Power Government Departments Closing in 7 days TDR #57886671

Tender For Augmentation Of Receiving Station Kunzer From 2X10 Mva To 3X10 Mva Under Ut Capex

Issued by Government Departments · Baramulla, Jammu and Kashmir
Tender Value
1.07 Crore
Estimated cost
Bid Submission
07 Nov 2026
7 days left
EMD
2.15 Lakhs
Bank guarantee accepted
Document Fee
3003
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Baramulla → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Augmentation Of Receiving Station Kunzer From 2X10 Mva To 3X10 Mva Under Ut Capex

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 29-Oct-2026 Extension-I Date 07-Nov-2026

BOQ

Name of Work:- Augmentation of Receiving Station Kunzer from 2x10 MVA to 3x10 MVA under UT Capex
Sl. No. Item Description
1Supply, Installation, Testing and Commissioning of
2Installation, testing and successful commissioning of 10 MVA Power Transformer including loading at ECSD Pampore, handling, Carriage upto site/ Unloading /Dragging /Assembling at site including insurance during transit (Complete Job) to Receiving Station ( Power Transformer to be provided by the Department)
3Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of 33 kV VCB (36 kV, 1250A, 26.2 kA, Outdoor Type of reputed make as per approved drawings/standards
4Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV Isolator with Earthing Blade (36KV,800A,Outdoor,3 poles,25 KA) of reputed make as per approved drawings/standards
5Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV Isolator without Earthing Blade (36KV,800A,Outdoor,3 poles,25 KA) of reputed make as per approved drawings/standards
6Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 KV Current Transformer (33 KV, 1Φ, 2 Ratio 3 Core, Outdoor Type ; 300-150/5-5A) of reputed make including supply and fixing of suitable CT Clamps as per approved drawings/standards
7Supply, Carriage upto site (including Loading/Unloading),Testing of 11kV/ 110 V, Three phase epoxy resin cast Voltage Transformer with rated burden 15VA per phase and accuracy class 0.5 (reputed make)
8Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV Lightening Arrestors (33 kV, 10kA, Station class, ZnO, Polymer) gap less (1 No. per Φ) of reputed make as per approved drawings/standards
9Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV C&R Panel along with O/C, E/F,REF and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port
10Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV 10 kN Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m of reputed make as per approved drawings/standards
11Supply, Carriage upto site (including Loading/Unloading),Testing and Erection of Steel Tubular Pole, 11 Mtr. Long Pole(ST-410 SP-56) with planting depth of 1/6 th of the height of the pole, (11 mtr. Long ) as per approved drawings/standards
12Supply & Laying of Cement bottoming for 11 Mtr ST Pole in 1:2:4 mix as per Standards 0.66 cum / pole including the Loading/Carriage/Unloading of required material.
13Providing & Fixing of Pole Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip.25x3mmas per approved drawings/standards
14Providing & Painting of 11 Mtr ST Poles with one coat of Red Oxide and two coats of aluminium paint as per approved drawings/standards
15Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of G.I Pipe of Dia 150mm, 5.9 mm Thick 3 m long with G.I Base Plate 8 mm Thick as per approved drawings/standards
16Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of GI Channel/Angle/Flat of sizes including clamps as per approved drawings/standards
17Supply,Testing,Loading,Carriage,Unloading and fixing of Galvanised Nuts & Bolts of sizes
18Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make) as per approved drawings/standards
19Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make) as per approved drawings/standards
20Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 4 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make) as per approved drawings/standards
21Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make) as per approved drawings/standards
22Supply & Fixing of Lugs, Ferrules etc.
23Supply, Carriage upto site (including Loading/Unloading),Testing and fixing of 200 mm² ACSR Conductor( Panther) as per approved drawings/standards
24Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fitting as per approved drawings/standards
25Supply, Carriage upto site (including Loading/Unloading) Testing & fixing of Earth wire 7/4.00 mm sq. as per approved drawings/standards
26Supply, Carriage upto site (including Loading/Unloading) Testing & fixing of GI flat for earthing (50x6) mm as per approved drawings/standards
27Supply, Carriage upto site (including Loading/Unloading) Testing & fixing of T Clamps as per approved drawings/standards
28Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 KV Outgoing SCADA Compatible VCB Panel Board (12 kV, 1250A, 25 kA-3 Sec, Indoor) with Numerical O/C, E/F relays confirming to IEC61850, Master Trip Relay, Mimic Diagram, Digital Voltmeter with VSS, Digital Ammeter with ASS, PF Meter, Annunciation Windows with annunciation relays(6-Windows), 3-phase Tri-vector meter -5 Amps DLMS Compliant with RS-485 port ,Double Ratio; Three Core(0.5,5P10,PS) Epoxy Casted CT with CTR :400-200/5-5A,TNC Switch, LR switch, Indication Lamps & other equipments as per approved Technical Specifications, of reputed make including Fixing of Earthing & Feeder Name Plate with Name of feeder written on it by using high intensity reflective Tape. (Reputed Make)
29Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 KV Incomer SCADA Compatible VCB Panel Board (12 kV, 1250A, 25 kA-3 Sec, Indoor) with Numerical O/C, E/F relays confirming to IEC61850, Master Trip Relay, Mimic Diagram, Digital Voltmeter with VSS, Digital Ammeter with ASS, PF Meter, Annunciation Windows with annunciation relays(6-Windows), 3-phase Tri-vector meter -5 Amps DLMS Compliant with RS-485 port ,Double Ratio; Three Core(0.5,5P10,PS) Epoxy Casted CT with CTR :600-300/5-5A,Epoxy Casted PT with PTR :11KV/110 V, TNC Switch, LR switch, Indication Lamps & other equipments as per approved Technical Specifications, of reputed make including Fixing of Earthing & Feeder Name Plate with Name of feeder written on it by using high intensity reflective Tape. (Reputed Make)
30Supply, installation, testing and commissioning of 11 kV Bus Coupler Panel with Adaptor Panel, complete with suitable VCB, numerical protection relay, CTs, operating mechanism, interlocking arrangement, metering and indication, control wiring, busbar extensions, supports, insulators, flexible/solid bus links, shrouding and necessary interconnections for matching with existing 11 kV switchgear, including all accessories, hardware, earthing, testing and commissioning, complete in all respects.
31Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type as per approved drawings/standards
32Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 kV 630 mm² Single Core XLPE Cable armoured, FRLS (Havells/KEI/Polycab or any other reputed make ) as per approved drawings/standards
33Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11kV Indoor Heat Shrinkable Cable Termination Kits suitable for 630 mm² Single Core XLPE Cable (3M/Vitchem or any other reputed brand) as per approved drawings/standards
34Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11kV Outdoor Heat Shrinkable Cable Termination Kits suitable for 630 mm² Single Core XLPE Cable (3M/Vitchem or any other reputed brand) as per approved drawings/standards
35Supply, Carriage upto site (including Loading/Unloading),Testing & laying of HDPE Pipe Outer Dia 160 mm Inner Dia 148 mm for 11kV XLPE Cable from Power Transformer to Control Room including excavation as per approved drawings/standards
36Supply & Laying of Reinforced cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 20 mm nominal size for Transformer Bed foundation (3mx2.5mx1.5m) including Excavation of existing Earth,centering shuttering works, 15mm plastering (1:6),Curing, TMT Bars,Back Filling of Existing earth as per the requirement,Speading of Extra Soil in available space as per the directions of Engineer Incharge & Loading/Carriage/Unloading of required material (The job should be executed strictly as per approved KPDCL Drawings)
37Supply & Laying of Reinforced cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 20 mm nominal size for Equipment Foundation and Gantry Foundation including Excavation of existing Earth,centering shuttering works, 15mm plastering (1:6),Curing, TMT Bars,Back Filling of Existing earth as per the requirement,Speading of Extra Soil in available space as per the directions of Engineer Incharge & Loading/Carriage/Unloading of required material (The job should be executed strictly as per approved KPDCL Drawings)
38Supply, Carriage upto site (including Loading/Unloading), Fabrication, Installation & Testing of Earthing Mat (GI Flat 50mm x8 mm) as per approved drawings/standards (Joints should be welded properly and painting of joints to be carried out by using Red Oxide and Deeco Paint. The job includes the excavation of existing earth to the depth as per the KPDCL standards in vogue and back filling of good earth upto ground level after fixing the earth mat including spreading of extra soil in available space as per the directions of Incharge Engineer
39Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Earthing Electrode ( 3m long 40mm dia GI pipe) including their jointing to earthing mat through GI Strip (50x6)mm by welding/bolting and painting of joints with Red Oxide and Deeco Paint as per approved drawings/standards
40Supply & Laying of Yard concrete in 1:2:4 mix (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 20 mm nominal size ) including excavation of earth as per the requirement, centering shuttering,Spreading of extra soil in available space as per the directions of Incharge Engineer & Loading/Carriage/Unloading of required material.
41Supply, Laying & Spreading of Yard Metal by way of stone aggregate 20 mm nominal size including the Loading/Carriage/Unloading of required material.
42Providing & Construction of 750 m Cable Trench by laying of Reinforced cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 20 mm nominal size including Excavation of existing Earth,Centring shuttering works, Angle Iron and TMT Bars as per the KPDCL standards, 15mm plastering (1:6), fabrication,Back Filling of Existing earth as per the requirement,Speading of Extra Soil in available space as per the directions of Engineer Incharge,Fixing of 8 mm thick chequered plates & Loading/Carriage/Unloading of required material as per the drawings/standards
43Extension of existing Control Room building by dismantling the existing side wall and reconstruction of the extended portion, including foundation, RCC works, masonry, roof slab, plastering, flooring, doors/windows and other allied civil works, complete in all respects as per approved drawings and specifications
44Construction and erection of structural steel truss over an area of 1.5 times the existing plinth area, including fabrication, fixing, welding/bolting, necessary supports and bracing, colour-coated profiled roofing sheets, ridge, flashing, gutters and all allied works, complete in all respects as per approved drawings and specifications.
45Supply, Carriage upto site (including Loading/Unloading) & Fixing of Rubber Mat 1mx2m 19mm thick as per approved drawings/standards
46Supply , installation and testing of Fire Fighting Equipment (3 No. Fire Buckets of 9 ltrs,having round bottom with handle, painted white from inside and post office red colour from outside , bottom is painted black. Filled with sand.
47Supply, and Carriage upto site (including Loading/Unloading) of 33kV level Rubber Gloves as per relevant IS/standards
48Supply, and Carriage upto site (including Loading/Unloading) of 11kV level Rubber Gloves as per relevant IS/standards
49Supply, and Carriage upto site (including Loading/Unloading) of Safety Shoes (Ankle Boot) as per relevant IS/standards
50Supply, and Carriage upto site (including Loading/Unloading) of Earthing Discharge rod 5 mtr long with 25 sq mm cable 12 mtr as per relevant IS/standards
51Supply, Testing and Carriage upto site (including Loading/Unloading) of Aluminium Ladder 2x20' long, 3 mm thick extendable with rope and pully arrangement as per relevant IS/standards
52Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of CCTV Complete(LED 32\\" with 06 No.AHD Cameras) of reputed make.
53Supply, Testing and Carriage upto site (including Loading/Unloading) of HV Detectors all voltages along with attached fiber rod as per relevant IS/standards
54Dismantling of existing outdated 11 kV VCB Panels, including careful removal, handling, loading, transportation/carriage up to Divisional Stores, unloading and stacking at Divisional Stores, complete in all respects as directed by the Engineer-in-Charge
55Spares/Contengencies/T&P Items
56Hiring of Vehicle (Scorpio/Bolero/Innova/Tavera or equivalent) to be used by the Engineer Incharge for supervision of the project including Fuel/Toll Tax/ Driver/ any other maintenace charges of the vehicle. The max. Kms to be driven per day is 120 Km. In case the vehicle is utilized less than 120 km on any given day, the payment shall be subject to deduction on account of actual fuel savings. Such deduction shall be worked out proportionately based on the approved mileage (km per litre) of the vehicle and the prevailing fuel rate.
57Supply, Carriage upto site (including Loading/Unloading),Testing of 20 A Auxiallary Switch suitable for 11KV VCB reputed make
58Supply, Carriage upto site (including Loading/Unloading),Testing of Limit Switch suitable for 11KV VCB reputed make Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57886671
AUTHORITY Government Departments
TENDER VALUE 1.07 Crore
LAST DATE 07-11-2026
Authority
Authority Name Power Development Department
Work Description Tender for Augmentation Of Receiving Station Kunzer From 2X10 Mva To 3X10 Mva Under Ut Capex
Basic Detail
Tender No STDS/22 of 2026-27
Bidding Type Tender
Location
City Baramulla
State Jammu and Kashmir
Key Dates
Publish Date 29 Oct 2026
Submission Date 07 Nov 2026
Open Date 09 Nov 2026
Finance
Tender Value 1.07 Crore
Tender Fee 3003
EMD 2.15 Lakhs
Exemption Not Available
Document List
BOQ_1107115.xls
c29aa1bd-b21a-4230-94dd-2411025907f7.html
Drawing.pdf
SBD22.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 29, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 07, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 7 days
Nov 07, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 7 days
Nov 09, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 9 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_1107115.xls

html

c29aa1bd-b21a-4230-94dd-2411025907f7.html

pdf

Drawing.pdf

pdf

SBD22.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender