Tender For Replacement Of Faulty Runway Cable And Provision Of Surge Protection Device In Ccrs At Birsi Airport, Gondia.
Tender Value
1.48 Crore
Estimated cost
Bid Submission
27 Oct 2026
17 days left
EMD
2.97 Lakhs
Bank guarantee accepted
Document Fee
1180
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Gondia → Maharashtra
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Replacement Of Faulty Runway Cable And Provision Of Surge Protection Device In Ccrs At Birsi Airport, Gondia.
BOQ
| Sl. No. | Item Description |
| 1 | Supply of 5 KV grade SINGLE CORE 16 Sq.mm size Airfield Lighting Cable with stranded Copper Conductor PVC insulated, PVC Sheathed Single Core, Unshielded, Anti-Termite & rodent treated UG Cable generally conforming to IS 1554, Part-II with upto date amendment as required. |
| 2 | Supply of 5 KV grade SINGLE CORE 6 Sq.mm size Airfield Lighting Cable with stranded Copper Conductor PVC insulated, PVC Sheathed Single Core, Unshielded, Anti-Termite & rodent treated UG Cable generally conforming to IS 1554, Part-II with upto date amendment as required. |
| 3 | Supply of following 5KV grade plug & receptacle (essna connector)of type-1 class B connector & suitable field attachment suitable for following size 5KV grade PVC insulated PVC sheathed single core stranded copper conductor cable confirming to IS:1554 (Part-II) with upto date amendment. 16 Sq.mm |
| 4 | Supply of following 5KV grade plug & receptacle (essna connector)of type-1 class B connector & suitable field attachment suitable for following size 5KV grade PVC insulated PVC sheathed single core stranded copper conductor cable confirming to IS:1554 (Part-II) with upto date amendment. 6 Sq.mm |
| 5 | Making field connections by crimping of 6/16 sq.mm. plug & receptacle with existing 6/16 sq.mm. single core PVC insulated Copper Conductor cable including filling the gap with water sealant material applying PVC insulation tape and HT tape insulation etc complete as reqd. |
| 6 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 7 | Laying of one number PVC/ XLPE insulated and PVC sheathed cable of 5 KV grade of following size in the existing RCC/ HUME/ METAL pipe/ HDPE Pipe as required. a) Single core 6.0 Sq.mm or 16 Sq.mm(or Upto 35 Sq.mm) |
| 8 | Laying of one number PVC/ XLPE insulated and PVC sheathed power cable of 5 KV grade of following size in masonnary open duct etc as required. Single core 6.0 Sq.mm or 16 Sq.mm(or Upto 35 Sq.mm) |
| 9 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 10 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. wire in 15mm dia G.I.pipe from electrode including connection with G.I. thimble excavation and re-filling as required.(From light fitting to earth electrode) |
| 11 | Providing and fixing 6 SWG GI wire on surface or in recess for loop earthing along with existing surface/recessed conduit/submain wiring/cable as required. |
| 12 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/terminal with GI thimble etc. as required.(From light fitting to earth electrode) |
| 13 | Supplying & fixing cable route marker with 10X10X5mm thick GI plate with description there on bolted/welded to 35mmX35mmX6mm angle iron 60cm long and fixing the same in ground as required. |
| 14 | Supply of Two Pin Secondary Plug Assembly for Taxi Fitting of length 0.5 Mtrs of 2.5 Sq. mm. |
| 15 | Supply, Installation, testing and commissioning of MOV based 40 KA Surge Protection module for CCR panel output (Two Phase, Incoming & Outgoing) with rated voltage MCOV 5000V (the protection of CCR panel from the surge entering from runway light) tested as per from IEC 61643-11 : 2011 (As per IEC 61000-4-5:2014:+A1:2017) NABL in IP55 metal enclosure, interconnection with copper cables, end terminations etc. as required to be installed at the main switch board panel in parallel mode, complete etc as required. |
| 16 | Supply, Installation, Testing & Commissioning of Digital Grounding Device 80 kA, 3 phase 4 wire Portable type with built in Low Impedance Grounding & bonding system. Provides 100% protection against Lightning Surges, static charge, Noises, ESD,EPR. It eliminates all abnormal electrical disturbances which always enters from power lines and always ensuring clear bonding potential (earth to Neutral voltage) less than 1.0V to all equipment connected hereafter. It is having a digital 6 digit lightening surge counter also having tested capability to handle lightning impulse current upto 45KA,self-health visual status indicator. It offers low resistance to all devices connected her after with in permissible distance facility to display of Resistance values offered to all equipment connected hereafter. It is Pre- wired, pulverulent body painted, metallic enclosure always to be connected in parallel to the power supply circuit. DGD is tested & certified from CPRI, MIL STD810G, IEC61000-6-1, IEC 61000-6-3,IEC 61643-11- 2011 & confirming to ISO 9000 & ISO 14001-2015 & CE, complete etc as required. |
| 17 | Supply of CPRI Approved Insulation mat confirming to IS 15652 up to date amendment, complete etc as required. 1mtr x 10mtr x 2mm ( 3.3 KV) Class A |
| 18 | Supply of CPRI Approved Insulation mat confirming to IS 15652 up to date amendment, complete etc as required. 1mtr x 10mtr x 2.5mm ( 11 KV ) Class B Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 07, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 27, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysOct 28, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender