Tender For Repair / Replacement Of Oh Lt Acsr Conductor With Ug Xlpe Lt Cable And Connected Items At Domestic Area And Tech Area Of Air Force Station Yelahanka.
Tender Value
40 Lakhs
Estimated cost
Bid Submission
28 Oct 2026
20 days left
EMD
80000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Bengaluru Urban → Karnataka
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair / Replacement Of Oh Lt Acsr Conductor With Ug Xlpe Lt Cable And Connected Items At Domestic Area And Tech Area Of Air Force Station Yelahanka.
BOQ
| Sl. No. | Item Description |
| 1 | Dismantling existing ACSR (of any size or type) from over head electric line carefully without making any damage to the other existing lines and removing from site complete all as specified and as directed. |
| 2 | Dismantling of insulator any type /size/ grade from over head electric line and setting aside removing from site complete all as specified and as directed. |
| 3 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes, foundation for poles etc., and getting out in hard/dense soil all as specified and as directed. |
| 4 | Returning filling in excavated soil upto a depth of 30 cm after riddling of excavated soil (in lieu of sand) for cushioning of cable and refilling of trenches with left over normal excavated soil including spreading, leveling, watering and well ramming in layers complete all as specified and as directed. |
| 5 | Removing surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point as directed. |
| 6 | Supplying and laying un-reinforced precast concrete cable cover, class LV, Type 1 with peak, size 250 mm x 150mm x 40mm all as specified and as directed. |
| 7 | Supply and laying in trenches, LT underground cable of size 10 Sqmm 2 core XLPE insulated armoured and PVC sheathed 1100 Volts grade with aluminium conductor multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, roof, ducts and fixing using clamps, saddle for pole, wall including taking down complete all as directed. |
| 8 | All as per item No 7 here-in-before but 16 Sqmm 4 core |
| 9 | All as per item No 7 here-in-before but 25 Sqmm 3.5 core |
| 10 | All as per item No 7 here-in-before but 35 Sqmm 3.5 core |
| 11 | All as per item No 7 here-in-before but 70 Sqmm 3.5 core |
| 12 | All as per item No 7 here-in-before but 95 Sqmm 3.5 core |
| 13 | All as per item No 7 here-in-before but 120 Sqmm 3.5 core |
| 14 | All as per item No 7 here-in-before but 240 Sqmm 3.5 core |
| 15 | All as per item No 7 here-in-before but 300 Sqmm 3.5 core |
| 16 | M & L for boring of holes under roof, pavement, hardstanding by trenchless technology and necessary machine including GI pipe of 50/80/100mm dia suitable for 0.4mpa working pressure complete all as specified and as directed. |
| 17 | Supply and laying GI tubing light grade 50mm dia in trenches/fixing on pole /wall/crossing in drain etc. for protection of UG cable complete all as specified and as directed. |
| 18 | Supply and laying GI tubing light grade 80mm dia in trenches/fixing on pole /wall/crossing in drain etc. for protection of UG cable complete all as specified and as directed. |
| 19 | Supply and fix in repair 63 Amp rating, 415V, 10KA 'C' curve miniature circuit breaker (MCB) of four pole in the MCB DB complete with connection testing and commissioning complete all as specified and directed. |
| 20 | Supply and fix in repair 32 Amps rating, 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of Single Pole and Neutral, in the MCB DB Complete with connection testing and commissioning complete all as specified and directed. |
| 21 | Supply and fix cable route indicator made out of 3 mm thick MS sheet of size 20 cm x 15 cm duly painted with two coats black paint over a coat of red oxide primer and writing cable direction, capacity, size of cable with white paint, mounted on angle iron 40x40x3 mm, angle height 45 cm, (30cm below ground level) with PCC 20cmx20cmx15cm all as specified and as directed. |
| 22 | Supply, installation and commissioning in repair LT out door loop in loop out terminal box with sloping canopy of size 600x450x250mm made out of 3 mm thick CRCA sheet duly painted with two coars of synthetic enamel paint over a coat of rex oxide, front and rear hinged doors mounted on 40x40x6 mm MS angle iron frame 90 cms height erected in ground with PCC foundation 1:4;8 with 40mm stone aggregate including supply and fixing insulated aluminium bus bar of size 50x 6mm for three phase and neutral 300mm length suitable for 8 outgoings respectively mounted on insulators and terminating with suitable cable with glands and provision of one MCCB 63 Amps 4 pole ,415 Amps, 50 Hz of breaking capacity 16 KA as incomer with RYB Indicator, including taking down old terminal boxes complete all as specified and directed. |
| 23 | Supply, installation and commissioning in repair LT out door loop in loop out terminal box with sloping canopy of size 600x450x250mm made out of 3 mm thick CRCA sheet duly painted with two coars of synthetic enamel paint over a coat of rex oxide, front and rear hinged doors mounted on 40x40x6 mm MS angle iron frame 90 cms height erected in ground with PCC foundation 1:4;8 with 40mm stone aggregate including supply and fixing insulated aluminium bus bar of size 50x 6mm for three phase and neutral 300mm length suitable for 8-10 outgoings respectively mounted on insulators and terminating with suitable cable with glands and provision of one MCCB 125 Amps 4 pole ,415 Amps, 50 Hz of breaking capacity 25 KA as incomer, RYB indicator for incoming including taking down old terminal boxes complete all as specified and directed. |
| 24 | Supply, install, testing and commissioning of LT Panel board CPRI approved outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars duly insulated by insulation of RYB colour 500 Amps rating mounted on porcelain insulators .The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 50X50X5 mm duly embedded in PCC platform and duly powder coated with 7 tank process with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable all as directed at site and comprising of the following: (Security section ) INCOMING MCCB 4 pole 315 Amps 35 kA - 01 Nos OUTGOING MCCB 4 Pole 200 Amps 35 kA - 01 Nos MCCB 4 pole 125 Amps 25 kA - 02 Nos MCCB 3 pole 63 Amps 16 kA - 02 Nos Multifunctional VAF meter, PF meter - 1 No RYB Neon indicating lamp -1 set of three MS work incl angle iron frame and PCC work Internal wiring including copper lugsNote: Bottom portion of the Panels should minium 45 cmm above the ground level |
| 25 | Supply, install, testing and commissioning of LT Panel board CPRI approved outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars duly insulated by insulation of RYB colour 300 Amps rating mounted on porcelain insulators .The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 50X50X5 mm duly embedded in PCC platform and duly powder coated with 7 tank process with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable all as directed at site and comprising of the following: INCOMING:-MCCB 4 pole 125 Amps 25 kA - 01 Nos OUTGOING:- MCCB 4 pole 100 Amps 25 kA - 01 Nos MCCB 4 pole 63 Amps 16 kA - 03 Nos MCB DP 32 Amps 10 kA - 01 Nos Multifunctional VAF meter, PF meter - 1 No RYB Neon indicating lamp -1 set for incoming MS work incl angle iron frame and PCC work Internal wiring including copper lugs |
| 26 | Supply, install, testing and commissioning of LT Panel board CPRI approved outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars duly insulated by insulation of RYB colour 300 Amps rating mounted on porcelain insulators .The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 50X50X5 mm duly embedded in PCC platform and duly powder coated with 7 tank process with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable all as directed at site and comprising of the following: INCOMING :-(a) 4 Pole MCCB 250 Amp, 50 Hz, 415 V with rupturing capacity 25 KA, Incomer -1 NoOUTGOING(b) 4 Pole MCCB 160 Amp, 50 Hz, 415 V with rupturing capacity 25 KA, -01 No(c) 4 Pole MCCB 100 Amp, 50 Hz, 415 V with rupturing capacity 25 KA, -01 No(d) 4 Pole MCCB 63 Amp , 50 Hz, 415V with rupturing capacity 16 KA - 02 Nos (e) 3 Pole MCCB 40 Amp , 50 Hz , 415 V with rupturing capacity 16KA -02 nos (f) Digital VAF (0-500 V)-01 No(g) CT's 250/5- set of 3 No(h) LED type Indication lamps (RYB)-one set |
| 27 | Supply and fxing in repairs of 7 meter high hot dipped octagonal poles with 130mm bottom dia & 70mm top dia made up of 3mm thick HT Sheet alongwith base plate of size 200x200x12mm including foundation bolts & bracket of isze M20x600mm EN 8 grade 'J\\" type foundation bolts and numbering of poles, in white paint over black painted back ground at a height of 1.5m from bottom of pole with 5 cm large bold letters 2\\" (inch) wide with etc complete as required and all as specified and directed complete accessories as required including dismantling existing pole complete all as specified and directed |
| 28 | Supply and fixing in repairs steel tubular street light pole 6 mtr high with pure polyster coated having base plate 200x200x12mm thick bottom dia 114mm(OD)x3mm thk x 2mtr long , middle portion 88.9mm(OD) x 3mm thick x 2 Mtr long , top dia 76mm (OD) x 2.5mm thick x 2 Mtr long inbuilt juction box suitable for connection of 3.5 core cable of size upto 25 Sqmm 3.5 Core with SMI -05 Design single arm bracket of size 42mm (OD) x1 mtr long and 2mm thick with GI M16 x 600 mm foundation bolt & Nut assembly complete all as specified and directed |
| 29 | Supply and fix in repair glow signage boards with base frame made from angle iron and backside form ACP sheet 3mm thick with IP 68 Protection LED module, good quality virgin monomer Acrylic sheet, MES Logo & Southern Command logo in letters with 5 mm sun board channel, including complete wiring and power supply with IP 68 protection, each letter will be made with computer offset for having same letter style and type as approved by Engineer - in- charge, complete all as specified and directed. |
| 30 | Supply and jointing straight through joint outdoor type 1100 volts grade heat shrinkable type suitable for 3.5x 25 sqmm to 3.5x 95 sqmm LT XLPE cable and testing after jointing complete all as specified and as directed. |
| 31 | Supply and jointing straight through joint outdoor type 1100 volts grade heat shrinkable type suitable for3.5x 120 sqmm to 3.5x 240 sqmm LT XLPE cable and testing after jointing complete all as specified and as directed. |
| 32 | Supply and fix in repair CTs suitable for existing LT panel board of capacity 400 to 630 Amps all as specified and as directed. |
| 33 | Supply and fix in repair CTs suitable for existing LT panel board of capacity 250 to 320 Amps Amps all as specified and as directed. |
| 34 | Supply and fix in repair CTs suitable for existing LT panel board of capacity 63 to 200 Amps Amps all as specified and as directed. |
| 35 | Supply and fix in repair LED indicator lamps (R Y B ) suitable for existing panel all as specified and directed. |
| 36 | Supply and fix in repair digital ammeter 500amps range suitable for mounting existing panel all as specified and directed |
| 37 | Supply and fix in repair digital voltmeter 500 Volts range suitable for mounting existing panel all as specified and directed |
| 38 | Supply and fix in repair selector switches suitable for ammeter/voltmeter all as specified and as directed. |
| 39 | M & L for Earthing complete with galvanised earth plate electrode of size 600x600x6 mm thick burried directly in ground earth pit not less than 2.25 m below ground level with top edge of earth plate not less than 1.5 mtrs below ground level connected to GI Strip of size 32x6mm upto a length of 7.5 metre long by means of bolts,nuts, washers etc. and protected by GI pipe light grade 15 mm dia and 20 mm dia GI tubing light grade with funnel for watering, all as shown in electrical plate No 3 of SSR Part-I, back-fill with salt and charcoal, provision of test point including connected to earth test point and necessary earth work excavation in any type of soil PCC (1:3:6) type C1 bed and chamber RCC (1:2:4) type B1, iron grill including GI cover with hinge and funnel watering pipe etc all as specified and directed. Note:(a) Earthing value should be less than 5 ohms.(b) If desired value of earth resistance not achieved during testing, the earthing work shall be redone by the contractor at free of cost to achieve the desire value of earthing resistance. The rate quoted by the contractor deemed to be inclusive of the provision. |
| 40 | Material and Labour for maintenance free earthing complete comprising of 17.2 mm dia 3 mtr long Earth electrode of low carbon steel electrode with 250 micron copper bonding, 50 pounds of Ecosafe based environment friendly backfill and suitable clamp, back-fill earthing enhancing compound should strictly be a Eco Safe carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm mtr as per Clause 14.5D of IEEE : 80 standard. Back-fill compound should be electronically conductive (like in metals) and should not depend on moisture for conduction. Back-fill compound should be environment friendly, should solidify when mixed water and set like concrete and should not leach /diffuse into the ground. Back-fill compound shall not mixed with any soil while pouring in the bore hole. Test Certificate as per IEC :62561-7 for Back-fill compound shall be submitted alongwith the material. 17.2 OD SS clamp both side, Eco friendly rust proof heavy duty weather proof Polythylene Earth pit chamber with following dimensions : 254 mm dia (top),330 mm dia (bottom) & 260 mm (height). Note::(a) Earthing value should be less than 5 ohms for Ser item No 2 to 4 and less than 1 ohms for ser item No 5.(b) If desired value of earth resistance not achieved during testing, the earthing work shall be redone by the contractor at free of cost to achieve the desire value of earthing resistance. The rate quoted by the contractor deemed to be inclusive of the provision. |
| 41 | Supply and fix in repair 10 mm copper bonded Round steel solid Conductor in compliance with IS/ IEC 62305 and IEC 62561-2. The coating shall be smooth, continuous & free from flux stains(Ring Earthing) should be tested and use exclusively for lightning protection ,earthing system and ring equipotential bonding complete all as specificed and directed. |
| 42 | Supply and fix in repair test link in order to disconnect the earth termination system for enabling measurements. to connect Aluminium round conductor to Ring Earthing complete all as specificed and directed. |
| 43 | M & L for hardcore of gauge not exceeding 63 mm of broken stone, deposited, spread and leveled in layers not exceeding 15 cm thick, watered and rammed to a true surface comlete all as specified and directed |
| 44 | M&L local sand dry, filling in trenches around under ground cable complete all as specified and directed. |
| 45 | M& L for spreading / filling loose stone aggregate of 40mm graded all as specified and directed. |
| 46 | Supply and fix in repair energy saving rectangular LED flood light fitting 150 Watts, 240 volts AC, cool white colour, CCT 5700°K, CRI>70, THD<10%, system lumens not less than 100lumens/watt with innovative thermal management, available with multiple optics, equipped with IP-66 protection, 5 KV surge protection, aluminium die cast housing, life of luminaires should not be less than 50000 burning hours and suitable for large area lighting including fixing on High mast pole/Buildings/TARMAC poles etc. by means of clamps, nuts, bolts and any other accessories complete all as specified and as directed. |
| 47 | Supply and fix in repair LED street light fitting 72 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP-66 protection, CCT 5700K, lumen efficacy not less than 110 lumen/watts complete all as specified and directed. |
| 48 | Supply and fix in repair Display board for Pro-33 of 30 KW Solar String Inverters of make ABB complete all as specified and as directed.Make : ABB Cat part No (Part No YVDH0002)/ FIEMER or equivalent compatible with existing |
| 49 | Supply and fix in repair Logic Board of 20 KW Solar String Inverters of make ABB complete all as specified and as directed.Make : ABB Cat part No (Part No VPBV1830E0) / FIEMER or equivalent compatible with existing |
| 50 | Supply and fix in repair AC filter board of 20 KW Solar String Inverters of make ABB complete all as specified and as directed.Make : ABB Cat part No (Part No VKA.V1811.7)/ FIEMER or equivalent compatible with existing |
| 51 | Supply and fix in repair PCBA Communication board of 20 KW Solar String Inverters of make ABB complete all as specified and as directed. Make : ABB Cat part No (Part No VTAV06L09.3) / FIEMER or equivalent compatible with existing |
| 52 | Supply and fix in repair PCBA DC filter board of 20 KW Solar String Inverters of make ABB complete all as specified and as directed.Make : ABB Cat part No (Part No 1908.0SI) / FIEMER or equivalent compatible with existing |
| 53 | Supply and fix in repair Dehn DG M TT 275 FM of 20 KW Solar String Inverters of make ABB complete all as specified and as directed.Make : ABB Cat part No (Part No 3AYNAC275N-SPD) / FIEMER or equivalent compatible with existing |
| 54 | Supply and fix in repair AC Filter board of 30 KW Solar String Inverters of make ABB complete all as specified and as directed.Make : ABB Cat part No (Part NoYVD.H0027.0) / FIEMER or equivalent compatible with existing. |
| 55 | Supply and fix in repair Fuse control board of 20 KW Solar String Inverters of make ABB complete all as specified and as directed.Make : ABB Cat part No (Part No VTA.V0R.7.SI) / FIEMER or equivalent compatible with existing. |
| 56 | Supply and fix in repair IGBT Board of 30 KW Solar String Inverters of make ABB complete all as specified and as directed.Make : ABB Cat part No (Part No YVP.H0004.0) / FIEMER or equivalent compatible with existing. |
| 57 | Supply and fix in repair Negative/Positive Fuse board of 50 KW Solar String Inverters of make ABB complete all as specified and as directed.Make : ABB Cat part No (Part No VKA.V2Y36) / FIEMER or equivalent compatible with existing. |
| 58 | Supply and fix in repair Power module external fan of 50 KW Solar String Inverters of make ABB complete all as specified and as directed..Make : ABB Cat part No (Part No VUD.V1U04) / FIEMER or equivalent compatible with existing |
| 59 | Supply and fix in repair Switch disconnector OT100F4N2 of 50 KW Solar String Inverters of make ABB complete all as specified and as directed.Make : ABB Cat part No (Part No ZEC.00132)/ FIEMER or equivalent compatible with existing |
| 60 | Supply and fix in repair Power module internal fan of 50 KW Solar String Inverters of make ABB complete all as specified and as directed.Make : ABB Cat part No (Part No ZFV.V1U02.0) / FIEMER or equivalent compatible with existing |
| 61 | Supply and fix in repair PCBA Input fuse board negative side of 50 KW Solar String Inverters of make ABB complete all as specified and as directed.Make : ABB Cat part No (Part No YVD.V2Y5W.0) / FIEMER or equivalent compatible with existing. |
| 62 | Supply and fix in repair DC Switch 4 pole of 50 KW Solar String Inverters of make ABB complete all as specified and as directed. Make : ABB Cat part No (Part No ZEC.00196) / FIEMER or equivalent compatible with existing. |
| 63 | M&L for PCC 1:4:8 type D2 using 40mm graded stone aggregate in foundation complete all as directed. |
| 64 | M&L for PCC 1:3:6 type C1 using 20mm graded stone aggregate for stay and coping for poles including necessary form work to exposed surface finished smooth and even all of specified. |
| 65 | S&F roof trusses (framed ) trussed , purlins , crane gantries , rails and fastenings and heavy bracket framing (Beam , tee, angle, channel or falt sections) including distance pieces, cleats etc Fe -410W (gde -E--250) quality A complete all as specified and directed. |
| 66 | S&F for MS plates (Plane or chequered) Channel square cut or notched (Ordinary and counter sunk) forming holes with riveted bolted attachment complete all as specified and directed. |
| 67 | S&F bands straps, clamps cleats and small articles, support or stay for rainwater ventilating pipes including bolts etc conforming to Fe-290Gde -E-165 complete all as specified and directed. |
| 68 | S&F Mild steel screw machine made with hexagonal or square heads at one end and screwed both ends screwed end to end fitted with washer and one hexagonal or square nut length exc 5 cm but n exc 10 cm, neck dia 5 to 10mm complete all as specified and directed. |
| 69 | S&F pre painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength 550mpa as in roof covering / cladding to wall, fixed with self tapping screws as specified and directed. |
| 70 | S&F Pre painted galvalume aluminium zinc coating GI Based plain steel sheet 0.50mm thick of any colour having tensile strength of 550mps as in ridge, hip valley gutters, drip and straight flashing with grade of zinc coating 275 (lenth and girth as fixed ) complete all as specified and directed. |
| 71 | M&L for two coats synthetic enamel paint over a coat of red oxide on new iron surface of any description not otherwise described over 10cm including preparation of new or previously untreated surface complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 07, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 28, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysNov 04, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 27 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender