Tender For Repairs And Replacement Of Hygiene Of Lt Ug Cables At Navy Area Of Age E/M Under Ge Haddo, Sri Vijaya Puram
Tender Value
43 Lakhs
Estimated cost
Bid Submission
28 Oct 2026
10 days left
EMD
86000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
South Andamans → Andaman And Nicobar Islands
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repairs And Replacement Of Hygiene Of Lt Ug Cables At Navy Area Of Age E/M Under Ge Haddo, Sri Vijaya Puram
BOQ
| Sl. No. | Item Description |
| 1 | Material and Labour for lifting the RCC slab, approximate length (2 to 4.5m) x width (1 to 2m) and upto 300 mm thick and about 3.0 to 5.0 ton in weight on IN Jetty by lifting of suitable slab with in 10 to 15m of length as per site condition by cutting/chipping the clearance, groove all around, keeping aside using a crane for laying of LT/HT cables or removing and relaying after fault rectification and replacing RCC slab at the same location after carrying out repairs including making good the surface with pack 1:2:4 complete all as specified and directed. Note: Two to three Nos of slab shall be taken out/ removed as per site condition for laying of cables/ earth strip in the cable duct of Jetty after for a span of 15 to 20 meters or as per site requirement. |
| 2 | Excavation in trenches not exc 1.5 M deep and 1.5 M width and getting out in soft or loose soil for foundation of poles (or) cable laying complete all as specified and directed. |
| 3 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm in soils complete all as specified and directed. |
| 4 | Removing/excavated soil to a distance not exc 50 M and depositing where directed at a level not exc 1.5 M above the starting point all as specified and directed. |
| 5 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 2 core x 6 sq.mm. (laid in trenches, ducts, pole, wall etc.) including taking out old unserviceable LT cable from trenches/pole/ducts etc. complete all as specified and as as directed by engineer in charge. |
| 6 | Supply, laying, testing and commissioning of underground LT XLPE insulated, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of cross section 2 x 10 sqmm (laid in terenches, ducts, pole,wall etc.) complete all as specified and directed by Engr In Cahrge. |
| 7 | Supply, laying, testing and commissioning of underground LT XLPE insulated, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of cross section 4 x 16 sqmm (laid in terenches,ducts,pole,wall etc.) complete all as specified and directed |
| 8 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3½ core x 25 sq.mm. (laid in trenches, ducts, pole, wall etc.) including taking out old unserviceable LT cable from trenches/pole/ducts etc. complete all as specified and as as directed . |
| 9 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3½ core x 35 sq.mm. (laid in trenches, ducts, pole, wall etc.) including taking out old unserviceable LT cable from trenches/pole/ducts etc. complete all as specified and as as directed . |
| 10 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3½ core x 50 sq.mm. (laid in trenches, ducts, pole, wall etc.) including taking out old unserviceable LT cable from trenches/pole/ducts etc. complete all as specified and as as directed . |
| 11 | Supply, laying, testing and commissioning of underground LT XLPE insulated, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of cross section 3½ x 70 sqmm (laid in terenches, ducts, pole,wall etc.) complete all as directed by Engr In Charge. |
| 12 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3½ core x 95 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge. |
| 13 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3½ core x 120 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge. |
| 14 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3½ core x 185 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge. |
| 15 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3½ core x 240 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge. |
| 16 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3½ core x 300 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge. |
| 17 | Supply, laying, testing and commissioning of LT XLPE insulated, sheathed, armoured heavy duty electric aluminium conductor cable 1100 Volts grade of size 3½ core x 400 sq.mm. (laid in trenches, ducts, pole, wall etc.) complete all as specified and as as directed by engineer in charge. Note for Item No.5.00 to 17.00 : (i) Necessary test results like continuity test, megger tests, shall be submitted to Engineer-in-Charge before the cable is laid. (ii) Excavation earth work will be measured and paid separately. |
| 18 | M & L for GI earth strip of size 32 x 6 mm laying in trench, fix to pole with necessary clamp and nut, bolt etc including taking out of unsv earth strip complete all as directed. |
| 19 | Taking down the corroded/detrioted GI pipe from the trench crossings/obstructions for cable protection, supply & lay GI Pipe 100 mm medium grade including cutting of existing road and making good the disturbed surfaces all as specified & directed Make : Oswal/Jindal/TATA |
| 20 | Supply, connect and testing for straight though joints for 1100volts grade of LT UG cables of size 3½ core 25 to 50 sqmm including taking out old joint complete all as specified & directed. |
| 21 | Supply, connect and testing for straight though joints for 1100volts grade of LT UG cables of size 3½ core 70 to 95 sqmm including taking out old joint complete all as specified & directed. |
| 22 | Supply, connect and testing for straight though joints for 1100volts grade of LT UG cables of size 3½ core 120 to 150 sqmm including taking out old joint complete all as specified & directed. |
| 23 | Supply, connect and testing for straight though joints for 1100volts grade of LT UG cables of size 3½ core 185 to 240 sqmm including taking out old joint complete all as specified & directed. |
| 24 | Supply, connect and testing for straight though joints for 1100volts grade of LT UG cables of size 3½ core 300 to 400 sqmm including taking out old joint complete all as specified & directed. |
| 25 | Material & labour for laying of chequered plates of any thickness by cutting / making in to the shape providing necessary angular supports and handles with 6 mm dia rod as per the site condition for cable trencehs of various sub-stations alongwith painting of one coat of synthetic enamel over a coat of two coats of redoxide all as specified and directed. |
| 26 | Taking down/removal of old burnt/damaged LT cable end termination and supply and making new LT 1100 volts termination with suitable size of lugs duly crimped for LT 3½ core armoured aluminium conductor cable after isolating supply to transformer/LT pillar box/LT panel and disconnecting burnt/faulty cable from the bunch of cable gland and connecting back with new nuts, bolts and washers of nickel chromium with petroleum jelly after end termination testing and commissioning for the 3½ core X 95 Sqmm to 500 Sqmm cable all as specified and directed. |
| 27 | Supply and laying in trenches or in cable ducts, HDPE DWC pipe of size 120mm (OD) x103.5mm (ID) along with connected accessories like couplers, bends, end caps etc. for LT/ HT cable protection fixed on walls with clamps complete all as specified and as as directed. |
| 28 | Supply and laying HDPE DWC pipe of size 77 mm(OD) x 63mm (ID) along with connected accessories like couplers, bends, end caps etc. for LT/ HT cable protection complete including taking down all as specified and as directed . |
| 29 | Supply and laying in trenches or in cable ducts or clamping on wall DWC HDPE pipe of size 50 mm (OD) x 38 mm (ID) along with connected accessories like couplers.bends,end caps etc. for LT/HT cable protection complete all as specified and as directed . |
| 30 | M&L Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick,40mm bore medium grade (steel pipe) buried directly in ground (earth pit not less than 2.25m deep below GL) with top edge of the plate not less than 1.5m below normal GI, connected to galvanised earth strip 32 x 6 mm by means of bolts nuts check nuts and washers of galvanised iron or steel all as shown in electrical plate No.5 connected to earthing test point all as specified or indicated including testing on completion.Note : Rate shall be deemed to be inclusive of necessary excavation and earth work in any type of soil, removal of surplus soil to a distance not exceeding 50 M RCC covers slab and PCC chamber etc. |
| 31 | Disconnecting old unservieable / under rated LT UG cables of size 3.5 core 50 to 185 sqmm and draw out from the pipe or under ground or cable duct from power house to different feeders/ on Jetty/ at any other location including re-laying the same in trenches or on walls or in cable duct with necessary clamping where required all as specified and as directed by Engineer-in-Charge.Note: Necessary excavation will be measured and paid seperately. |
| 32 | Disconnecting old unservieable / under rated LT UG cables of size 3.5 core 185 to 500sqmm and draw out from the pipe or under ground or cable duct from power house to different feeders/ on Jetty/ at any other location including re-laying the same in trenches or on walls or in cable duct with necessary clamping where required all as specified and as directed by Engineer-in-Charge.Note: Necessary excavation will be measured and paid seperately. |
| 33 | Disconnecting and taking out existing old unserviceable copper bus bar of any size or shape and supply and fix new copper bus bar of suitable size and capacity to suit the existing requirement with proper insulators for mounting including reconnecting the electric cables complete all as specified and as directed by Engineer in charge. |
| 34 | M&L for mild steel framed brackets of angles, tees, plates, heavy duty hinges for welding of cope boxes/LT Panel boards with web and flanges cut to shape, drilled and countersunk for screw including bending with necessary welding works for angles/hinges if necessary, gusset plates, riveting, brackets including of painting with two coats of synthetic enamel spray paint over a coat of redoxide primer including dismantling existing brackets complete all as specified and as directed by Engineer in charge. |
| 35 | S&F heat shrinkable sleeves suitable for 150Sqmm to 500Sqmm LT UG cable, 415V grade including disconnecting LT UG cable from Transformer/LT Panel/Feeder Pillar Box/Cope boxes and re-connection after completion complete all as specified and directed. |
| 36 | Material and Labour for cutting existing BT / PCCroad of size 45cm x 60cm for taking out/laying of underground cable/pipe and including necessary earth work and refilling the same in layers well ramming including watering as required and matching with the existing surface with 200mm thick PCC 1:2:4 type B1 and curing the same with wet gunny bags and removing debris to a distance not less than 50m complete all as specified and as directed . |
| 37 | M&L for PCC 1:2:4 type B1 (using 20mm graded stone aggregate) as in coping of pole including use & waste of necessary form work including weathering, slightly rounded or chamfered angles and throating, complete all as specified and as as directed by engineer in charge. |
| 38 | S&F MCCB 4 Pole, 63 Amps, 25kA, 415 volts, 50 Hz adjustable over load 80-100%, with thermal magnetic release Ics=100%Icu, connecting up with necessary spreader links complete all as directed including disconnecting & taking down existing unserviceable MCCBs from LT panels / feeder pillar boxes complete all as specified and as directed by Engineer in charge.[Cat No. CM91712OOJOOG of make: L&T or equivalent in Schneider/ ABB/ Legrand] |
| 39 | S&F MCCB 4 Pole, 100-125 Amps, 25kA, 415 volts, 50 Hz adjustable over load 80-100%, with thermal magnetic release Ics=100%Icu, connecting up with necessary spreader links complete all as directed including disconnecting & taking down existing unserviceable MCCBs from LT panels / feeder pillar boxes complete all as specified and as directed by Engineer in charge.[Cat No. CM90642OOLO of make: L&T or equivalent in Schneider/ ABB/ Legrand] |
| 40 | S&F MCCB 4 Pole, 160-200 Amps, 25kA, 415 volts, 50 Hz adjustable over load 80-100%, with thermal magnetic release Ics=100%Icu, connecting up with necessary spreader links complete all as directed including disconnecting & taking down existing unserviceable MCCBs from LT panels / feeder pillar boxes complete all as specified and as directed by Engineer in charge.[Cat No. CM90642OONO of make: L&T or equivalent in Schneider/ ABB/ Legrand] |
| 41 | S&F MCCB 4 Pole, 200-250 Amps, 36 kA, 415 volts, 50 Hz adjustable over load 80-100%, with thermal magnetic release Ics=100%Icu, connecting up with necessary spreader links complete all as directed including disconnecting & taking down existing unserviceable MCCBs from LT panels / feeder pillar boxes complete all as specified and as directed by Engineer in charge.[Cat No. CM92109OOP1OG of make: L&T or equivalent in Schneider/ ABB/ Legrand] |
| 42 | S&F MCCB 4 Pole, 200-250 Amps, 36 kA, 415 volts, 50 Hz adjustable over load 80-100%, with thermal magnetic release Ics=100%Icu, connecting up with necessary spreader links complete all as directed including disconnecting & taking down existing unserviceable MCCBs from LT panels / feeder pillar boxes complete all as specified and as directed by Engineer in charge. |
| 43 | Material & labour for sand filling in trenches with clean dry fine sand unwashed including gently punning around cables complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 08, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 28, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysOct 30, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 12 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender