c) RYB indication lamp - 01 set |
| 37 | -ditto- but of the following specifications :-(a) TPN, Aluminium bus bar 400 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators including M & L for aluminium bus bar for taking connection from transformer bush rod to main bus bar of panel including nut bolt and washers etc.(b) MCCB 160 Amps 25 KA, 415 Volts, 50 Hz, TP - 01 No(c) RYB indicating lamp - 01 set |
| 38 | -ditto- but of the following specifications :-(a) TPN, Aluminium bus bar 600 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators including M & L for aluminium bus bar for taking connection from transformer bush rod to main bus bar of panel including nut bolt and washers etc.(b) MCCB 200 Amps 25 KA, 415 Volts, 50 Hz, TP - 01 No(c) RYB indicating lamp - 01 set |
| 39 | -ditto- but of the following specifications :-(a) TPN, Aluminium bus bar 600 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators including M & L for aluminium bus bar for taking connection from transformer bush rod to main bus bar of panel including nut bolt and washers etc.(b) MCCB 250 Amps 25 KA, 415 Volts, 50 Hz, TP - 01 No(c) RYB indicating lamp - 01 set |
| 40 | -ditto- but of the following specifications :-(a) TPN, Aluminium bus bar 600 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators including M & L for aluminium bus bar for taking connection from transformer bush rod to main bus bar of panel including nut bolt and washers etc.(b) MCCB 250 Amps 35 KA, 415 Volts, 50 Hz, 04 pole- 01 No(c) RYB indicating lamp - 01 set |
| 41 | -ditto- but of the following specifications :-(a) TPN, Aluminium bus bar 400 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators including M & L for aluminium bus bar for taking connection from transformer bush rod to main bus bar of panel including nut bolt and washers etc.(b) MCCB 400 Amps 35 KA, 415 Volts, 50 Hz, 04pole- 01 No(c) RYB indicating lamp - 01 set |
| 42 | M&L for earthing complete with galvanised steel, earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtrs below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron/steel all as shown in in electrical plate No 5 on page 19-49 of MES schedule 1991 Part I connected to main switch board /main DBs/ earthing test point Including all necessary excavation and earth work in hard/ dense soil common salt and charcoal dust mixed and packed 150 mm thick all-round the GI earth plate, watering pipe 20 mm dia G I medium grade . GI sheet 0.63 mm thick funnel, wire gauge, 50mm thick RCC cover in PCC 1:2:4 type B1 duly reinforced with MS round bars 6mm dia @ 150C/C both ways and pit/ chamber in PCC 1:3:6 type C1 with suitable lifting handle to cover, GI protection pipe 25mm dia light grade up to 7.5m from complete all as specified ,indicated on electrical plate No 5 and as directed incl testing on completion.NOTE: ( i ) Earth lead beyond 7.5 m from electrode to earth terminal GI pipe light grade 25mm/40mmdia for protection against mechanical damage to lead shall be measured separately (ii) On testing after completion if desired earth resistance is not obtained, the earthing will be redone at no extra cost. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 08, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 29, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 12 daysNov 05, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 19 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender