Tender For Execution Of Electrical Installation Work For Providing Power Supply To 11Kv Line With 10 Mtr Psc Pole And 55 Sq. Mm- Aaa Covered Conductor -0.015Km, Installation Of 25 Kva Psc Pole Mounted Dt,Lt Line -0.37 Km At Rwss Point At Gobardhanpur
Tender Overview
Project Description
Tender for Execution Of Electrical Installation Work For Providing Power Supply To 11Kv Line With 10 Mtr Psc Pole And 55 Sq. Mm- Aaa Covered Conductor -0.015Km, Installation Of 25 Kva Psc Pole Mounted Dt,Lt Line -0.37 Km At Rwss Point At Gobardhanpur Village For Pws To Gobardhanpur Under Pipili Block
BOQ
| Sl. No. | Item Description |
| 1 | PART-A 11 kv Line Length with 40 Mtr Span using 55 SQMM AAA Cover Conductor PSC Pole 10 mtr long 330 Kg |
| 2 | PSC Pole Clamp (GI) |
| 3 | Streight Cross Arm 100x50x6mm. 9.56 Kg/mtr each channel (GI) length 1.2 mtr 4 nos channel (GI) required = (4 x 9.56 x 1.2) |
| 4 | Fish plate (GI) 50x6 mm . 2.36 kg/mtr each 0.280 mtr length 16 nos required =(16x2.36x0.280) |
| 5 | Streight Cross Arm 100x50x6mm. 9.56 Kg/mtr each channel (GI) length 0.308 mtr 4 nos channel (GI) required = (4 x 9.56 x 0.306) |
| 6 | Danger Plate 1 nos |
| 7 | Back Clamp for danger plate 25x3 mm Plate (GI) 0.59 kg/mtr Flat(GI) of 0.510 mtr length 2 nos =(2x0.50x0.510) |
| 8 | GI barbed wire anticlimbing device 3 kg per support |
| 9 | Back clamp for anticlimbing device 25x3 mm flat(GI) 0.59 kg/mtr flat(GI) of 0.510 mtr length 8 nos =(4x0.59x0.510) |
| 10 | 11 KV pin insulator polymer |
| 11 | HW fitting (B&S 70 KN 3 Bolt |
| 12 | Disc insulator (B&S) 70 KN polymer |
| 13 | Earthing of support (Coil Type) |
| 14 | No-8 GI wire (Dia 4.6mm) D 131 Kg/mtr - 2 mtr for concreting pole with coil earthing |
| 15 | WEDGE CONNECTOR FOR 55 SQMM CONNECTION |
| 16 | POLY CORBONATE BIRD GUARD |
| 17 | HT Stay Clamp |
| 18 | HT Stay set (Complete ) |
| 19 | HT Stay Insulator Type-C |
| 20 | 7/10 SWG stay wire of different size |
| 21 | GI Nut Bolt & Washer of different sizes |
| 22 | Black Paint |
| 23 | Yellow colour Paint for Background |
| 24 | CIVIL & SERVICES Fixing of complete 11 kv line complete stay set includes1) Turn Buckle Assembly2) Stay Rod & Stay plate3) Stay Insulator4) Stay wire5) Stay clamp with Nuts & bolts BA will do the excavation suply of 0.5 Cum cement concrete foundation 1:2:4 size (500 mmx500mmx800mm ) using 20mm BHG metal with all labour and materials as per TPCODL Drawing & standard. |
| 25 | Concreting ratio 1.153(M 20 Grade) (500mmx500mmx667mm)=0.375 Cu mtr(Per Pole) |
| 26 | MATERIALS FOR 11 KV PIN POINTS WITH WPB 55 sqmm x LPE Insulated AAA conductor |
| 27 | PART-B 25 KVA DP Mounted DSS 9 mtr long 300 kg PSC Pole for DP |
| 28 | PSC Pole Clamp (GI) |
| 29 | 9 mtr long 300 kg PSC Pole for LT O/G feeders |
| 30 | Pole Clamp for EYE hook for (XLPE Aerial bunched Cable) |
| 31 | EYE hook for XLPE Aerial buched Cable |
| 32 | Dead End clamp suitable for messanger XLPE Aerial buched Cable |
| 33 | LT Cable raising channel GI 75x40x4.8 mm GI channel GI (1000 mm long) (7.14 kg/mtr 3 nos) (Each 3x1000x7.14=21.42 kg) |
| 34 | Top Channel(GI) 100x50x6mm. (3000 mm long) (9.56 kg/mtr 2 nos (Each 2x3000x9.56 =57.36 kg) |
| 35 | Fish Plate(GI) 50x6 mm 2.36 kg/mtr ech 0.280 mtr length 6 nos required =(6x2.38x0.280) |
| 36 | AB switch Mounting channel(GI) 75x40x4.8mm 7.14 KG/mtr each channel (GI) length 3 mtr 2 nos channel (GI) requird 7.14x3x2) |
| 37 | AB switch Mounting channel(GI) 75x40x4.8mm 7.14 KG/mtr each channel (GI) length 0.35 mtr 2 nos channel (GI) requird 79.56x2x0.35) |
| 38 | Channel(GI) support channel(GI) 75x40x4.8mm 7.14 KG/mtr each channel (GI) length 3 mtr 2 nos channel (GI) requird 9.56x2x0.35) |
| 39 | HG/DD Fuse mounting channel(GI) 75x40x4.8 mm GI channel(GI) (810 mm long -2 nos) long (7.14 kg/mtr 2 nos) Each 2 x 3000x7.14=42.84 kg) |
| 40 | Centilever support channel(GI) 75x40x4.8mm 7.14 KG/mtr each channel (GI) (810 mm long -2 nos) long (7.14 kg/mtr 2 nos) Each 2 x 0.810x7.14=11.57 kg) |
| 41 | Centilever support channel(GI) 75x40x4.8mm GI (1282 mm long) 4.5kg/mtr 2 nos (Each 2 x 1.28x4.5=11.54 kg) |
| 42 | Transformer Base GI channel(GI) 100x50x6mm (3000 mm long) (9.56kg/mtr 2 nos (Each 2x3x3000x 9.56=57.36 kg) |
| 43 | Transformer Base GI channel(GI) 100x50x6mm (515 mm long) (9.56kg/mtr 2 nos (Each 2x0.515x9.56=9.85 kg) |
| 44 | Transformer Bearing support Angle(GI) 50x50x6mm GI(580 mm long)4.5 kg/mtr -2 nos) (Each 2x0.580x4.5 kg) |
| 45 | Transformer Belling support Angle(GI) 50x50x6mm GI(515 mm long)4.5 kg/mtr -2 nos (Each kg/mtr -2 nos) (Each 2x0.580x4.5 kg) |
| 46 | LTDB Mounting Angle (GI) 50x50x6mm GI(1000 mm long) 4.5 kg/mtr -2 nos (Each kg/mtr -2 nos) (Each 2x0.580x4.5 kg) |
| 47 | 50x6mm Flat(GI) for eathing 2.36 kg/mtr. For mesh formation 12 mtr for LA and 2.5 mtr For raising 11 mtr for AB switch 2.8 mtr HG Fuse 5x2 mtr for DTR Nutral, (1.3+4.5) mtr For DTR Body 0.500 mtr for LTDB & AB switch operating handle 3 mtr for Fencing) (Each 65.6x2.36=154.81 kg) |
| 48 | 25 KVA 11/0.4 KV(AL) Transformer BIS Energy Loss level II. Alluminium-4 |
| 49 | LT Distribution Box with MCCB Alluminium Busbar of singlr Bay with kit kat fuse for 25 KVA S/S |
| 50 | 55 SSQM AAAC x LPE covered conductor |
| 51 | 4 Cx35mm2 LTxLPE cable (Armoured for 25 KVA Trf. |
| 52 | 4 Cx35mm2 LTxLPE cable (Armoured for (TDB to PSC Pole |
| 53 | AB switch (11 KV 400 A 3 pole 50 Hz) |
| 54 | HG Fuse (11 KV 200 A 3 pole) |
| 55 | WEDGE CONNECTOR FOR 55 SQMM CONDUCTOR |
| 56 | POLYCARBONATE BIRD GUARD |
| 57 | Disc insulator (B&S) 70 KN polymer |
| 58 | H.W. FITTING (B&S) 70 KN 3 bolts |
| 59 | Lighting Arrester (12 KV 10KA) Station class-2 |
| 60 | 11 KV pin ibsulator polymer |
| 61 | HT Stay set (Complete ) |
| 62 | HT Stay clamp (1.9 kg/pair) |
| 63 | HT Stay Insulator Type-C |
| 64 | 7/10 SWG stay wire 15 kg /stay |
| 65 | 40mm Nominal bore GI pipe (medium gauge earthing device with 3 mtr long |
| 66 | GI Nut Bolt of Assorted size (25 kg/DSS DP) |
| 67 | GI Barbed wire / Anticlimbing device (3 kg/Pole) |
| 68 | Back clamp for anticlimbing device 25x3 mm flat(GI) 0.59 kg/mtr flat(GI) of 0.510 mtr length 8 nos =(8x0.59x0.510) |
| 69 | Danger Plate 11 KV |
| 70 | Back Clamp for danger plate 25x3 mm Plate (GI) 0.59 kg/mtr Flat(GI) of 0.510 mtr length 2 nos =(2x0.50x0.510) |
| 71 | Name Plate |
| 72 | Structure Numbering and Marking Yellow Colour PAINT (GIS Numbering & Zebra stripping) for Back ground |
| 73 | Black Colour Paint (GIS Numbering & Zebra stripping) |
| 74 | CIVIL & SERVICES Concreting 1.1.5:3 (M 20 Grade) (500 mmx500mmx1800mm)=0.450 Cu.mtr (Per Pole (For WPB Pole) |
| 75 | PCC ratio 1:3:6) (M-10 Grade) For DSS Area (5x3x0.1) =1.5 cum/mtr |
| 76 | Fixing of stay set with 0.5 cum cement concrete foundation 1:3:6) (M-10 Grade) size 900mmx600mmx900mm )using 40mm BHG metal with all labur and materials except stay set, stay wire ,stay insulator |
| 77 | Construction Earthing chamber including installation of earthing pipe Making earthing chamber including excavation ,soil treatment with bentonite powder calculation of earh resistance , including installation of 3 mtr GI pipe 40mm/50mm including welding of Flat (GI) around pipe |
| 78 | Laying of 4 C x 35 mm2 x LPE Cable |
| 79 | SITC and Errection of GI Fencing with Gate |
| 80 | Concreting ratio 1:1.5:3 (M-20 Grade) (500x500x1500)=0.375 Cu mtr Per Pole)(For PSC Pole) |
| 81 | Supply of AL Lugs suitable for 35 sqmm cable/conductor ,climbing with cable and fixing/concreting include supply and errection of PVC Taps as per voltage requiremnt . |
| 82 | Supply and errection of double Compression Flameproof Type Glanding for armoured Cab,e 3.5/4C 16-35 sqmm including making hole in Base plate and dressing of cable along with vermin. Supply to be done as per TPCODL Spae and approved make dowells. |
| 83 | PART-C LT AB Cable Line Length with 33 Mtr. Span Using -4Cx35 mm2 9 mtr long 300 kg PSC Pole for DP |
| 84 | LT stay set Complete |
| 85 | 7/12 SWG GI stay wire Grade-2 |
| 86 | LT Stay clamp (1.40 kg/pair) |
| 87 | LT Stay Insulator |
| 88 | LT Accessories with Eye hook and Clamp Pole Clamp for EYE hook for (XLPE Aerial bunched Cable ) |
| 89 | EYE hook for XLPE Aerial bunched Cable |
| 90 | Dead End Clamp suitable for messanger XLPE Aerial bunched Cable |
| 91 | Suspension Clamp with EYE hook for ABC |
| 92 | 4C x 35 mm2 (P)+ICx16 mm2(Streat Light) (LT AB Cable |
| 93 | Insulated piercing connector Type-B-main 25 to 150 sqmm & Tap-6 to 35 sqmm |
| 94 | GI Pipe Earthing (each 5th pole to earth) |
| 95 | Coil Earthing |
| 96 | No-8 GI wire (Dia 4.6 mm) 0.131 KG/Mtr-2 Mtr For connecting pole with Coil Earthing |
| 97 | Danger Plate (LT) |
| 98 | Back clamp for Danger Plate 25x3 mm. Flat(GI) 0.59 Kg/Mtr Flat (GI) of 0.51 mtr length 1 no =(1x0.59x0.510) |
| 99 | GI barbed wire anticlimbing device 3 kg per support |
| 100 | Back clamp for anticlimbing device 25x3 mm flat(GI) 0.59 kg/mtr flat(GI) of 0.510 mtr length 8 nos =(4x0.59x0.510) |
| 101 | GI Nut Bolt & Washer of different sizes (0.5 Kg/Pole) |
| 102 | Black Pain (GIS Numbering & Zebra Stripping) |
| 103 | Yellow Colour PAINT (GIS Numbering & Zebra stripping) for Back ground |
| 104 | Civil & Services Fixing of LT Complete stay setincluds -I) Turn Buckle Assembly2) Stay Rod & Stay wire -3) Stay Insulator 4) Stay wire 5) Stay clamps with Nuts & bolts including excavation, supply of 0.5Cum cement concrete foundation 1:2:4 size ( 500mmx500mmx800mm )using 20mm BHG metal with all labur and materials(Excavation of earth will be done of size 500x500x1500 mm) |
| 105 | Concreting 1.1.5:3 (M 20 Grade) (500 mmx500mmx1500mm)=0.375 Cu.mtr (Per Pole) |
| 106 | Construction Earthing chamber including installation of earthing pipe Making earthing chamber including excavation ,soil treatment with bentonite powder calculation of earh resistance , including installation of 3 mtr GI pipe 40mm/50mm including welding of Flat (GI) around pipe Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 7 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender