Bids Are invited for Sitc Of Led Luminaires, Led Retrofit L S And Occupancy With Control Wiring And Lux Survey - Part A — Sitc Of Led Street Light, Max. 70 W, Min. 8,400 Lm, 5700 K, Ip66, Ik08, With 10 Kv / 5 Ka Spd And Side-Entry Spigot Mounting Wit
Tender Overview
Project Description
Bids Are invited for Sitc Of Led Luminaires, Led Retrofit L S And Occupancy With Control Wiring And Lux Survey - Part A — Sitc Of Led Street Light, Max. 70 W, Min. 8,400 Lm, 5700 K, Ip66, Ik08, With 10 Kv / 5 Ka Spd And Side-Entry Spigot Mounting With Tilt. , Sitc Of Led Street Light, Max. 35 W, Min. 3,850 Lm, 5700 K. Construction, Protection And Mounting As Item 1 , Sitc Of Led Recessed Luminaire 595 X 595 Mm, Max. 30 W, Min. 3,450 Lm, Cri 80+, Ugr 22 Or Lower, Ip20, With Surface Frame Free Where The Ceiling Is Not Modular. , Sitc Of Led Recessed Downlighter, Ip44, Max. 12 W, Min. 1,200 Lm, 5700 K, With Adaptor Ring To Suit The Existing Cut-Out. , Sitc Of Led Recessed Downlighter, Max. 15 W, Min. 1,500 Lm, 5700 K, Cri 80+, Ip20, With Adaptor Ring To Suit The Existing Cut-Out. , Sitc Of Led Spot / Accent Downlighter, Max. 8 W, Min. 600 Lm, Beam 24 Deg, Cri 80+, Tilt And Rotate, Ip20. , Sitc Of Led Flood Light, Max. 55 W, Min. 5,500 Lm, 5700 K, Ip66, Ik08, 10 Kv / 5 Ka Spd, Cradle With Graduated Tilt. , Sitc Of Led Linear Batten 2 Ft, Max. 12 W, Min. 1,200 Lm, 5700 K, Aluminium Housing, Ip20. , Sitc Of Led Linear Batten 4 Ft, Max. 18 W, Min. 1,980 Lm, 5700 K. Construction As Item 8. , Sitc Of Led Linear Batten 4 Ft, Max. 30 W, Min. 3,300 Lm, 5700 K. Construction As Item 8. , Sitc Of Led Surface Mounted Luminaire, Max. 18 W, Min. 1,620 Lm, 5700 K, Cri 80+, Die-Cast Aluminium, Ip40. , Sitc Of Led Flood Light, Max. 150 W, Min. 15,000 Lm, 5700 K, Ip65 Or Better, 10 Kv / 5 Ka Spd, Cradle Mount For High Mast Carriage. , Sitc Of Led Mirror Light 1 Ft, Ip44, Max. 5 W, Min. 450 Lm, Complete With Clips And Screws. , Sitc Of Led Recessed Luminaire, Ip44, Max. 47 W, Min. 4,700 Lm, 5700 K, With Trims To Suit The Existing Cut-Out. , Sitc Of Ed Recessed Downlighter With Dali-2 Driver, Max. 22 W, Min. 2,200 Lm, 4000 K, Cri 80+, Ip20. , Sitc Of Led Post-Top Lantern, Architectural Design, On Existing Pole, Max. 40 W, Min. 3,000 Lm, 5700 K, Ip65, Incois-Chosen Colour, 10 Kv / 5 Ka Spd. , Sitc Of Led Bollard, Architectural Design Matching Item 16, On Existing Base, Max. 10 W, Min. 600 Lm, 5700 K, Ip65, With Incois Name / Logo Etched. , Part B -Sitc Of Led T8 Tube 4 Ft, G13, Max. 18 W, Min. 1,800 Lm, 6500 K, Direct Mains, With Ballast Removal, Bypass Wiring And Caution Label. , Sitc Of Led Retrofit L , 4-Pin, For Existing 2 X 2 Thorn Fittings, Max. 18 W, Min. 1,600 Lm, Cap To Match The Existing L . , Sitc Of Led Retrofit L , 2-Pin Pl-C (G24d / G23), Max. 9 W, Min. 800 Lm, For Existing Downlighters. , Sitc Of Led Retrofit L , 4-Pin Pl-L (2G11), Max. 10 W, Min. 800 Lm, For Existing Fittings. , Sitc Of Led L , E27 Cap, Max. 27 W, Min. 2,700 Lm, 6500 K, For Existing Outdoor Dome Fittings. , Sitc Of Led L , B22 Or E27 Cap To Suit The Holder, Max. 9 W, Min. 900 Lm, 6500 K. , Part C- Sitc Of Occupancy Sensor, Pir, Ceiling Mounted, 360 Deg, Ip20, With Daylight Sensor, Adjustable Time Delay And Light Off After Power Failure; Wide-Area Lens In Large Rooms And Halls. Cable Paid Separately. , Sitc Of Occupancy Sensor, Microwave, Ip20 Indoors And Ip44 (Or In Protective Housing) In Toilets, Parking And Plant Rooms; Corridor Range 20 M; Manual Override Switch In Critical Rooms. Cable Paid Separately. , Part D -Sitc Of 1.5 Sq Mm Single Core Frls Copper Cable, Isi Marked, 1100 V, To Is 694. , Sitc Of 3 Core X 1.5 Sq Mm Frls Copper Cable, Isi Marked, 1100 V, To Is 694 / Is 1554 (Part 1). , Laying, Drawing, Ferruling And Termination Of 1.5 Sq Mm Single Core Frls Cable In Existing Conduit / Raceway, With Testing. , Laying, Drawing, Ferruling And Termination Of 3 Core X 1.5 Sq Mm Frls Cable In Existing Conduit / Raceway, With Testing. , Sitc Of Of 20 Mm Isi Pvc Conduit Or Pvc Casing-Capping With Bends, Boxes And Saddles, Where No Existing Conduit Or Raceway Is Available. , Part E-Removal Of Old Fittings At Every Replacement Position (Items 1 To 17), With Access Equipment, And Handover To Incois Stores Against Receipt. Lump Sum. , Any Other Item Required For Satisfactory Completion Of The Work, Covering Contingencies And Miscellaneous Site Related Works Not Specifically Listed In Items 1 To 31, As Per Clause 3.1. Lump Sum (If Any, Please Mention).
BOQ
| Sl. No. | Item Title | Item Description |
| 1 | PART A — SITC of LED street light, max. 70 W, min. 8,400 lm, 5700 K, IP66, IK08, with 10 kV / 5 kA SPD and side-entry spigot mounting with tilt. | PART A — SITC of LED street light, max. 70 W, min. 8,400 lm, 5700 K, IP66, IK08, with 10 kV / 5 kA SPD and side-entry spigot mounting with tilt. |
| 2 | SITC of LED street light, max. 35 W, min. 3,850 lm, 5700 K. Construction, protection and mounting as Item 1 | SITC of LED street light, max. 35 W, min. 3,850 lm, 5700 K. Construction, protection and mounting as Item 1 |
| 3 | SITC of LED recessed luminaire 595 x 595 mm, max. 30 W, min. 3,450 lm, CRI 80+, UGR 22 or lower, IP20, with surface frame free where the ceiling is not modular. | SITC of LED recessed luminaire 595 x 595 mm, max. 30 W, min. 3,450 lm, CRI 80+, UGR 22 or lower, IP20, with surface frame free where the ceiling is not modular. |
| 4 | SITC of LED recessed downlighter, IP44, max. 12 W, min. 1,200 lm, 5700 K, with adaptor ring to suit the existing cut-out. | SITC of LED recessed downlighter, IP44, max. 12 W, min. 1,200 lm, 5700 K, with adaptor ring to suit the existing cut-out. |
| 5 | SITC of LED recessed downlighter, max. 15 W, min. 1,500 lm, 5700 K, CRI 80+, IP20, with adaptor ring to suit the existing cut-out. | SITC of LED recessed downlighter, max. 15 W, min. 1,500 lm, 5700 K, CRI 80+, IP20, with adaptor ring to suit the existing cut-out. |
| 6 | SITC of LED spot / accent downlighter, max. 8 W, min. 600 lm, beam 24 deg, CRI 80+, tilt and rotate, IP20. | SITC of LED spot / accent downlighter, max. 8 W, min. 600 lm, beam 24 deg, CRI 80+, tilt and rotate, IP20. |
| 7 | SITC of LED flood light, max. 55 W, min. 5,500 lm, 5700 K, IP66, IK08, 10 kV / 5 kA SPD, cradle with graduated tilt. | SITC of LED flood light, max. 55 W, min. 5,500 lm, 5700 K, IP66, IK08, 10 kV / 5 kA SPD, cradle with graduated tilt. |
| 8 | SITC of LED linear batten 2 ft, max. 12 W, min. 1,200 lm, 5700 K, aluminium housing, IP20. | SITC of LED linear batten 2 ft, max. 12 W, min. 1,200 lm, 5700 K, aluminium housing, IP20. |
| 9 | SITC of LED linear batten 4 ft, max. 18 W, min. 1,980 lm, 5700 K. Construction as Item 8. | SITC of LED linear batten 4 ft, max. 18 W, min. 1,980 lm, 5700 K. Construction as Item 8. |
| 10 | SITC of LED linear batten 4 ft, max. 30 W, min. 3,300 lm, 5700 K. Construction as Item 8. | SITC of LED linear batten 4 ft, max. 30 W, min. 3,300 lm, 5700 K. Construction as Item 8. |
| 11 | SITC of LED surface mounted luminaire, max. 18 W, min. 1,620 lm, 5700 K, CRI 80+, die-cast aluminium, IP40. | SITC of LED surface mounted luminaire, max. 18 W, min. 1,620 lm, 5700 K, CRI 80+, die-cast aluminium, IP40. |
| 12 | SITC of LED flood light, max. 150 W, min. 15,000 lm, 5700 K, IP65 or better, 10 kV / 5 kA SPD, cradle mount for high mast carriage. | SITC of LED flood light, max. 150 W, min. 15,000 lm, 5700 K, IP65 or better, 10 kV / 5 kA SPD, cradle mount for high mast carriage. |
| 13 | SITC of LED mirror light 1 ft, IP44, max. 5 W, min. 450 lm, complete with clips and screws. | SITC of LED mirror light 1 ft, IP44, max. 5 W, min. 450 lm, complete with clips and screws. |
| 14 | SITC of LED recessed luminaire, IP44, max. 47 W, min. 4,700 lm, 5700 K, with trims to suit the existing cut-out. | SITC of LED recessed luminaire, IP44, max. 47 W, min. 4,700 lm, 5700 K, with trims to suit the existing cut-out. |
| 15 | SITC of ED recessed downlighter with DALI-2 driver, max. 22 W, min. 2,200 lm, 4000 K, CRI 80+, IP20. | SITC of ED recessed downlighter with DALI-2 driver, max. 22 W, min. 2,200 lm, 4000 K, CRI 80+, IP20. |
| 16 | SITC of LED post-top lantern, architectural design, on existing pole, max. 40 W, min. 3,000 lm, 5700 K, IP65, INCOIS-chosen colour, 10 kV / 5 kA SPD. | SITC of LED post-top lantern, architectural design, on existing pole, max. 40 W, min. 3,000 lm, 5700 K, IP65, INCOIS-chosen colour, 10 kV / 5 kA SPD. |
| 17 | SITC of LED bollard, architectural design matching Item 16, on existing base, max. 10 W, min. 600 lm, 5700 K, IP65, with INCOIS name / logo etched. | SITC of LED bollard, architectural design matching Item 16, on existing base, max. 10 W, min. 600 lm, 5700 K, IP65, with INCOIS name / logo etched. |
| 18 | PART B -SITC of LED T8 tube 4 ft, G13, max. 18 W, min. 1,800 lm, 6500 K, direct mains, with ballast removal, bypass wiring and caution label. | PART B -SITC of LED T8 tube 4 ft, G13, max. 18 W, min. 1,800 lm, 6500 K, direct mains, with ballast removal, bypass wiring and caution label. |
| 19 | SITC of LED retrofit lamp, 4-pin, for existing 2' x 2' Thorn fittings, max. 18 W, min. 1,600 lm, cap to match the existing lamp. | SITC of LED retrofit lamp, 4-pin, for existing 2' x 2' Thorn fittings, max. 18 W, min. 1,600 lm, cap to match the existing lamp. |
| 20 | SITC of LED retrofit lamp, 2-pin PL-C (G24d / G23), max. 9 W, min. 800 lm, for existing downlighters. | SITC of LED retrofit lamp, 2-pin PL-C (G24d / G23), max. 9 W, min. 800 lm, for existing downlighters. |
| 21 | SITC of LED retrofit lamp, 4-pin PL-L (2G11), max. 10 W, min. 800 lm, for existing fittings. | SITC of LED retrofit lamp, 4-pin PL-L (2G11), max. 10 W, min. 800 lm, for existing fittings. |
| 22 | SITC of LED lamp, E27 cap, max. 27 W, min. 2,700 lm, 6500 K, for existing outdoor dome fittings. | SITC of LED lamp, E27 cap, max. 27 W, min. 2,700 lm, 6500 K, for existing outdoor dome fittings. |
| 23 | SITC of LED lamp, B22 or E27 cap to suit the holder, max. 9 W, min. 900 lm, 6500 K. | SITC of LED lamp, B22 or E27 cap to suit the holder, max. 9 W, min. 900 lm, 6500 K. |
| 24 | PART C- SITC of Occupancy sensor, PIR, ceiling mounted, 360 deg, IP20, with daylight sensor, adjustable time delay and light OFF after power failure; wide-area lens in large rooms and halls. Cable paid separately. | PART C- SITC of Occupancy sensor, PIR, ceiling mounted, 360 deg, IP20, with daylight sensor, adjustable time delay and light OFF after power failure; wide-area lens in large rooms and halls. Cable paid separately. |
| 25 | SITC of Occupancy sensor, microwave, IP20 indoors and IP44 (or in protective housing) in toilets, parking and plant rooms; corridor range 20 m; manual override switch in critical rooms. Cable paid separately. | SITC of Occupancy sensor, microwave, IP20 indoors and IP44 (or in protective housing) in toilets, parking and plant rooms; corridor range 20 m; manual override switch in critical rooms. Cable paid separately. |
| 26 | PART D -SITC of 1.5 sq mm single core FRLS copper cable, ISI marked, 1100 V, to IS 694. | PART D -SITC of 1.5 sq mm single core FRLS copper cable, ISI marked, 1100 V, to IS 694. |
| 27 | SITC of 3 core x 1.5 sq mm FRLS copper cable, ISI marked, 1100 V, to IS 694 / IS 1554 (Part 1). | SITC of 3 core x 1.5 sq mm FRLS copper cable, ISI marked, 1100 V, to IS 694 / IS 1554 (Part 1). |
| 28 | Laying, drawing, ferruling and termination of 1.5 sq mm single core FRLS cable in existing conduit / raceway, with testing. | Laying, drawing, ferruling and termination of 1.5 sq mm single core FRLS cable in existing conduit / raceway, with testing. |
| 29 | Laying, drawing, ferruling and termination of 3 core x 1.5 sq mm FRLS cable in existing conduit / raceway, with testing. | Laying, drawing, ferruling and termination of 3 core x 1.5 sq mm FRLS cable in existing conduit / raceway, with testing. |
| 30 | SITC of of 20 mm ISI PVC conduit or PVC casing-capping with bends, boxes and saddles, where no existing conduit or raceway is available. | SITC of of 20 mm ISI PVC conduit or PVC casing-capping with bends, boxes and saddles, where no existing conduit or raceway is available. |
| 31 | PART E-Removal of old fittings at every replacement position (Items 1 to 17), with access equipment, and handover to INCOIS Stores against receipt. Lump sum. | PART E-Removal of old fittings at every replacement position (Items 1 to 17), with access equipment, and handover to INCOIS Stores against receipt. Lump sum. |
| 32 | Any other item required for satisfactory completion of the work, covering contingencies and miscellaneous site related works not specifically listed in Items 1 to 31, as per Clause 3.1. Lump sum (if any, please mention). | Any other item required for satisfactory completion of the work, covering contingencies and miscellaneous site related works not specifically listed in Items 1 to 31, as per Clause 3.1. Lump sum (if any, please mention). |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 10 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender