Bids Are invited for Sitc Of Two (2) Nos. Ups Output Distribution Boards And Two (2) Nos. Static Transfer Switches - Part A: Equipment (Supply, Installation, Testing, Commissioning And Five-Year On-Site Warranty), Ups Output Distribution Board (New U
Tender Overview
Project Description
Bids Are invited for Sitc Of Two (2) Nos. Ups Output Distribution Boards And Two (2) Nos. Static Transfer Switches - Part A: Equipment (Supply, Installation, Testing, Commissioning And Five-Year On-Site Warranty), Ups Output Distribution Board (New Ups Db-A And New Ups Db-B): Floor-Standing Psc Panel To Is/Iec 61439-1 And -2, Oem Design-Verified, Form 4B Type 2, Ip42, Icw 50 Ka 1 S, 630 A E-Cu Busbar 3P + 100% N + E. Incomer 400 A 4P Mccb, Lsig, Icu = Ics = 50 Ka, Modbus, In A Compartment Suitable For A 630 A Frame. Eight Outgoing Units All Suitable For 250 A Frame Mccbs, Fitted With 4 X 160 A, 2 X 125 A And 2 X 63 A 4P Mccbs (Icu 36 Ka Or More, In Oem-Verified Cascade). Modular, Extendable. Class 0.5S Mfm On Incomer And Class 1.0 Mfm On Each 160 A Unit, With Provision For Meters On The Other Units. Bms On/Off/Trip Contacts And Modbus To Terminal Block. Type 2 Spd, Space Heater, Internal Light, Labels, Danger Boards. Complete As Per Section 4A, With Factory Inspection, Installation, Testing And Commissioning By The Oem Or Its Authorised Partner. , Static Transfer Switch Sts-1, Not Less Than 200 A, Scr Type To Iec 62310-1 And -2, 415 V 3 Ph 4 W, 4 Pole, Transfer 6 Ms Or Less, Break-Before-Make, Integral Maintenance Bypass, Redundant Controls, Snmp / Modbus, As Per Section 4B. Installed In The Ups Room, Tested And Commissioned By The Oem Or Its Authorised Partner. , Static Transfer Switch Sts-2, Not Less Than 100 A, As Per Item 2 And Section 4B, Installed Near The Data Centre Server Racks. , Mounting Of Sts As Per Section 4C: Grouted Ms Base Channel (Or Matching Cubicle) For Sts-1; Floor-Standing Rack Of At Least 800 Mm Depth With Shelf Or Rails (Or Plinth) For Sts-2. , Part B: Site Works: Relocation Of Existing Ups Panels To The Stores Area In The Old Car Park, As Per Section 6. , Disconnection, Re-Routing, Re-Laying On Existing Trays And Re-Termination Of Existing Power Cables To Suit The New Positions, Including Ir Test Of Every Re-Used Cable; Earthing And Bonding Of The Boards, Sts And Mountings To The Existing Earth Grid (Two Connections Each, With Measurement, As Per Is 3043); And All Lugs, Glands, Sleeves, Ferrules, Fasteners, Hardware And Consumables Needed To Complete The Installation, As Per Section 5. , Part C: Contingency And Miscellaneous: Supply And Laying Of 1.1 Kv Xlpe Armoured Copper Cable, 4C X 95 Sq Mm, To Is 7098 (Part 1), On Existing Tray, With Glands, Lugs And Termination At Both Ends. Provisional Quantity, Only In Case Of Contingency, With The Written Approval Of The Engineer-In-Charge. Paid As Per Actual Measurement. , Any Other Item Required For Satisfactory Completion Of The Work, Covering Contingencies And Miscellaneous Site Related Works Not Specifically Listed In Items 1 To 7, As Per Section 3. Lump Sum.
BOQ
| Sl. No. | Item Title | Item Description |
| 1 | PART A: EQUIPMENT (supply, installation, testing, commissioning and five-year on-site warranty), UPS output distribution board (New UPS DB-A and New UPS DB-B): floor-standing PSC panel to IS/IEC 61439-1 and -2, OEM design-verified, Form 4b Type 2, IP42, Icw 50 kA 1 s, 630 A E-Cu busbar 3P + 100% N + E. Incomer 400 A 4P MCCB, LSIG, Icu = Ics = 50 kA, Modbus, in a compartment suitable for a 630 A frame. Eight outgoing units all suitable for 250 A frame MCCBs, fitted with 4 x 160 A, 2 x 125 A and 2 x 63 A 4P MCCBs (Icu 36 kA or more, in OEM-verified cascade). Modular, extendable. Class 0.5S MFM on incomer and Class 1.0 MFM on each 160 A unit, with provision for meters on the other units. BMS ON/OFF/TRIP contacts and Modbus to terminal block. Type 2 SPD, space heater, internal light, labels, danger boards. Complete as per Section 4A, with factory inspection, installation, testing and commissioning by the OEM or its authorised partner. | PART A: EQUIPMENT (supply, installation, testing, commissioning and five-year on-site warranty), UPS output distribution board (New UPS DB-A and New UPS DB-B): floor-standing PSC panel to IS/IEC 61439-1 and -2, OEM design-verified, Form 4b Type 2, IP42, Icw 50 kA 1 s, 630 A E-Cu busbar 3P + 100% N + E. Incomer 400 A 4P MCCB, LSIG, Icu = Ics = 50 kA, Modbus, in a compartment suitable for a 630 A frame. Eight outgoing units all suitable for 250 A frame MCCBs, fitted with 4 x 160 A, 2 x 125 A and 2 x 63 A 4P MCCBs (Icu 36 kA or more, in OEM-verified cascade). Modular, extendable. Class 0.5S MFM on incomer and Class 1.0 MFM on each 160 A unit, with provision for meters on the other units. BMS ON/OFF/TRIP contacts and Modbus to terminal block. Type 2 SPD, space heater, internal light, labels, danger boards. Complete as per Section 4A, with factory inspection, installation, testing and commissioning by the OEM or its authorised partner. |
| 2 | Static transfer switch STS-1, not less than 200 A, SCR type to IEC 62310-1 and -2, 415 V 3 ph 4 W, 4 pole, transfer 6 ms or less, break-before-make, integral maintenance bypass, redundant controls, SNMP / Modbus, as per Section 4B. Installed in the UPS room, tested and commissioned by the OEM or its authorised partner. | Static transfer switch STS-1, not less than 200 A, SCR type to IEC 62310-1 and -2, 415 V 3 ph 4 W, 4 pole, transfer 6 ms or less, break-before-make, integral maintenance bypass, redundant controls, SNMP / Modbus, as per Section 4B. Installed in the UPS room, tested and commissioned by the OEM or its authorised partner. |
| 3 | Static transfer switch STS-2, not less than 100 A, as per Item 2 and Section 4B, installed near the data centre server racks. | Static transfer switch STS-2, not less than 100 A, as per Item 2 and Section 4B, installed near the data centre server racks. |
| 4 | Mounting of STS as per Section 4C: grouted MS base channel (or matching cubicle) for STS-1; floor-standing rack of at least 800 mm depth with shelf or rails (or plinth) for STS-2. | Mounting of STS as per Section 4C: grouted MS base channel (or matching cubicle) for STS-1; floor-standing rack of at least 800 mm depth with shelf or rails (or plinth) for STS-2. |
| 5 | PART B: SITE WORKS: Relocation of existing UPS panels to the stores area in the old car park, as per Section 6. | PART B: SITE WORKS: Relocation of existing UPS panels to the stores area in the old car park, as per Section 6. |
| 6 | Disconnection, re-routing, re-laying on existing trays and re-termination of existing power cables to suit the new positions, including IR test of every re-used cable; earthing and bonding of the boards, STS and mountings to the existing earth grid (two connections each, with measurement, as per IS 3043); and all lugs, glands, sleeves, ferrules, fasteners, hardware and consumables needed to complete the installation, as per Section 5. | Disconnection, re-routing, re-laying on existing trays and re-termination of existing power cables to suit the new positions, including IR test of every re-used cable; earthing and bonding of the boards, STS and mountings to the existing earth grid (two connections each, with measurement, as per IS 3043); and all lugs, glands, sleeves, ferrules, fasteners, hardware and consumables needed to complete the installation, as per Section 5. |
| 7 | PART C: CONTINGENCY AND MISCELLANEOUS: Supply and laying of 1.1 kV XLPE armoured copper cable, 4C x 95 sq mm, to IS 7098 (Part 1), on existing tray, with glands, lugs and termination at both ends. Provisional quantity, only in case of contingency, with the written approval of the Engineer-in-Charge. Paid as per actual measurement. | PART C: CONTINGENCY AND MISCELLANEOUS: Supply and laying of 1.1 kV XLPE armoured copper cable, 4C x 95 sq mm, to IS 7098 (Part 1), on existing tray, with glands, lugs and termination at both ends. Provisional quantity, only in case of contingency, with the written approval of the Engineer-in-Charge. Paid as per actual measurement. |
| 8 | Any other item required for satisfactory completion of the work, covering contingencies and miscellaneous site related works not specifically listed in Items 1 to 7, as per Section 3. Lump sum. | Any other item required for satisfactory completion of the work, covering contingencies and miscellaneous site related works not specifically listed in Items 1 to 7, as per Section 3. Lump sum. |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 10 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender