Tender For B.O.Q For Construction Of Clock Tower At Tangmarg Bus Adda B.W.O Electric Work
Tender Overview
Project Description
Tender for B.O.Q For Construction Of Clock Tower At Tangmarg Bus Adda B.W.O Electric Work
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 24-Oct-2026 | CORRIGENDUM | Date | 02-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | A. Internal Electrification |
| 2 | Wiring for Light point/Fan point/Exhaust fan/Bell point with (P+N+E) 3x1.5 sq.mm FRLS-H PVC insulated Multi strand Copper conductor single core cable, (Havells Lifeguard/Anchor Fireguard/Ploycab Green/Apar Shakti/Eq Make) in surface/recessed Conduits laid in slabs (Including Cost of Conduit 25mm) with 01 No.of 6 Amp Modular Switch,Modular Plate,Cover in front & suitable GI box etc ISO/IEC Certified/Schneider Zencelo/ Havells Crabtree/ Legrand Arteor/Anchor roma plus/ABB Tvisha (Anti bacterial)/Eq.Make & items shall be approved before execution of work by SDO. |
| 3 | Providing & Fixing of IK08 IP-66 protected high power LED 50 Watt flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each. Integrated potted driver as a unique BIS R number having efficiency more than 85% and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 Im/wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector, Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K 355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR:-High Power LED Flood Light Minimum lumen output 6200 Im of Havells/Crompton/Philips Make as approved and to be installed on outside block including S/F of suitable size of Gyser bolt.The job further includes replacement warranty of fixture (if damaged/burnt out what so ever reason) for a period of two years reckoned from date of successful commissioning /handing over of site to intending department. |
| 4 | Supply/Fixing/Testing and Commissioning of 6Amp to 32Amp Rating SP,240v,*C* Curve 10K, Miniature Circuit Breaker suitable for inductive load of following poles in existing MCB . DB Complete with connections.(L&T/Siemens/Legrand/Havells/ABB/Eq. Make) |
| 5 | Supply/Fixing/Testing and Commissioning of following rating, Double pole, (P+N) 240 V, C* Curve 10K,Miniature Circuit Breaker (MCB) in the existing MCB DB complete with connections. (L&T/Siemens /Legrand/Havells/ABB/Eq Make) |
| 6 | 63 Amp. |
| 7 | Supplying and Fixing of MCB way 8 way , horizontal typed , sheet steel, Double Door Distribution Board, SPN 240V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc, as required. (L&T/Siemens/Legrand/ Schneider/ABB/Eq Make) |
| 8 | B. SUPPLY OF LIGHTING FIXTURES & HARDWARE |
| 9 | Supply of High-Power RGBW Outdoor LED Linear Wall Washer Light:• Wattage: 36W, Voltage: 24V DC / 230V AC• Optics: 10° x 60° Asymmetric Beam Angle• Protection: IP66 weather-proof, IK08, Die-cast Aluminum housing, toughened glass cover• Control Protocol: DMX512 / RDM compliant for dynamic color scenes• Application: Column & Shaft illumination (36 ft Height) Aproved Makes: Havells/Wipro/Eq.make |
| 10 | Supply of RGBW Outdoor LED Narrow-Beam Architectural Spotlight:• Wattage: 24W, Beam Angle: 8° Narrow Spot• Protection: IP66 rated, extruded aluminum housing• Control Protocol: DMX512 integrated driver• Application: Top Roof Truss & Spire long-throw highlight Aproved Makes: Havells/Wipro/Eq.make |
| 11 | Supply of Heavy-Duty In-Ground / Surface Mounted RGBW LED Uplighter:• Wattage: 36W, IP67 waterproof, Stainless Steel Trim (316 grade)• Optics: 30° Medium Flood Optics• Control Protocol: DMX512• Application: Hexagonal Pedestal Base illumination (Green Zone) Aproved Makes: Havells/Wipro/Eq.make |
| 12 | C. CONTROL SYSTEM, DRIVERS & AUTOMATION HARDWARE |
| 13 | Supply of Master DMX512 Architectural Lighting Controller:• Programmable scenes (Tricolour, Warm White, Festive, Animations)• Calendar & Timer based scheduling triggers, Wi-Fi / App / Glass touch panel interface Approved Makes: LTECH/Sunlite/Eq.make |
| 14 | Supply of Central DMX Signal Splitter / Amplifier (4-Port Isolated):• DIN-rail mounted, surge protected, photoelectric isolated DMX signal distributor Aproved Makes: LTECH/Sunlite/Eq.make |
| 15 | Supply of Industrial Grade Power Supply Units (SMPS):• 24V DC Output, IP67 Waterproof enclosure, Short circuit & Overload protection Aproved Makes: Mean Well/Delta Electronics/Eq.make |
| 16 | Supply of Outdoor Weatherproof Control Panel Box:• IP65 powder-coated metallic enclosure housing controller, SMPS, MCBs, and terminal blocks Aproved Makes: Hensell/Rittal/Eq.make |
| 17 | D. CABLING, CONDUITING & ELECTRICAL BALANCE OF PLANT |
| 18 | Supply & Laying of 3-Core x 2.5 sq.mm Armored Power Cable (Copper, XLPE insulated, 1.1kV grade) through heavy-duty PVC/GI conduits on outer structure Aproved Makes: Polycab/Hacvells/Eq.make |
| 19 | Supply & Laying of 2-Pair Twisted Shielded DMX Signal Cable (UV & Weather resistant) for noise-free data communication. Approved make: Belden/Polycab/Eq.make |
| 20 | Supply & Installation of Outdoor IP68 Junction Boxes, Cable Glands, Connectors, Mounting Brackets, and Stainless Steel Fasteners |
| 21 | E. ERECTION, TESTING, COMMISSIONING & SCENE PROGRAMMING |
| 22 | Erection Works including High-Reach Scaffolding, Mobile Elevating Platforms / Safety Harness setup for 36ft tower work |
| 23 | System Testing, DMX Addressing, Scene Programming & Commissioning:• Programming Tricolour (Saffron/White/Green) Static & Breathing modes• Programming Warm White Architectural mode, Festive dynamic chases, and automatic calendar switches |
| 24 | F. Main Control Panel, Servo and Cable |
| 25 | Design,Fabrication,Supply, Installation, Testing and Commissioning of CPRI Approved Main LT Control outdoor slopped Roof,Double Door panel Floor Mounted fabricated of 16 gauge sheet steel,the panel should have standing dust & vermin proof with gasket lockable door with angle iron stand of 2.5 feet height/ground clearance properly grouted in cement concrete (If Required) of 1:2:4 ratio-filter . The Panel should be painted with Electro static powder coated colour, Siemens grey structural with proper chemical pre-treatment with film thickness 35-40 Microns,duly fitted with Voltmeter, Phase-indicators etc with baby insulators/thimbles suitable for use at 230 Volts, 50Hz system complete in all respects complete in all respects with following:-(1) Normal Incoming125-160 Amp DP MCCB with extended thimbles of Legrand/Siemens/ABB//LK make = 1 no 200 Amp P-N Bus bar Al Strips = 1 Set, Voltmeter =1 no, Ammeter = 1 no , CT coils for Am meter 300 /5A = 1 set ,phase indicator =1No.(2) Generator Incomer63 Amp Four Pole Change over switch of Legrand/Siemens/ABB//LK make = 1 no., 100 Amp P-N Bus bar Al Strips = 1 Set,Voltmeter =1 no, Ammeter = 1 no , CT coils for Am meter 300 /5A = 1 set ,phase indicator =1No.(3) Bypass Switch: Single/Three Phase, Double/Four Pole 63-100 Amp,415V Ac,50Hz Bypass Switch Seimens/LK/ABB Make for bypassing 10 KVA AVR.Outgoing .(1) 1 no 200 Amp P-N Bus bar Al Strips = 1 Set(2) 63 Amps DP MCB (10 KA) of Legrand / Siemens/ ABB /Schinder /L&T make = 02 No.The Panel manufacturing unit should be CPRI Registered and the Contractor has to submit the test certificate of main switch gear and Drawing of panel (Showing claerly dimensions of panel with spacing of switchgear as per IE Standards) is to approved by Engineer Incharge before manufacturing |
| 26 | Supply/Installation/Testing & Commissioning of 1-phase 10 KVA,50 Hz Oil cooled unbalanced type Voltage Stabilizer SERVO control of Approved brand COPPER wound of AE/Chinar/Cosco/AlBA Make ISI/1SO/IEC certified for smooth functioning/constant voltage supply having Technical Specifications :Input voltage(Ph-Ph) ranging from 90 Volts to 240 Volts and a balanced output Voltage of 230 Volts, ±2% Buck Boost Transformer Copper wound 99.9% ,OIL Immersed COOLING OIL, High cut/Low Cut /Time delay/Over Cut through Micro Controller and Spike Protection Complete job. |
| 27 | P/F of sheet steel Kiosk/Canopy suitable outdoor type to house 10KVA servo stabilizer of capacities fabricated out of 16 SWG M.S sheet having front door with locking arrangements and duly powder coated. |
| 28 | Structural steel work in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat and paint of approved quality all complete.Bench=50x50x6mm Side frame 3x2.5'-0\\"= 7.5.00 rft 3x2.5\\"-0\\" =7.5.00 rft Legs 4x 2'-6\\" = 10.4 rft Total = 25.4 rft or 7.74 Rm @ 4.50Kg/rm = 34.84Kg ---(A) |
| 29 | Supply/Laying/Testing and Commissioning of 2-Core 35 mm sq. armored XLPE Insulated,PVC Al cable Polycab/Havells/Eq. Make. Including Supply/Laying of HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench of standard make as approved.The cable shall include end termination lugs with its crimping /taping. |
| 30 | Supply/Excavation & Laying of GI Pipe (A-Class) of 02 inches dia with ISI Marked for Road cut and refilling of same with cement concrete. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 8 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 8 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 9 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender