Project Description

Tender for Construction Of Animal Husbandary Departmental Building Along With Residential Quarter For Doctors Of S/U Darhal

BOQ

Name of Work:- Construction of Animal husbandary departmental building along with residential quarter for Doctors of S/U Darhal
Sl. No. Item Description
1Earth work in bulk excavation by mechanical means (hydraulic excavator) over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 m2 on plan) including disposal of excavated earth lead upto 50 meters and lift upto 1.5 m, as directed by Engineer-in-Charge. All kinds of soil
2Earth work in bulk excavation by manual means over areas (exceeding 30 cm indepth, 1.5 m in width as well as 10 m2 on plan) including disposal of excavated earthlead upto 50 meters and lift upto 1.5 m, as directed by Engineer-in-Charge. All kinds of soil
3Extra for every additional lift of 1.5 m or part thereof in excavation/banking excavated or stacked material :All kinds of soil
4Stone filling hand packed in horizontal on level including cost of stones.
5Providing and laying in position cement concrete of specified grade including curing butexcluding the cost of centring and shuttering. All work upto plinth level with:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
6Reinforced cement concrete work in walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts upto floor five level including curing but excluding cost of centering shuttering, finishing and reinforcement. 1:1½:3 (1 cement : 1½ coarse sand : 3 graded stone aggregate 20 mm nominal size)
7Demolishing stone rubble masonry manually/by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 meters lead as per direction of Engineer-in-charge: In cement mortar
8Dismantling roofing including ridges, hips valleys and gutters etc., and stacking the material within 50 meters lead of : G.S. Sheet
9Dismantling wood work in frames, trusses, purlins and rafters upto 10 meters span and 5 meters height including stacking the material within 50 meters lead : Of sectional area 40 sqcm. and above.
10Demolishing cement concrete manually/by mechanical means including disposal of material within 50 meters lead as per direction of Engineer-incharge: 1:3:6 or richer mix (i/c equivalent design mix)
11Supply and filling good earth in layers not exceeding 150 mm in thickness including watering, rolling loading unloading all complete carriage upto site
12Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 meters lead : Of area of 3 sqm. and below
13Providing & fixing upto floor five level precast cement concrete hollow blocks, including hoisting and setting in position in cement mortar 1:3 (1cement:3 coarse sand), cost of required centring, shuttering and curing complete 1:2:4 (1 cement : 2 coarse sand : 4 graded crushed stone aggregate 20 mm nominal size)
14Structural steel work in single section, fixed with or without connectingplate, including cutting, hoisting, fixing in position and applying a primingcoat of approved steel primer all complete
15Structural steel work in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete Welded
16Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-incharge. Made of G.I. wire of dia 4 mm
17Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead upto 50 m and lift upto 1.5 m.
18Supplying and filling in plinth with fine sand under floors including, watering, ramming, consolidating and dressing complete
19Providing and laying in position machine batched and machine mixed design mix M-25grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-incharge. Note: - Cement in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is content considered payable or recoverable separately. All works upto plinth level
20All works above plinth level upto floor V level
21Add or deduct for using more or less cement in the items of design mix over and above the specified cement content therein
22Providing and laying in position cement concrete of specified grade including curing butexcluding the cost of centring and shuttering. All work upto plinth level with:1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)
23Centering and shuttering including strutting, propping, etc and removal of form work for
24foundations , footings ,bases of columns, Plinth Beams etc.
25suspended floors,roofs,landings,balconies and access platforms, stairs and spiral stairs cases.
26Lintel, beams, plinth beams, girders, bressumers and cantilevers.
27Columns, pillars, piers, abutments, posts and struts.
28Stairs (excluding landings) except spiral staircases
29Edges of slabs and breaks in floors and walls Under 20 cm wide
30Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing inposition and binding all complete upto plinth level Thermo-Mechanically Treated bars of grade Fe-500D or more.
31Brick work with common burnt clay (non-modular) bricks of class designation 7.5 in foundation and plinth including curing in Cement mortar 1:6 ( 1 cement : 6 coarse sand) .Extra for brick work with common burnt clay bricks/cement concrete bricks in superstructure above plinth level upto floor five level
32Half brick masonry with common burnt clay (non-modular) bricks of class designation7.5 in foundations and plinth including curing in :Cement mortar 1:3 ( 1 cement : 3 coarse sand)
33Providing wood work in frames of doors, windows, clerestory windows andother frames, wrought framed and fixed in position with hold fast lugs or withdash fasteners of required dia and length (hold fast lugs or with dash fasteners shall be paid for separately):
34Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embeddings in cement concrete block 30x10x15 cm 1:3:6 mix ( 1 cement : 3 coarse sand : 6 gradedstone aggregate 20 mm nominal size
35Providing and fixing panelled or panelled and glazed shutters for doors, windows and clerestory windows fixing with butt hinges of required size with necessary screws, excluding panelling which will be paid for separately, all complete as per direction of Engineer-in-charge. First class kail wood (35mm Thick)
36Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured). Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick First class kail wood
37Providing and fixing glazed shutters for doors, windows and clerestory windows using 4mm thick float glass panes including ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws.First class kail wood 35 mm thick
38Providing and fixing wire gauze shutters using galvanized M.S. wire gauze ofaverage width for aperture 1.4 mm in both directions with wire of dia. 0.63 mm for doors, windows and clerestory windows with ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws as per direction ofEngineer-in-charge :first class kail wood
39Providing and fixing 3.5mm including cost and fixing wooden fillets/ beeding of required size and shape with nail incl all carriage complete
40Providing and fixing aluminum sliding door bolts ISI marked anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete : 250x16 mm
41Providing and fixing aluminum tower bolts ISI marked anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete
42200x10mm
43100 x 10mm
44Providing and fixing aluminum handles ISI marked anodized (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade with necessary screws etc. complete.
45150mm
46100mm
47Providing and fixing aluminum hanging floor door stopper, ISI marked, anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete :Single rubber stopper
48Providing and fixing PVC rigid foam sheet 1mm thick on existing door shutters (bathroom and W.C. doors) using synthetic rubber based adhesive and other allied fixing material to fix it properly on base complete job
49Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622 of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1cement :4 coarse sand) including grouting the joints with white cement and matching pigments etc. complete Size of tile 600 mm x 600 mm
50Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying :(a) First layer of slurry of cement @ 0.488 kg/sqm mixed with with water proofing cement compound @ 0.253kg/ sqm. This layer will be allowed to air cure for 4 hours.(b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm . This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours.The rate includes reparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry.
51Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer- in-Charge, in skirting, risers of steps and dados over 12 mm thick bed of cement mortar 1:3 ( 1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3 kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
526 mm cement plaster of mix :1:6 (1 cement: 6 fine sand)
5312 mm cement plaster of mix :1:6 (1 cement: 6 fine sand)
5415mm Cement plaster on the rough side of single or half brick wall of mix: 1 : 4 ( 1 cement : 4 fine sand). Complete job
55Providing and applying white cement based putty of specified thickness, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. ( 2mm Thick)
56Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound) content. With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre
57Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound) content less than 50 grams/ liter of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour. (Two Coats)
58Finishing walls with water proofing cement paint of required shade onNew work (two or more coats applied @ 3.84 kg/10sqm)
59Applying priming coat with ready mixed pink or grey primer of approved brand and manufacture on wood work (hard and soft wood).
60Painting with synthetic enamel paint of approved brand and manufacture of required color to give an even shade. Two or more coats on new work.
61Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservoir, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI- 212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of selfhealing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-incharge. The product performance shall carry guarantee for 10 years against any leakage. For vertical surface two coats @ 0.70 kg per sqm
62For horizontal surface one coat @1.10 kg per sqm.
63Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes channels, plates etc. including welding ,grinding, buffing, polishingand making curvature (wherever required) and fitting the same withnecessary stainless steel nuts and bolts complete ,including fixing the railing with necessary accessories and stainless steel dash fasteners, stainless steel bolts etc. of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be consideredexcluding fixing accessories such as nuts, bolts, fasteners etc.).
64Structural steel work in single section, fixed with or without connectingplate, including cutting, hoisting, fixing in position and applying a primingcoat of approved steel primer all complete.
65Providing and fixing gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels Granite of any colour or shade (18mm Thick)
66Providing edge moulding to 18 mm marble stone /granite stone counters, Vanities etc.including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge (Granite Work) Double moulding
67ELECTRICAL ITEMS
68Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required
69Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
70Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
712 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire(in minimum 20mm)
722 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire(in minimum 20mm)
732 X 4 sq. mm +1 X 4 sq. mm earth wire(in minimum 20mm)
742 X 6 sq. mm +1 X 6 sq. mm earth wire(in minimum 25mm)
754 X 10 sq. mm + 2 X 6 sq. mm earth wire(in minimum 40mm)
76Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
77Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
78Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlet and 2 Nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in Labs).
79Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
80Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
81Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required.
82Supplying and fixing call bell/ buzzer suitable for single phase,230 V, complete as required.
83Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way , Double door
8412 way, Double door
85Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator)6 way (4 + 18), Double door
86Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
87Double pole
88Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
89Supplying and fixing following rating, double pole, 240 V, MCB(10kA) in the existing MCB DB complete with connections, testing and commissioning etc. as required.25A
90Supplying and fixing following rating, four pole, 415 V, MCB(10kA) in the existing MCB DB complete with connections, testing and commissioning etc. as required.40A
91Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required 25A
92Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with testing and commissioning etc. as required.For 6 way, Double door SPN MCBDB
93For 10 way, Double door SPN MCBDB
94Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required.For 6 way, Double door TPN MCBDB
95LED Down lighter (SMD Type) (System lumen efficacy ≥120<135lm/Watt)Supplying, installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round /square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), life time of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. \\"complete in all respect i/c external connections with 1.5 sqmm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120<135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).owder coated die cast /Extruded aluminium Body including trim8 - 10 watt.
96LED Down lighter (SMD Type) (System lumen efficacy ≥120<135lm/Watt)Supplying, installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round /square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), life time of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. \\"complete in all respect i/c external connections with 1.5 sqmm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120<135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).owder coated die cast /Extruded aluminium Body including trim.12-15 watt
97LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120lm/Watt)Supplying, installation, Testing & Commissioning of LED Recessed / surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim 18 watt
98Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver& electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum powerconsumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copperconductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved byEngineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
99Supply, installation, testing, commissioning and numbering of indoor type 10W surface/wall mounted LED batten fitting (Mirror Light) covered by diffuser, high efficiency reflecctor, prewired electronic driver complete with all accessories suitable for operation on single phase 240V 50Hz AC supply as required. LED shall be SMD type. ( similar to BCLSB 10W LED Mirror light or equivalent)
100SITC of 3W LED Unidirectional Exit Signage Light with inbuilt 2 hours battery back up .
101Brush Less DIrect Current (BLDC) Motor Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al bodyPower Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (prefreably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req.1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210CM/Min (Minimum)
102Supply, Installation, Testing and Commissioning of 300mm dia sweep PVC body, 900±10% RPM Exhaust fan with guard and mounting arrangement.
103Supply of following sizes of Power Cables multi stranded Aluminium conductor, XLPE Insulated, cores laid up PVC tape / Extruded Inner sheath , Armour, FRLS at outer sheath,1100V grade as per IS 7098(Part 1) 1988 with upto date amendments.
104Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
105Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required 4 X 25 sq. mm (28mm) 4 X 25 sq. mm (28mm)
106Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.63 mm dia (OD-63 mm & ID-51 mm nominal)
107120 mm dia (OD-120 mm & ID-103 mm nominal)
108Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.
109Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
110Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
111Providing and fixing 32 mm X 6 mm G.I. strip on surface or in recess for connections etc. as required.
112Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
113Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
114Supplying, installation, testing and commissioning of following bolted fabricated in compartmentalized conform to IS: 8623/1993, Suitable for 415V, 3Phase, 4 Wire 50 Hz Ac supply, are housed in design from CRCA sheet steel of 2mm thick for frame work and covers, 3mm thick for gland plate, bottom base channel of MS section not less than 100mmx 50mmx50mmx 5mm thick for Main L.T. Panel and capacitor panels and 40mmx25mmx25mmx 5mm thickplates for MDB/MCC and SDBs etc., The degree of protection of minimum IP:42 for indoor and IP:65 for outdoor use.
115i/c cleaning & finishing complete, having extensible type aluminium bus bars of high conductivity, SMC bus bar supports, with short circuit withstand capacity of 31MVA for 1 Sec., fabrication shall be done in transportable sections and all front and back doors shall be hinged type and earth with frame, Entire panel shall have a common aluminium earth bar of size 32mm x 6mm or as specified below at the rear with 2 Nos. earth stud each side, solid inter connections from main bus bar to switch gears upto cable alley, bus bars and control wiring with suitable size of ZHLS PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, i/c providing following switch gears :-
116The Bus bars will be Copper purity 99.9% / electrolytic grade E91 Aluminium duly sleeved with Helogen Free heat shrink coloured Insulated tube confirming to IEC 6068-3-247 Standard. Provide electrical insulating shrouds, reusable type covers for busbars Boots on corners Panels will be powder coating (60-80micron as per IS:13871 for indoor and 90-100 micron for outdoor), include one size higher terminal block in cable alley and interconnecting wires between bus bars and terminals via MCB. All Bus-Bar alley and relay compartments shall be provide fully automtic control thermotate with strip heater.
117Also, refer to General Notes and Specifications for Panels/ Boards.
118Contractor to submit manufacturer's Total discrimination curves prove the same, insulation material & corners cover on bus-bars for approval. Feeders should be totally bolted structure with interchangeable feeder.
119All live accessible parts shall be shrouded and all equipment shall be finger touch proof. SMC shrouds bus bar supports shall be used. Padlocking facility shall be provided on all MCCB feeder doors and switch handles shall be lockable in OFF position.
120Sealing Arrangement :- PE Foam Rubber Gasket
121Bus Bars Supports - Non-Hygroscopic, Non Carbonising, Corrosion Resistant, SMC Supports
1221Set of connector (Phase+Neutral) shall be provided in cable alley for all outgoing with interconnection wires between MCB and Connector.
123Minimum Air Clearances between bus bars shall be as per IEC 61439 Clause 8.2.5;
124Panel Power and control Wiring all ZHLS PVC insulated
125AC voltage circuit-1.5 sqmm Red,Yellow,Blue &Black
126Current circuit-1.5 sqmm Red,Yellow,Blue &Black
127AC Control circuit-1.5 sqmm White for Phase & Black for Neutral
128DC Control circuit-2.5 sqmm Grey
129Power circuit- Red,Yellow,Blue for Phase &Black for Neutral
130Labeling- Computerised Laminated Aluminium Name Plate with White letters on Blue/Black Background For Each Feeder and Panel Itself.
1311) If mentioned fault and Automatic transfer switch rating is unavailable consider nearby upside rating
1322) A separate compartment for Minimum 20% spare space of Panel shall be provided for outgoings in future and busbars shall be drilled accordingly.
1333) Total Discrimination of system shall be checked and required setting shall be made. If any component required to change will change free of cost. The switch-gear & Panel manufacturer (jointly) will submit discrimination check report duly checked and signed on company letter head.
134GENERAL NOTES FOR ACB's:
135ACB shall be with 4 NO + 4 NC Auxiliary contacts.
136Safety Shutter.
137Door Sealing Frame.
138Inbuilt Ethernet Port
139Inbuilt TRIP LED indication.
140ON/ OFF/ TRIP status on Ethernet
141Ics = Icu = Icw for 1 sec. for the breakers.
142With built in micro-processor based releases: ( digitally upgradable)
143Adjustable over current with time setting.
144Adjustable short circuit with time setting.
145Instantaneous short circuit.
146Adjustable earth fault with time setting.
147Power wiring with one size higher terminals / bus bars for termination of cables as specified.
148There shall be no deration upto 50 degree celcius.
149ACBs shall be provided with both side terminal adaptors (Preferably Hr Vr)
150All the ACBs must be equipped with features like ZSI, Thermal Memory, last 10 trip histories, current & Voltage Metering, % loading Bar graph, LED fault differentiation, display of per phase energy & Total Harmonics Distortion
151GENERAL NOTES FOR MCCB's:
152MCCB's shall be of TPN (3P with solid neutral link) or 4P as called for in the BOQ.
153Ics = Icu = 100% or more for the breakers.
154All Thermal Magnetic MCCB's shall have adjustable over current and Fixed short circuit if used as outgoing and when used as incomer short circuit rating shall be adjustable.
155All micro-processor based MCCB's shall have adjustable over current with time setting, adjustable short circuit and Adjustable earth fault with indication due to earth fault.
156MCCB's shall be with extended rotary handle with Phase spreaders & Phase Barriers at both sides
157MCCB's shall have auxiliary contacts for BMS compatibility.
158All MCCBs above 250A shall be microprocessor based. Thermal Magnetic MCCBs shall have modular external earth fault protection
159All the MCCBs in Main Panel to communicate ON/OFF/TRIP status on Ethernet.
160GENERAL NOTES FOR MCB's:
161MCB's shall be of minimum 10kA breaking capacity for 1 sec
162Use 'B' curve MCB's for lighting & small power circuits, 'C' curve for motor duty i.e. for pumps, AC motors, AHU motors, window and split AC's etc. & 'D' curve for UPS DB's i.e. for computers/ PC's circuit. Main Incomer & outgoing circuit MCB's shall be selected accordingly i.e. type B,C & D. as per the nature of the circuit/ load.
163Exact MCB rating & category is to be calculated by the electrical contractor based on the final load of the circuit, its nature and fault current.
164Meter Panel Board-1 (INDOOR PANEL-IP:42) MPB-1
165INCOMER
1661 Nos. 63A 4P MCCB built in thermal magnetic based release (adjustable O/L, adjustable S/C) of fault breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall conforming to IS-1397-2 1993 as amended Complete with Lock & sealing arrangement
167BUSBAR
168100Amps 4P, 35kA, 500volts grade busbar chamber of suitable length with Aluminium busbars. All interconnections shall be with Aluminium Bus-bars, current density of bus-bars shall not be less than 1.3 Amps/sq.mm for Aluminium cross sectional area of Bus Bar Complete with Lock & sealing arrangement
169INDICATIONS
1701Set of R,Y,B phase indication lamps with 4Nos. SP HRC fuses as per fault requirement for each Incomer.
171OUTGOINGS
1722 Nos. Minimum diamension of 400MM (H) x 300MM(W), Glass window compartment each with Lock & sealing arrangement including backelite sheet for mounting existing three Phase pre-paid Energy Meter by SEB (PDD) and 4 x 10.0sqmm FR PVC copper power wiring colour coded between Meter and busbar. Name plate should also be provided as per flat numbing provided client
1732 Nos. 40A,4P, MCB, 10kA in separate compartment on top of Meter compartment each with Lock & sealing arrangement for each MCB and 4 x 10.0sqmm FR PVC copper power wiring colour coded between Meter and MCB. Name plate should also be provided as per flat numbing provided client.
1743 Nos. 25A,2P, MCB
1752 Nos. 40A,4P, MCB
176MPB-1 as described above.
177Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS) system suitable for Single Phase input, Single Phase output AC Supply. The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. The UPS systems shall be Microprocessor based Digital Control, using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter with PWM (Pulse Width Modulation) Technology.The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE.The operating efficiency of the UPS systems shall be >95% at 100% non-linear loads. Current total harmonic distortion (ITHD)/ total demand distortion (TDD) on the input grid shall be < 5% at 100 %load. (The required LC filters shall be included in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ) however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC single phase 160-270V 50 Hz and delivering output AC supply true sine wave single phase 220/230/240 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins and 150% for 1 minute. Operating temperature 0 to 40 0C, Relative humidity 0-95% non condensing, noise level less than 60db at 1 meter distance, Protection for Under voltage,over voltage, abnormal output voltage, battery over charging, output over current, short circuit, battery deep discharge 10 KV surge. Display for watt/VA,Amp and
178UPS shall comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI) type UPS (as per standard IEC 62040-1, 2 & 3) . The UPS should be with IGBT Based Inverter Technology, Communication RS232/ RS485/ SNMP port open protocol for BMS integration as per approved by Engineering in charge. Required battery racks, DC breaker of suitable rating and interconnecting copper conductor cable of suitable size and connectors and all required accessories are inclusive in the cost. The UPS should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc
179Supply, installation, testing and commissioning of Non- PCB based Information Outlet (I/O) RJ45 for following systems, Tooless Termination TIA-568C Category-6, Termination of Catergory-6 UTP Cable, UL listed, Shall confirm to EIA/TIA-568C.2 Certified by independent labs like ETL/GHMT/3P, Shall have minimum duraility of 950 or above mating cycles and 200 termination cycles minimum complete in all respect.
180Active Data
181Redundant Data
182IP Voice
183Analoge Voice
184Supply, installation, testing and commissioning of Spring shuttered type Single/ Double Port (RJ45) plate of the suitable size required as per site condition & box dimentions complete in all respect.
185Supply and fixing 1 or 2 Module (suitable to OEM), 0.8mm thick GI box in recess/ PVC box where surface mount etc as required.
186Supply, installation, testing and commissioning of 8 ports UTP Jack Panel, fully loaded for Non-PCB based IO Jacks (RJ45 Category-6), complying to TIA-568.C.2 complete as required.
187Supplying, laying, dressing, ferruling and terminations at both ends of 24AWG 4-pair Category 6 UTP (Unshielded twisted pair) 1Meter Patch cord with a cross filler (+), modular plug at each end confirming to TIA -568C.2, tested till 250 MHz, Shall be FR-LS-ZH as per IEC:60332-1, IEC 61034-2 & IEC 60754-1 respectively. All patch cords shall be compatible with both T568A and T568B wiring schemes complete as required.
188Supplying, laying, dressing, ferruling and terminations at both ends of 24AWG 4-pair Category 6 UTP (Unshielded twisted pair) cable with a cross filler (+), confirming to TIA -568C.2, tested till 250 MHz, Shall be FR-LS-ZH as per IEC:60332-1, IEC 61034-2 & IEC 60754-1 respectively.
189Penta testing, Documentation & Certification of Cat6 cable.
190OUTDOOR TELEPHONE AND INTERCOM CABLING- (Jelly filled Ar. Cables)
191Supply & laying including termination at both ends and ferruling of following sizes of 0.5mm dia tinned Copper conductor, PVC insulated, sheathed, Jelly filled armoured telephone cables
192KRONE BOX
19320 pair tele tag block
194DATA/SERVER/ NETWORKS RACKS
195Supply & installation of 36U (800mm(W) X 800mm (D) Open/Closed type floor standing/wall mounted cabinet with/without 4Nos. unidirectional wheels steel sheet enclosure with glassed front door and perforated rear door powder coated black (RAL 9002/9003) confirms to DIN 41494 and EIA 310 standards side panels with slam lateches, top cover, ventilation fan & fins, cable entry cut-outs and gland plates,levelling legs, Ventillation grills on all sides for housing Equipment with 2Nos. vertical mounted Power strip each consisting of 18Nos 6A power socket and backed up 32A SP MCB with indicator of ON, tray and all hardwares complete with all necessary accessories as required as per approved drawings, specifications of this tender and directions of Engineer-in-Charge
196Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required 25mm
197IT/ NETWORKING ACTIVE WORKS
198IP PBX
199Supply, Installation, Testing & Commissioning of Type 1 IP Phone 1 VoIP account , Full duplex speaker phone, IPV6, 2xLAN, PoE . Approved Makes: Tadiran/Arista /Polycom/Toshiba/ Aeonix
200SITC of Analog Telephone Instruments with CLI Facility,Flash, Redial, Tone & Pulse Dailing.Approved Make: Beetel/Protel/BPL
201Wi-Fi
202Supply, Installation, Testing & Commissioning of the Microservices based WLAN Architecture. The indoor AP should have radios to support 2.4Ghz and 5 Ghz band in a 4X4:4 Mu-MIMO configuration with support for 802.11 a/b/g/n/ac. The AP should have internal Omni Antennas and should support vBLE and RF optimization. It should also support way finding and asset tracking via bluetooth.Should support Artificial Intelligence platform, WIPS/WIDS to detct Rogue APs and the facility to terminate connevction to the Rogue APs.Plenum rated and support for UL 60950-1 CAN/CSAC22.2 No. 60950-1, FCC Part 15.247, 15.407, 15.107, and 15.109 RSS247 ICES003
203SUB-HEAD-II: IP CCTV SYSTEM
204Note- All the bidders must attach authorization certificate and each product's technical sheet & cat. number of any one make from the OEM alongwith bid. This is must unless otherwise bid will be rejected wihout MAF.
205Supply, installation, testing and commissioning of UL Listed, IP CCTV Coloured Dome camera, 2.0 Megapixel ( 1920 x 1080 )@ 25 FPS, High resolution, 1/2.8/ 1/3\\" Progreesive scan CMOS, 2.8 mm Lens,High-performance and long service life Infrared LED, Approx. 30 meters Support 120dB wide dynamic range ,H.265, tripple stream, Bit rate 32kbps - 16 Mbps, PoE (802.3af) with ONVIF profiles supported, IP 66, shall support analytic - motion detection, intrusion detection, suport 128 gb SD card( SD Card not included) with ANR function, fixed type for mounting recessed in false ceiling or mounted on wall. Make Hikvision DS-2CD2123G0-I or equivalent.
206Supply, installation, testing and commissioning of UL Listed 4 Ch Smart Network Video Recorder : Connect Up to 16 IP Cameras, Dual OS, Up to 8 Megapixels Resolution, HDMI - 4K/ VGA -2MP Output , Support H.265, MJPEG, Incoming Bandwidth 256Mbps, 4 SATA Hard Disks, ANR Technology, 4 SATA interfaces for 4 HDDs and capacity of each HDD upto 6TB, front panel: 2 × USB 2.0 rear panel: 1 × USB 3.0, Alarm I/O 16/4, RS-485, RS-232, 2 RJ-45 10 /100/1000 Mbps self-adaptive Ethernet interface, Multiple network monitoring: Web viewer. Make Hikvision DS-7716NI-K4I or equivalent.
207SITC of (24/7) working VIDEO SURVELLIANCE HARD DISK 6TB.
208Supply, Installation, Testing and Commissioning of LED Display Monitor 40\\" high resolution, Diagonal size :40\\", Type 60 Hz LED BLU, Resolution 1,366 x 768 (16:9), Brightness 330 nit, Contrast ratio 4,000:1, Display colors 16.7 M, Dynamic C/R 50,000:1 (AV mode), Connectivity HDMI, VGA, Power supply AC 100 - 240 V ~ (+/- 10%), 50/60 Hz, Operating temperature 0°C - 40°C (32°F - 104°F), Built-in speaker (10 W + 10 W), PIP/PBP, narrow bezel, light weight, RS-232C in/out 1 D-sub and 1 HDMI, no function key, 3 Star Rating
209Supply, installation, testing and commissioning of Non- PCB based Information Outlet (I/O) RJ45 for following systems, Tooless Termination TIA-568C Category-6, Termination of Catergory-6 UTP Cable, UL listed, Shall confirm to EIA/TIA-568C.2 Certified by independent labs like ETL/GHMT/3P, Shall have minimum duraility of 950 or above mating cycles and 200 termination cycles minimum complete in all respect.
210Supply, installation, testing and commissioning of Spring shuttered type Single/ Double Port (RJ45) plate of the suitable size required as per site condition & box dimentions complete in all respect.
211Supply and fixing 1 or 2 Module (suitable to OEM), 0.8mm thick GI box in recess/ PVC box where surface mount etc as required.
212Supply, installation, testing and commissioning of 8 port PoE Switch with PoE standard of IEEE 802.3af , IEEE 802.3at, PoE port, Uplink ports. Make- Hikvision DS-3E0318P-E or equivalent.
213Supply, installation, testing and commissioning of 24 ports UTP Jack Panel, fully loaded for Non-PCB based IO Jacks (RJ45 Category-6), complying to TIA-568.C.2 complete as required.
214Supplying, laying, dressing, ferruling and terminations at both ends of 24AWG 4-pair Category 6 UTP (Unshielded twisted pair) 1Meter Patch cord with a cross filler (+), modular plug at each end confirming to TIA -568C.2, tested till 250 MHz, Shall be FR-LS-ZH as per IEC:60332-1, IEC 61034-2 & IEC 60754-1 respectively. All patch cords shall be compatible with both T568A and T568B wiring schemes complete as required.
215Supplying, laying, dressing, ferruling and terminations at both ends of 24AWG 4-pair Category 6 UTP (Unshielded twisted pair) 2Meter Patch cord with a cross filler (+), modular plug at each end confirming to TIA -568C.2, tested till 250 MHz, Shall be FR-LS-ZH as per IEC:60332-1, IEC 61034-2 & IEC 60754-1 respectively. All patch cords shall be compatible with both T568A and T568B wiring schemes complete as required.
216Supplying, laying, dressing, ferruling and terminations at both ends of 24AWG 4-pair Category 6 UTP (Unshielded twisted pair) cable with a cross filler (+), confirming to TIA -568C.2, tested till 250 MHz, Shall be FR-LS-ZH as per IEC:60332-1, IEC 61034-2 & IEC 60754-1 respectively.
217Penta testing, Documentation & Certification of Cat6 cable.
218Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.25mm
219PLUMBERING -SANITARY FIXTURES
220Providing and fixing Floor mounted white vitrous china double trap syphonic WC with 10 litre cistern and all fittings & fixtures,seat cover etc with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required :W.C. pan with ISI marked white solid plastic seat and lid
221Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever required White Vitreous China Wash basin size 630x450 mm with a pair of 15 mm C.P. brass pillar taps
222providing and fixing cp brass 32mm size bottle trap of approved quality & make and as per the direction of engineer-in-charge 32mm dia
223Providing and fixing Braided Hoses with Two 15mm CP Brass Nuts & Rubber Washers Without Nipple (Suitable for Geysers and basins) of approved make 45 cm length 15 mm nominal bore
224Providing and fixing toilet paper holder :CP Brass
225Providing,Fixing,testing and commissioning of CP brass twin coat hook with concealed screws.
226Providing and Fixing Health Faucet 15mmdia with CP flush pipe, CP nozzel hook complete including CP flange etc.
227Providing,Fixing,testing and commissioning of CP brass towel ring hook with concealed screw
228Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 15mm nominal bore
229Providing and fixing PTMT soap dish holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106gms.
230Providing and fixing horzontal/vertical Hot water geyser made of MS body with copper jacket inside with necessary inlet, outlet, drain, overflow, vent and all safety accessories etc. complete including cutting and making good the walls, wherever required. 25 lit for shower
231Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
232Providing ,Fixing, testing and commissioning of solid state, no touch operting, fully hygienic hand drier of approved shade with single blower, with time delay, summer & winter control, music while drying, volume ON/OFF controls including providing necessary brackets, cable from drier to Plug, Plug top key and lock etc, complete as required
233Providing and fixing UV stabilised UPVC pipes, Type B as per IS:13592 for soil, waste, rain water and vent, including all fittings with or without access i.e Clean out plug,bends, junctions, cowls, offsets, couplers, connectors, heavy duty Metal pipe clamps with rubber seal/clips//holders etc. and jointing with heavy duty solvent cement, complete as per manufacturer's specifications and making good the same, complete as directed by the Engineer-in-Charge. (vertical pipes can be jointed through rubber O rings)
234Inclouding cement concrete 1:2:4 mix (1 cement :2 coarse sand :4 graded stone aggregate, 20 mm down gauge) 75 mm in bed and all around soil and waste pipes under floor, including shuttering and centering for: 75mm outer dia
235110mm outer dia.
236Providing and fixing thermal insulation over pipes/fitting/Trap Etc as req. in exposed/chase with 32 mm thick approved equivalent thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber having density of 60-90 Kg/m3 over pipes of following sizes including all required accessories complete as per manufacturer's specifications and finishing it with 6mm thick rough plaster of 1:3 mix (1 Portland Cement : 3 hard settling cement compound)(Make-K-Flex,Eurobatex,Vidoflex.)75mm outer dia
237110mm outer dia.
238Providing and fixing M.S. holder-bat clamps of approved design to Sand Cast iron/cast iron (spun) pipe embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including cost of cutting holes and making good the walls etc. 100mm dia pipe
239Providing and fixing multi inlet uPVC floor trap with minimum 50mm water seal of self cleaning design with 110 mm outlet consisting of all necessary fittings and provding strainer of 150 x 150 mm square stainless steel 2 mm thk frame with slotted lockable grating on top of the trap level matching the level of floor finish etc, complete including cost of cutting and making good the walls and floors wherever required and as directed by Engineer in charge. (The inlet diameter shall be 32mm, 40mm or 50mm as per site requirements)
240Providing and fixing uPVC pipe as per IS 4985, Class-3, 6Kg/cm2 with cement solvent joint, complete with all fittings and clamps etc including cutting and making good the walls and floors for waste pipes from wash basins, urinals, sinks & balcony drainage, as directed by the Engineer-in-charge.32mm OD
24140 mm OD
242Providing and fixing SS grating with frame including fixing to the floor with cement mortar.100mm dia
243Providing and fixing 110mmx50mm outlet. UPVC floor drain consisting of all necessary fittings and provding strainer of 150 x 150 mm square stainless steel 2 mm thk frame with slotted lockable grating on top of the trap level matching the level of floor finish etc all complete as per specifications and direction of Engineer-In-Charge.
244PP-R should be a complete installation system consisting of pipes and fittings of a thermoplastic polopropylene PP-R 3-layer glass fibre compound (type 3/ type 4) of PN20 (SDR 6)/PN16 (SDR 7.4) and PP-RCT (SDR9 and SDR11) within a range of diameters 20-200 mm in Green/Grey colour of pipe dimension series in accordance with EN ISO 4065 having linear expansion of 0.05 mm/mK with DVGW and QB/CSTB certification as per EN ISO 15874-2:2013-06E, EN ISO 15874-3:2013-06E standard. System elements are connected by muff-welding (thermal polyfusion) or electrofusions welding with the use of electric welders. The welding technology i.e. uniform connections, guarantees an exceptional leak-tightness and mechanical strenth of a system and use for internal and external water supply, cooling systems (hot and cold water), production process industrial systems and use in shafts, basements, terrace with insulation. : MAKE : KAN-therm, Aquatherm, Poloplast Concealed work including cutting chases and making good the wall.16x2 mm outer dia pipe
24520x2 mm pipe
24625x2.5 mm outer dia pipe
247PP-R should be a complete installation system consisting of pipes and fittings of a thermoplastic polopropylene PP-R 3-layer glass fibre compound (type 3/ type 4) of PN20 (SDR 6)/PN16 (SDR 7.4) and PP-RCT (SDR9 and SDR11) within a range of diameters 20-200 mm in Green/Grey colour of pipe dimension series in accordance with EN ISO 4065 having linear expansion of 0.05 mm/mK with DVGW and QB/CSTB certification as per EN ISO 15874-2:2013-06E, EN ISO 15874-3:2013-06E standard. System elements are connected by muff-welding (thermal polyfusion) or electrofusions welding with the use of electric welders. The welding technology i.e. uniform connections, guarantees an exceptional leak-tightness and mechanical strenth of a system and use for internal and external water supply, cooling systems (hot and cold water), production process industrial systems and use in shafts, basements, terrace with insulation. : MAKE : KAN-therm, Aquatherm, Poloplast Exposed on wall/terrace16x2 mm outer dia pipe
24820x2 mm outer dia pipe
24925x2.5 mm outer dia pipe
250Providing and fixing thermal insulation overr pipes in exposed/chase with 32 mm thick approved equivalent thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber having density of 60-90 Kg/m3 over pipes of following sizes including all required accessories complete as per manufacturer's specifications and finishing it with 6mm thick rough plaster of 1:3 mix (1 Portland Cement : 3 hard settling cement compound)(Make-K-Flex,Eurobatex,Vidoflex.) 25mm dia
251Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete15mm nominal bore
25220 mm nominal bore
25325 mm nominal bore
254Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.
255Excavating trenches of required width for pipes, cables etc. including excavation for sockets and dressing of sides, ramming of bottoms, depth upto 1.5 M including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cms in depth including consolidating each deposited layer by ramming, watering etc. and disposing of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia. Metre
256Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement: 2 fine sand) including testing of joints etc. complete150mm dia RCC pipe
257250 mm dia. R.C.C. pipe
258Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating Brick block masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design :180x150 mm size P type With Sewer Brick block conforming to IS : 4885
259Constructing Brick block masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone- III) : 8 graded stone aggregate 40 mm nominal size),inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design :Inside size 90x80 cms and 45 cms deep including CI cover with frame (Light duty) 610x455mm internal diamesions total weight of cover and frame to be not less than 38 kg ( weight of cover 23 kg and weight of frame 15 kg) With Sewer Brick block conforming to IS : 4885
260Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated asper IS: 10910 on 12mm dia steel bar conforming to IS :1786 having minimun cross section as 23 mm x 25 mm and over all minimum length 263mm and width as 165mm with minimum 112mm space between protruded legs having 2mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and heaving manufacture\\"s permanent identification mark to be visible even after fixing \\" incluting fixing in manholes with 30x20x15 cm cement concrete block 1:3:6: (1 cement :3 coarse sand :6 graded stone aggregate 20mm nominal size )complete as per design.
261Making connection of drain or sewer line with existing manhole including breaking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement and making necessary channels for the drain etc complete.For pipes 250 to 300 mm diameter
262Constructing brick masonry road gully chamber of specified size with common burnt clay(non modular) bricks of class designation 7.5 in cement mortar 1:4 ( 1 cement : 4coarse sand) including precast R.C.C. horizontal grating with frame complete as per standard design: Chamber size 50x45x60 cm including precast R.C.C grating with frame 500x450 mm horizontal grating.
263Designing, providing, installation, testing and commissioning of PVC/FRP anaerobic Spptic tank of capacity 5000 liter.size as per manufacture of septic tank including excavation and its all acessories to make complete. ANAEROBIC SEPTIC TANK CAP-5 KL.
264Supply and installation of following types of extinguisher with provision of wall bracket (fixed with anchor fastner).ABC Stored Pressure type Fire Extinguisher 6 Kgs. capacity bearing ISI Mark for Fighting ABC Class of Fire. The Extinguisher will be Manufactured Strictly as per BIS: 15683:2006 bearing ISI. mark. EN3 615 Approved Powder. ABC 87% MAP. Complete with all accessories 6kg
265Co2 type Fire Extinguisher 4.5Kgs. Capacity, made from brand new seamless cylinder, as per IS: 7285 and CCE approval, fitted with Discharge hose and horn and Squeeze Grip type valve with initial Charge as per IS: 15683:2006 specification, bearing ISI Mark .4.5kg
266Carriage of material from source to site of work by mechanical transport including loading /unloading and stacking complete.
267Sand for an average distance of 140 kms by M.T
268Stone aggregate below 40mm for an average distance of 20 km by M.T
269stone aggrregate above 40mm for an average distance of 20km by M.T
270Bricks for an average distance of 150km by M.T
271stone for an average distance of 10 km by M.T
272Carriage of lineMoorum Building Rubbish for an average Distance of 5000mtr by M.T
273Carriage of Mulba for an average distance 5000mtr by M.T Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57896504
AUTHORITY Government Departments
TENDER VALUE 2.74 Crore
LAST DATE 21-10-2026
Authority
Authority Name Public Works Department
Work Description Tender for Construction Of Animal Husbandary Departmental Building Along With Residential Quarter For Doctors Of S/U Darhal
Basic Detail
Tender No e-NIT No. 34 of 2026-27 Dated 06.10.2026
Bidding Type Tender
Location
City Rajouri
State Jammu and Kashmir
Key Dates
Publish Date 07 Oct 2026
Submission Date 21 Oct 2026
Open Date 22 Oct 2026
Finance
Tender Value 2.74 Crore
Tender Fee 6000
EMD 5.48 Lakhs
Exemption Not Available
Document List
54f42ac3-2dde-4d80-8997-b90164998875.html
BOQ_1107263.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 07, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 21, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 3 days
Oct 22, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 4 days

Tender Documents

Download All (ZIP) ↓
html

54f42ac3-2dde-4d80-8997-b90164998875.html

xls

BOQ_1107263.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender