Bids Are invited for Repair, Maintenance, And Installation Of Plant/ Systems/Equipments (Version 2) - 33 Servicing Calibration And Attending Fault In 1250 A Acb At Te Gokulam And 800A Acbs At Te Zttc Mysore And Attending Electrical Complaints At Othe
Tender Overview
Project Description
Bids Are invited for Repair, Maintenance, And Installation Of Plant/ Systems/Equipments (Version 2) - 33 Servicing Calibration And Attending Fault In 1250 A Acb At Te Gokulam And 800A Acbs At Te Zttc Mysore And Attending Electrical Complaints At Other Tes Under De Gokul.. - Servicing Of Existing 1250A 3 Pole/ 4 Pole Air Circuit Breaker (L&T, Cncs) In The Mv Panel I/C Taking It Out From The Circuit, Getting It Serviced From The L&T Company Authorised Service Team, Calibration Of The Same, Cleaning The Carbon Deposits From The Contact Terminals With A Cleaning Agent, Aligning The Operating Handle Mechanism, Injecting The Fault Current From External Testing Devise To Conduct Trip Tests On Over Load, Short Circuit & Earth Fault, Checking The Trip Operation And Trip Time Etc And Setting The Parameters As Per Load, Connecting Back To The Circuit, Checking And Testing The Operation On Regular Eb/Dg Power Supply, Submitting The Test Results Etc As Reqd. , Servicing Of Existing 800A 3Pole/ 4Pole Air Circuit Breaker (L&T, Cncs) In The Mv Panel I/C Taking It Out From The Circuit, Getting It Serviced From The L&T Company Authorised Service Team, Calibration Of The Same, Cleaning The Carbon Deposits From The Contact Terminals With A Cleaning Agent, Aligning The Operating Handle Mechanism, Injecting The Fault Current From External Testing Devise To Conduct Trip Tests On Over Load, Short Circuit & Earth Fault, Checking The Trip Operation And Trip Time Etc And Setting The Parameters As Per Load, Connecting Back To The Circuit, Checking And Testing The Operation On Regular Eb/Dg Power Supply, Submitting The Test Results Etc As Reqd. , Servicing & Calibration Of Idmt Relays I/C Taking It Out From The Circuit, Getting It Serviced From The L&T Company Authorised Service Team, Calibration Of The Same, Cleaning The Carbon Deposits From The Contact Terminals With A Cleaning Agent, Injecting The Fault Current From External Testing Devise To Conduct Trip Tests On Over Load, Short Circuit & Earth Fault, Checking The Trip Operation And Trip Time Etc And Setting The Parameters As Per Load, Connecting Back To The Circuit, Submitting The Test Results Etc As Reqd. , Supply Of 25 S Ht Hrc Fuses Suitable For Operation On 9Kv/ 11Kv Ht Supply Complete Etc As Reqd. (Make: Eshwari/ Phoenix /Anand Or Ss Make) , Supplying And Fixing Of 4 Feet 20 W Led Light Batten With Driver I/C Making Connection Testing Etc As Reqd. (Make: Phillips, Syska, Cg, Bajaj Or Isi Approved) , S&F Of Aerial Fuse Cutouts Porcelain Type 100Ax3nos With 63A Nuetral Link, Fixed On A Suitable Size Hylum Sheet Board ,With Suitable Thickness , Mounting All Above On The Eb Pole For Service Cable Terminatons I/C Connections, Testing Complete As Reqd. (On Cesc Pole)
BOQ
| Sl. No. | Item Title | Item Description |
| 1 | Servicing of existing 1250A 3 Pole/ 4 Pole Air Circuit Breaker (L&T, CNCS) in the MV panel i/c Taking it out from the circuit, getting it serviced from the L&T company authorised service team, calibration of the same, cleaning the carbon deposits from the contact terminals with a cleaning agent, aligning the operating handle mechanism, injecting the fault current from external testing devise to conduct trip tests on Over Load, Short Circuit & Earth Fault, checking the trip operation and trip time etc and setting the parameters as per load, connecting back to the circuit, checking and testing the operation on regular EB/DG power supply, submitting the test results etc as reqd. | Servicing of existing 1250A 3 Pole/ 4 Pole Air Circuit Breaker (L&T, CNCS) in the MV panel i/c Taking it out from the circuit, getting it serviced from the L&T company authorised service team, calibration of the same, cleaning the carbon deposits from the contact terminals with a cleaning agent, aligning the operating handle mechanism, injecting the fault current from external testing devise to conduct trip tests on Over Load, Short Circuit & Earth Fault, checking the trip operation and trip time etc and setting the parameters as per load, connecting back to the circuit, checking and testing the operation on regular EB/DG power supply, submitting the test results etc as reqd. |
| 2 | Servicing of existing 800A 3pole/ 4Pole Air Circuit Breaker (L&T, CNCS) in the MV panel i/c Taking it out from the circuit, getting it serviced from the L&T company authorised service team, calibration of the same, cleaning the carbon deposits from the contact terminals with a cleaning agent, aligning the operating handle mechanism, injecting the fault current from external testing devise to conduct trip tests on Over Load, Short Circuit & Earth Fault, checking the trip operation and trip time etc and setting the parameters as per load, connecting back to the circuit, checking and testing the operation on regular EB/DG power supply, submitting the test results etc as reqd. | Servicing of existing 800A 3pole/ 4Pole Air Circuit Breaker (L&T, CNCS) in the MV panel i/c Taking it out from the circuit, getting it serviced from the L&T company authorised service team, calibration of the same, cleaning the carbon deposits from the contact terminals with a cleaning agent, aligning the operating handle mechanism, injecting the fault current from external testing devise to conduct trip tests on Over Load, Short Circuit & Earth Fault, checking the trip operation and trip time etc and setting the parameters as per load, connecting back to the circuit, checking and testing the operation on regular EB/DG power supply, submitting the test results etc as reqd. |
| 3 | Servicing & calibration of IDMT relays i/c Taking it out from the circuit, getting it serviced from the L&T company authorised service team, calibration of the same, cleaning the carbon deposits from the contact terminals with a cleaning agent, injecting the fault current from external testing devise to conduct trip tests on Over Load, Short Circuit & Earth Fault, checking the trip operation and trip time etc and setting the parameters as per load, connecting back to the circuit, submitting the test results etc as reqd. | Servicing & calibration of IDMT relays i/c Taking it out from the circuit, getting it serviced from the L&T company authorised service team, calibration of the same, cleaning the carbon deposits from the contact terminals with a cleaning agent, injecting the fault current from external testing devise to conduct trip tests on Over Load, Short Circuit & Earth Fault, checking the trip operation and trip time etc and setting the parameters as per load, connecting back to the circuit, submitting the test results etc as reqd. |
| 4 | Supply of 25 Amps HT HRC Fuses suitable for operation on 9Kv/ 11Kv HT supply complete etc as reqd. (Make: Eshwari/ Phoenix /Anand or SS Make) | Supply of 25 Amps HT HRC Fuses suitable for operation on 9Kv/ 11Kv HT supply complete etc as reqd. (Make: Eshwari/ Phoenix /Anand or SS Make) |
| 5 | Supplying and fixing of 4 Feet 20 W LED light batten with driver i/c making connection testing etc as reqd. (Make: Phillips, Syska, CG, Bajaj or ISI approved) | Supplying and fixing of 4 Feet 20 W LED light batten with driver i/c making connection testing etc as reqd. (Make: Phillips, Syska, CG, Bajaj or ISI approved) |
| 6 | S&F of Aerial fuse Cutouts Porcelain type 100Ax3Nos with 63A Nuetral link, fixed on a suitable size hylum sheet board ,with suitable thickness , mounting all above on the EB Pole for Service Cable terminatons i/c connections, testing complete as reqd. (On CESC Pole) | S&F of Aerial fuse Cutouts Porcelain type 100Ax3Nos with 63A Nuetral link, fixed on a suitable size hylum sheet board ,with suitable thickness , mounting all above on the EB Pole for Service Cable terminatons i/c connections, testing complete as reqd. (On CESC Pole) |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 12 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 13 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender