Tender For Repair/Maintenance Of E/M Internal/External Services, Dg Set And Misc Works At Cda Complex Patna Under Ge Danapur
Tender Value
37.50 Lakhs
Estimated cost
Bid Submission
26 Oct 2026
12 days left
EMD
75000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Patna → Bihar
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair/Maintenance Of E/M Internal/External Services, Dg Set And Misc Works At Cda Complex Patna Under Ge Danapur
BOQ
| Sl. No. | Item Description |
| 1 | Taking down carefully copper/aluminium point wiring (Light,fan,socket or power) complete fitting such as switches, ceiling rose, regulator, sockets etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of wall, floors, etc. all as specified and directed. |
| 2 | M&L light fan point controlled by one switch with PVC insulated, unsheathed , multi stranded, single core copper conductor FRLS ( Flame Retardant Low Smoke) cable 1.50 Sqmm suitable for fixing in concealed PVC conduit of size not less than 20 mm dia with metal flush boxes including white cover plate with frame of required module.Metal flush box should not less than 2 mm thick duly painted inside and outside with two coats of synthetic enamel paint over one coat of red oxide primer of required module suitable for housing modular switches, socket, fan regulator etc. PVC insulated, unsheathed, multi stranded, single core copper conductor FRLS cable 1.50 Sqmm used as earth wire to commen earth and connected to common dolly drawn in same conduit all as specified. |
| 3 | All as per item No 2 above but one 3/5 pin socket out let 5 amp on same board with other switches. |
| 4 | All as per item No 2 above but socket out let 5 amp on independent board. |
| 5 | All as per item No 2 above but One bell/ buzzer point controlled by one push button on the same board with other switches or independent with cables 1.5 sq.mm size |
| 6 | All as per item No 2 above but one light point controlled by two two way switches. |
| 7 | All as per item No 2 above but socket out let 3/6 pin 15 Amp with 2.5 sq mm size copper conductor for power point on indipendent board. |
| 8 | Supply & Fixing switch modular single pole, one way 6 Amp ,01 module. |
| 9 | Supply & Fixing switch modular bell push 6 Amp ,01 module. |
| 10 | Supply & Fixing switch modular , two way 6 Amp ,01 module. |
| 11 | Supply & Fixing switch modular single pole, one way 16 Amp ,01 module. |
| 12 | Supply & Fixing modular socket 6 Amp-2/3 pin combined ,2 module. |
| 13 | Supply & Fixing modular socket 6/16 Amp-2/3 pin combined ,2 module. |
| 14 | S&F Modular electronic type step fan regulator, 120 W-2 module. |
| 15 | M&L light fan point controlled by one switch with PVC insulated, unsheathed , multi stranded , single core copper conductor cable 1.50 Sqmm suitable for fixing in concealed conduit 20 mm dia with sunken pressed steel terminal boxes 2 mm thick of required size , duly painted inside and outside with two coats of synthetic enamel paint over one coat of red oxide primer including 3 mm thick plastic laminated sheet cover housing switches ,socket, fan regulator etc. PVC insulated, unsheathed, multi stranded, single core copper conductor cable 1.50 Sqmm used as common earth wire and connected to common earth dolly & drawn in same conduit all as specified. |
| 16 | All as per item No 15 above but one 3/5 pin socket out let 5 amp on same board with other switches. |
| 17 | All as per item No 15 above but socket 5 amp on independent board. |
| 18 | All as per item No 15 above but One bell/ buzzer point controlled by one push button on the same board with other switches or independent with cables 1.5 sqmm size |
| 19 | All as per item No 15 above but one light point controlled by two two way switches. |
| 20 | All as per item No 15 above but socket out let 3/6 pin 15 Amp with 2.5 sq mm size copper conductor for power point on indipendent board. |
| 21 | Supply & Fixing switch piano flush type single pole one way 5 Amp. |
| 22 | Supply & Fixing bell push flush type switch. |
| 23 | Supply & Fixing switch piano flush type two way 5 Amp. |
| 24 | Supply & Fixing socket 3/5 pin 5 Amp flush type. |
| 25 | Supply & Fixing switch socket combination 3/6 pin 5/15 Amp universal type. |
| 26 | Supply & Fixing electronic stepped type fan regulator. |
| 27 | Supply & Fixing call bell ding dong type 230 Volts AC supply. |
| 28 | Supply & Fixing ceiling rose surface backlite 65X20 mm two to three terminals complete. |
| 29 | Supply & Fixing lamp holder PVC / Ploycarbonate type. |
| 30 | Taking down carefully copper/aluminium power/sub main wiring of any size / type all as specified and directed. |
| 31 | M & L for power/sub main wiring with two runs of single core 4 sqmm size and one run of single core 4.0 sqmm (green colour as earth continuty conductor ) PVC insulated unsheathed multi stranded copper conductor cables drawn through and including rigid PVC concealed conduit complete all as specified and directed.( Note - two runs of 4 sq mm single core copper conductor and one runs of 4.0 Sq mm copper conductor & PVC conduit shall be measured as one unit length.) |
| 32 | M & L for power/sub main wiring with two runs of single core 6 sqmm size and one run of single core 6.0 sqmm (green colour as earth continuty conductor ) PVC insulated unsheathed multi stranded copper conductor cables drawn through and including rigid PVC concealed conduit complete all as specified and directed.( Note - two runs of 6 sq mm single core copper conductor and one runs of 6.0 Sq mm copper conductor and PVC conduit shall be measured as one unit length.) |
| 33 | M & L for power/sub main wiring with two runs of single core 10 sqmm size and one run of single core 10.0 sqmm (green colour as earth continuty conductor ) PVC insulated unsheathed multi stranded copper conductor cables drawn through and including rigid PVC concealed conduit complete all as specified and directed.( Note - two runs of 10 sq mm single core copper conductor and one runs of 10.0 Sq mm copper conductor & PVC conduit shall be measured as one unit length.) |
| 34 | M & L for power/sub main wiring with four runs of single core 10 sqmm size and one run of single core 10.0 sqmm (green colour as earth continuty conductor ) PVC insulated unsheathed multi stranded copper conductor cables drawn through and including rigid PVC concealed conduit complete all as specified and directed.( Note - Four runs of 10 sq mm single core copper conductor and one runs of 10.0 Sq mm copper conductor & PVC conduit shall be measured as one unit length.) |
| 35 | Taking down existing light fitting of any type,make & capacity . |
| 36 | Supply and fixing energy saving LED lights fitting 1x 20W, 220V, AC, natural white / warm whitedecorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose, including its all acessories complete all as specified and directed. |
| 37 | Supply and fixing engineering plastic batten with white acrylic cover LED light ( integrated LED channel) natural white / warm white,energy saving complete with its all acessories internally perwired and including connecting up with twin core twistered flexible copper conductor cable of suitable size complete all as specified and directed of 09 W . |
| 38 | Supply and fixing recess/surface mounting LED luminaire of size 600 mmx 600 mm white 35/36 watt, 230 volts with driver connector block etc complete with all accessories prewired and including connecting up with twin core twisted flexible copper conductor of suitable size complete all as specified and directed. |
| 39 | Supply & Fixing recess/surface mounting sleek round / Square LED downlight luminaire white 15 Watt , 230 Volts, complete with driver, connector block ,etc, complete with all accessories pre wired and including connecting up with twin core twisted flexible copper conductor of suitable size. |
| 40 | Supply & Fixing integral LED bulkhead luminaire, 10 W, 230 Volts, IP 65 protection decorative surface mounted , complete with all accessories pre wired and including connecting up with twin core twisted flexible copper conductor of suitable size. |
| 41 | Supply & Fixing in replacement Bldg security LED light fittings with pressure dia cast aluminium of 35 watts and including and connceting up ceiling rose and fittings with 3 core, PVC insulated multistranded copper conductor cable of 1.5 Sqmm complete all as specified and directed |
| 42 | Supply & Fixing in replacement LED lamp 12 Watt. |
| 43 | Supply & Fixing in replacement LED lamp 9 Watt . |
| 44 | Supply and fixing rechargeable LED bulb Cool Day light 9/10 watts having Luminous Efficacy range lies between ( ≥100 and <105 ) lm/W,CRI 80 as per BEE guidelines Long Life 25000 hours , colour temp 6500 K , frosted glass min back up time 4 Hrs after charge, In-built surge protection of 3 KVA 220V,AC complete all as specified and as directed. |
| 45 | Taking down old U/S MCCB/MCB DB of any type, make complete all as specified and directed. |
| 46 | Supply & Fixing sheet metal enclouser MCCB DB IP 43 double door bus bar neutral link earth bar and din rail TPN 4 way complete all as specified and directed. |
| 47 | Supply & Fixing sheet metal enclouser MCB DB double door bus bar neutral link,earth bar and din rail SPN 12 way. |
| 48 | Supply & Fixing sheet metal enclouser MCB DB double door bus bar neutral link,earth bar and din rail SPN 8 way. |
| 49 | Supply & Fixing sheet metal enclouser MCB DB double door bus bar neutral link,earth bar and din rail TPN 4 way . |
| 50 | Taking down old U/S MCCB / MCB of any type,make complete all as specified and directed. |
| 51 | S & F in replacement of MCCB 4 pole 415 Volt, 50 Hz,100 Amps with breaking capacity 16 KA fixed type all as specified and directed. |
| 52 | S & F in replacement of MCCB 4 pole 415 Volt, 50 Hz,125 Amps with breaking capacity 16 KA fixed type all as specified and directed. |
| 53 | Supply & Fixing MCB TPN 16 to 32 Amps 415 volts, 10KA \\"C\\" curve. |
| 54 | Supply & Fixing MCB TPN 40 to 63 Amps 415 volts, 10KA \\"C\\" curve. |
| 55 | Supply & Fixing MCB SPN 32 Amps 240 volts, 10 KA, \\"C\\" curve. |
| 56 | Supply & Fixing MCB SPN 40 to 63 Amps 240 volts, 10 KA, \\"C\\" curve. |
| 57 | Supply & Fixing MCB SP 5 to 32 Amps 240 volts, 10 KA, \\"C\\" curve. |
| 58 | Supply & fixing earth plug enclosure (plug and socket ) including MCB, SP 20 Amps modular type complete all as specified and directed . |
| 59 | Taking down ceiling fan of any sweep from its position opening the fan for inspection of worn out/ unserviceable parts. Repairing with replacement of unserviceable parts if required cleaning of blade and body properly oiling, greasing of bearing/ bush all as specified and fixing the fan in position all as specified and directed Note :- Parts to be replaced will be measured and paid separetly. |
| 60 | Transporting of unserviceable ceiling fans of 1200 mm sweep to work shop and carrying out rewinding to the starter by using superior quality enameled copper conductor of matching size in weight gauge, application best quality of supper enameled insulation material tapping varnishing drying and re-fitment with testing complete. |
| 61 | Same as item No 60 but for ceiling fan of 1400 mm sweep 230 volt AC 50 Hz. |
| 62 | Same as item No 60 but for heavy duty exhaust fan 300mm sweep 230 volt AC 50 Hz. |
| 63 | Same as item No 60 but for pedestal fan 400mm sweep 230 volt AC 50 Hz. |
| 64 | Same as item No 60 but for wall mounting fan 400mm sweep 230 volt AC 50 Hz. |
| 65 | Supply & fix in replacment fans ceiling having copper winding motor ,complete with remote and other accessories 230 V,50 Hz AC ,1200 mm sweep. With service value 6 .00 BEE 5 star rated with BLDC motor (Brushless direct current motor) complete all as specified and directed. |
| 66 | Same as item No 65 but for pedestal fan metal body 500mm sweep 230 volt AC 50 Hz. |
| 67 | Same as item No 65 but for wall mounting fan metal body 400mm sweep 230 volt AC 50 Hz. |
| 68 | Supply & fix in replacement exhaust fans heavy duty complete steel body and copper winding fan motor,1400 rpm ,AC single phase 230/ 240 V, 50 Hz AC, of size 300 mm sweep with louver including testing and commissioning complete all as specified and directed. |
| 69 | Supply and fixing in replacement capacitor 2.5/3.15 mfd. |
| 70 | Supply and fixing in replacement fan blade suiatable for 400mm sweep pedestal fan/ Wall mounting fan. |
| 71 | Supply and fixing in replacement fan blade suiatable for 300 mm sweep exhaust fan. |
| 72 | Supply and fixing in replacement ball bearing of size 6201 / 6202 / 6203 NBC suiatable for ceiling fan / exhaust fan. |
| 73 | Supply and fixing in replacement rubber bush (reel type) suiatable for 1200mm/1400mm sweep ceiling fan. |
| 74 | Repair to window / Split type Air conditioner by replacement of unserviceable sealed unit i.e.compressor (rotery or hermetic), cleaning of system properly with CTC and charging the refrigerant recommended by manufacturer of AC including commissioning and testing complete all as specified and directed at site for 1.5 TR Window/Split type AC. Note -Cost of refrigerant will be measuered and paid separately. |
| 75 | S & F in repair condenser coil as per sample for 1.5 Ton A.C. Note : Charging of refrigerant including cost of refrigerant will be measured and paid separately under respective item. |
| 76 | S & F in replacement relay suitable for split / window type AC upto capacity of 1.5TR. |
| 77 | S & F in replacement over load protector suitable for split type AC of 1.5 Ton. |
| 78 | S & F in replacement for air conditioners, capacitor 36 / 45 / 50 +6 mfd +/- 5% ,440 V AC . |
| 79 | S & F in replacement thermostatic switch suitable for 1.5 AC make Renutrol. |
| 80 | S & F in repalcement fan motor with blade as per size and sample suitable for FCU unit of Split type AC of capacity 1.5 Ton of make LG/Voltas/Blue Star complete all as specified and directed. |
| 81 | S & F in repalcement blower fan motor for indoor unit of Split type AC of capacity 1.5 Ton of make LG/Voltas/Blue Star complete all as specified and directed. |
| 82 | S & F in repalcement fan motor with blade for Window type AC of capacity 1.5 Ton of make LG/Voltas complete all as specified and directed. |
| 83 | M & L for gas charging in split type AC unit 1.5 TR capacity using refrigerant as per standard practice after flushing, vacuuming including detecting leakage, rectification leakage, commissioning and testing complete all as specified and directed. |
| 84 | Same as item No 83 above but for window type AC unit of capacity 1.5 TR. |
| 85 | S & F in repair power PCB as per sample suitable for 1.5 TR Split type AC, making connection & testing complete all as specified. |
| 86 | S & F in repair copper connection pipe with union at both ends and with insulation, between FCU unit and indoor unit of length twelve feet for 1.5/2 TR Split type AC, making connection & testing complete all as specified. |
| 87 | S & F in repair drain hose pipe suitable for 1.5 / 2 TR split type AC. |
| 88 | S & F in repair air filter as per existing size suitable indoor unit of 1.5 TR split type AC. |
| 89 | M & L for complete servicing of Air conditioner window/split type including cleaning of colling coil and condenser by caustic soda solution including removal of dust by using blower/brush to external fins and from beneath assets, cleaning of base tray properly including oil to fan & condenser motor, tightening of all electrical connections with proper alignment including fitments in their locations and repairs of suction & discharge tubes complete in all respects. (Note :-Filling of refrigerant if required or parts to be replaced will be measured and paid separately under respective items) |
| 90 | Repair of voltage stabilizer of capacity 5 KVA/4KVA by carying out rewinding of main transformer, replacement of volt meter, relay, timer and IC circuit as required and making functional and testing complete all as specified and directed . |
| 91 | Supply and fixing in replacement heating element of 1.5 KW /2.0 any type, as per sample ISI marked. |
| 92 | Supply & replace complete siphon assembly as per existing sample including rubber washer and nuts & bolts suitable for water heater of capacity 25 Ltrs of any make. |
| 93 | S & F in replacement SS inner tank as per size and sample for geyser of capacity 25 ltrs. |
| 94 | Supply and fixing in replacement thermo state switch suitable for above geyser ISI marked. |
| 95 | Supply and fixing in replacement PVC pipe of 450 mm long best quality, heavy duty for geyser of 15 mm dia with brass connecting nuts/couples. |
| 96 | S & F in replacement stop cocks brass CP 15 mm dia suitable for above geyser ISI Marked. |
| 97 | Supply and fixing in replacement PVC insulated copper conductor cable 3 core 6 Sq mm 660/1100 volts grade make Kalinga/Finolex/Rallison. |
| 98 | Supply and fixing in replacement of plug top 3 pin 15 Amps. |
| 99 | Supply and fixing in replacement indicator lamps red and green colour 230 volts 50 Hz AC supply. |
| 100 | Supply and fixing in replacement safety valve to blow of at high rated temperature having latest ISI marked. |
| 101 | Supply and fixing in replacement glass wool around the geyser. |
| 102 | Taking down the existing defective LT UG cable from trenches / pipes / pole for fault finding / replacement, all as specified and directed of any size between 10 Sqmm to 50 Sqmm 3.5 core/4 Core. Note-Excavation and earth work will be measured and paid seperately under relevant items. |
| 103 | All as per item No. 102 above but size 120 Sqmm 3.5 core to 240 Sq mm 3.5 core. |
| 104 | Supply, laying, jointing and testing XLPE insulated extruded PVC outer sheath and inner sheath galvanized steel armoured cable with aluminium conductor suitable for rated voltage of 1100 Volts grade conforming to IS 7089 (Pt I of 1988) laid in tranches/ pipe/duct/pole complete all as specified and directed of size 10 Sqmm 4 core. |
| 105 | Same as item No 104 above but size 25 sqmm 3.5 core. |
| 106 | Same as item No 104 above but size 50 sqmm 3.5 core. |
| 107 | Same as item No 104 above but size 120 Sqmm 3.5 core. |
| 108 | Same as item No 104 above but size 240 Sqmm 3.5 core. |
| 109 | S & F in replacement of MCCB 4 pole 415 Volt, 50 Hz, 400 Amps with breaking capacity 36 KA adjustable, theremal magnetic release type all as specified and directed. |
| 110 | S & F in replacement of MCCB 4 pole 415 Volt, 50 Hz, 250 Amps with breaking capacity 36 KA adjustable, theremal magnetic release type all as specified and directed. |
| 111 | S & F in replacement of MCCB 4 pole 415 Volt, 50 Hz, 200 Amps with breaking capacity 36 KA adjustable, theremal magnetic release type all as specified and directed. |
| 112 | S & F in replacement of MCCB 4 pole 415 Volt, 50 Hz,125 Amps with breaking capacity 16 KA fixed, theremal magnetic release type all as specified and directed. |
| 113 | S & F in replacement of MCCB 4 pole 415 Volt, 50 Hz,100 Amps with breaking capacity 16 KA fixed, theremal magnetic release type all as specified and directed. |
| 114 | Taking down existing street light fitting/flood light/post top lantern of any type, make & capacity. |
| 115 | Supply and fix roadway luminaire LED light fittings of 60 watts and including necessary electric connection with 2.5 Sqmm twin core Copper conductor unarmoured cable, complete all as specified and directed. |
| 116 | Same as item No 115 above but of 70 watts . |
| 117 | Same as item No 115 above but of 90 watts . |
| 118 | Supply and fix LED Flood light 70 W IP 66 including necessary electric connection with twin core twisted flexible copper conductor cable of suitable size . |
| 119 | Same as item No 118 above but of 120 watts |
| 120 | Same as item No 118 above but of 210 watts |
| 121 | Supply and fix LED post top lantern 20 W made in cast aluminium spigot housing with decorative opel polycarbonate diffuser and IP 65 protection including necessary electric connection with twin core twisted flexible copper conductor cable of suitable size complete all as specified and directed. |
| 122 | Same as item No 121 above but of 40 watts |
| 123 | Supply and fix in replacement FRP, hot press moulded SMC pole box 295X255X120 mm comprising of 100 Ams aluminium bus bar 4 strips ( IP 55 protection ) with one MCB SP 6 Ams to be fixed inside the box and box will be clamped bottom of the pole with FI clamps (duly painted) nut bolt washers of required size.Make - SINTEX, Model GSJB-2520 or any other sample approved by GE. |
| 124 | Preparation of old painted steel surface and painting of steel tubular pole upto 09 RM long applying two coats of aluminium paint on complete poles including cross arms and writing of numbers on pole with black paint in 40 mm font size of letters including surface dressing all around the poles approximetely 01 Sq Mtr area complete all as specified and directed . |
| 125 | S & F in repair on load changeover switch with sheet steel enclosure,I-O-II 3 phase & neutral,415 V, 50 Hz, 200 A complete all as specified and directed. |
| 126 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified and directed. |
| 127 | Same as item No 126 but of size above 95 Sqmm and upto 120 Sqmm. |
| 128 | M&L cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified and directed. |
| 129 | Same as item No 128 but of size above 95 Sqmm and upto 120 Sqmm. |
| 130 | M&L for cable jointing kit for 11 KV earthed grade cable straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size upto 95 Sqmm complete all as specified and directed. |
| 131 | Ditto but of size above 95 Sqmm and upto 120 Sqmm. |
| 132 | Repair / Servicing / maintenance of transformer 11 / .433 KV indoor / outdoor type , plinth / pole mounted type including the following work services :- (a) Disconnecting transformer from electric system and providing electric power to user from alternative arrangement including taking out from existing position . (b) Decanning of transformer oil , opening top cover , disconnecting of all internal connections , lifting and taking out of core assemble , LT / HT bushes, Tap changer etc ,cleaning and inspection of core and winding , segrigetion of serviceable and unserviceable items , removing of sludge and cleaning tank and cooling pipes / fins /tanks with pressure water and drying the tank complete. (c) Replacinig unserviceable LT / HT bushing by replacing rubber / cork oil seals and damage terminal rod & replacement of Transformer cover gasket of rubber cork sheet.(d) Re installation of TFR including reassembling of core / winding assebly complete including replacement of unsv parts , repair the defective parts and tighting of all loose / sparks wire / nut bolts etc and refixing the to the existing position , connecting with HT/LT cables and earthing strip and testing complete including necessary Transportation ( If required ) to the work shop and back and including Dehyderation and refilling of existing or new transformer oil of required quantity . NOTE FOR ITEM NO 153 :- (i) Dehydration of oil and new Transformer oil shall be measured seperately . (ii) Transportation of TFR measured and paid seperately . (iii) HT & LT Busing , Tap Changer will be measured & Paid separataly. (iv) In case HV / LV Winding found damages then Contactor shall be made serviceable with new winding and the same will be measured and paid seperately. (v) The rate of cork sheet & Packing Material for following cap of TFR are included in coated rate of transformer capacity 125 to 150 KVA . |
| 133 | Supply only for incorporation under the repair of transformer HT bushing porcelain with copper stud, nuts, bolts, washers, gasket, oil seal suitable for Indoor typeTransformer of capacity 125 to 150 KVA . |
| 134 | Supply only for incorporation under the repair of transformer LT bushing porcelain with copper stud, nuts, bolts, washers, gasket, oil seal suitable outdoor / Indoor typeTransformer of capacity 125 to 150 KVA . |
| 135 | Supply only for incorporation under the repair of transformer Off load Tap changer switch of existing model / type of Transformer of capacity 100 to 160 KVA. |
| 136 | Replacement of silica gel breather assembly including silica gel of transformer 11/0.433 KV of capacity 150 KVA complete all as specified and directed. |
| 137 | M&L for Dehydration of transformers oil minimum three cycles to achieve dielectric strength up to 50 KV in 2.5 mm gap electrode including toping up of Transformer oil if required at site . Note: (i) Dehydration of transformer oil shall be carried out at site and contractor shall take the testing result before and after dehydration of oil and show to the EIC at site and maintain necessary documents for record . (ii) Dehydration Machine with all T&P & Transformer oil testing machine for dehydration of Transformer oil and necessary transportation for the machines shall be arrange by contractor . (iii) Oil required for topping up of transformer will be measured & paid separately. |
| 138 | Supply and topup of transformer oil EHV as per IS 335 of 1993 Part II with dielectric strength up to 50 KV in 2.5 mm gap electrode complete and including necessary transportation complete all as specified and directed. |
| 139 | M&L for maintenance of 2 pole/4pole structure and taking out all old connection/jumpers and fixing fresh jumpers with proper lugs nut/bolts and tightening all incoming and outgoing connection, properly winging with conductor including servicing/greasing of existing GODs and testing for smooth operation and proper alingment of contacts including replacement of any part of fixed/moving contact complete all as specified and directed. |
| 140 | M&L painting of two pole structure of 11m steel poles with cross arms, bracings, clamps of any length and shape for HT power supply upto 11 KV with two coat of aluminium paint including preparation of the existing surface including marking pole numbers in a 15cm dia yellow circle & marking three black & two yellow bands width 30cm by fluorescent paint,from bottom of pole above coping to 1.5 mtr height,complete all as specified and directed. |
| 141 | Supply and fixing in replacement of lightning arrestor suitable for 11 KV grade,expulsion type, complete with all fitting transmission class for outdoor discharge capacity 65KA, complete all as specified and directed. |
| 142 | M&L danger notice plate for HT 25 x 20cm x 1.5mm thick mild steel sheet,vitreous enameled white with letters,figures and conventional skull and bones in signal red colour and fixed with MS clamps,bolts and nuts, complete all as specified and directed. |
| 143 | M & L cleaning of area around two pole structure sub station, power house, pump house U/G sump area by surface excavation not exceeding 30 cm, averaging 15 cm deep and getting out removing shrubs, grass mini plants and other unwanted material, stones etc leveling complete all as directed.Note:- (i) The contractor shall use own T&P as required at site including safety measures. |
| 144 | Excavation in trenches n.exc. 1.5 m wide and n.exc.1.5 m deep in any type of soil and forming bottom surfaces for laying of cable complete all as specified and directed. |
| 145 | Supply & laying sand cushioning for cable protection in trenches 8 cm before laying cable and 15 cm thick over the cable complete all as specified and ditected. Note: Punned down thickness shall be measured for payments purposes. |
| 146 | Supply & laying brick for protection of cable sub class 'B' laid dry flat across the cable with width equal to the length of whole bricks complete all as specified and ditected. |
| 147 | Returning filling in including spreading leveling watering and well ramming in layers n. exc. 25 cm complete all as specified and directed. |
| 148 | Removal surplus soil at a distance n. exc. 50 m and deposited where diredted at a lavel not exc. 1.50 m above the starting pont complete all as specified and directed. |
| 149 | Boring, holes for insertion of 50/80 mm bore GI pipe under the road/hard standing or any other location not less than 1200 mm deeep complete all as specified and ditected. |
| 150 | M & L GI pipe 40 mm bore light grade fixed on pole/under road/on wall for protection of cable including all fittings complete all as specified and directed. |
| 151 | M & L GI pipe 50 mm bore light grade fixed on pole/under road/on wall for protection of cable including all fittings complete all as specified and directed. |
| 152 | M & L GI pipe 80 mm bore light grade fixed on pole/under road/on wall for protection of cable including all fittings complete all as specified and directed. |
| 153 | M&O for periodical maintenance / servicing of DG set consisting of normal repairs such as tightening of nut bolts, greasing, checking of lube oil level , fuel tank, fuel pipes, water / coolent level in radiator,cleanness of air filter, condition of hose ,V belts , battery connections / checking of battery terminals , level of distilled water in battery and checking of all other visual parts of DG set including routine cleaning of dust with vacuum cleaner etc ( once a week or as required and directed by Engr-in-Charge / JE.) (a) For DG Set 180 KVA, Make;- Ashok Leyland (i) The maintenance cost of DG Set for whole month shall deemed to comprises of cost of labour employed for the purpose, T&P used and other petty items such as cotton waste, Kerosene oil, Grease, nuts, bolts etc. (ii) Replacement of spares parts and oil will be measured and paid separately under relevant items of BOQ. |
| 154 | Supply only following spare parts for DG set 180 KVA , Make Ashok Leyland |
| 155 | Diesel Filter (fuel filter) |
| 156 | Mobile filter (lube oil filter) |
| 157 | Air filter (primery & safety element) including air cleaner hose with T bolt and clamp. |
| 158 | Piston assembly. |
| 159 | Set of Piston ring. |
| 160 | Valve seat Intake. |
| 161 | Valve seat Exhaust. |
| 162 | Valve insert. |
| 163 | Valve Guide stem. |
| 164 | Injector cup |
| 165 | Connector female. |
| 166 | Bearing connecting rod. |
| 167 | CR bush. |
| 168 | Upper gasket kit |
| 169 | Lower gasket kit |
| 170 | V Belt for fan drive. |
| 171 | Starter ring |
| 172 | Fuel pipe with copper washer and banjo bolt ( fuel tank to fuel filter) |
| 173 | Oil pipe with copper washer and banjo bolt |
| 174 | Drain cock with adoptor. |
| 175 | Lube oil pressure sensor (sensor + switch) |
| 176 | Water line hose kit |
| 177 | M/L for cleaning the fuel tank both internally and externally by removing all the dust / sediments etc including replacement of fuel tank lid by new one for DG set of capacity 180 KVA , Make Ashok Leyland |
| 178 | Taking down the defective water pump from DG set of any type and capacity and replace with new one for DG set of capacity 180 KVA , Make Ashok Leyland all as directed . |
| 179 | M&L for Repair to Radiator assy by disconnecting the radiator from engine frame and servicing/cleaning with acid and brazing where required to stop leaking tubes/joints etc. cleaning fins and re-fixing the same for DG set of capacity 180 KVA , Make Ashok Leyland all as directed. |
| 180 | Supplying and filling coolant as recommended by manufacturer in DG sets. |
| 181 | Supply in sump / topping up engine oil, multi grade 20w /40 in engine or replacement of engine oil for DG SETS .Make: Indian oil / Hindustan petroleum / Castrol. |
| 182 | Dismantling and taking out all burnt windings from Armature, Main field, stator field and armature complete assembly fitted in 180 KVA DG Sets and M& L for rewinding of alternator with super enameled copper wire of existing gauge size and turns and makers specifications including all associated insulating material such as separator and heat varnishing etc including both inner and outer bearing of existing size and model, after complete repair of alternator re-assembling and refixing the same in position including testing complete all as specified and directed. |
| 183 | Supply and fix in replacement battery of capacity 150 AH, 12 V including brass battery terminal suitable for DG sets complete all as specified and directed. |
| 184 | M &L for Removing the fuel injection pump (FIP) from DG set cap180 KVA Make Ashok Leyland and carry out servicing and calibration from authorised maker's work shop including replacement of injectors, nozzles, etc. and refitting the same for smooth and efficient functioning all as directed. Note :-Repairs will be carried out from authorised workshop of MICO or manufacturer of DG set. |
| 185 | Taking down defective self starter and supply and fix in replacement self starter for 180KVA DG set of Kirloskar make. |
| 186 | Supply and fix in replacement AVR (automatic voltage regulator) for DG sets 180 KVA complete all as specified and directed. |
| 187 | Supply and fixing in replacement DG set controller in control panel of DG Set 180 KVA, Make Ashok Leyland,duly programmed by manufacturer,testing and comissioning complete all as specified and directed. |
| 188 | M&L for replacement of power contactor 4 pole, 415 volts, 400 amps coil operating voltage 230 Volt AC, Make-INDO ASIAN / L & T model MCX-43 or equivalent as in PS. |
| 189 | Supplying and laying synthetic rubber insulated mats 2.5 mm thick for voltage upto 11 KV for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m. |
| 190 | Supply installation testing and comissioning glow sign board in replacement made by emerged letters in red colour or as asked ( CDA PATNA ) of dimentions width X height of each letter not less than 4 feet X 2 feet fixed with LED light modules & SMPS adapter as per size and shape of required letter ,letters made with fiber acrylic sheet and both side of letters framed with alluminium coated panel of thickness not less than 3 mm fixed on existing metal framed sign board structure complete all as secified and directed. Note : Contractor has to submit warrenty for at least two years for LED lights fixed in sign board and fiber acrylic sheet/material used in sign board. |
| 191 | Supply and fix in replacement sluice valve of 80 mm dia ISI marked with cast iron body bonnet wedge stuffing box galvanized thrust plate band plate wheel of gry cast iron ,operated with heigh tensil brass spindle, wedge body seal ring and wedge facing lead tin brass bolt and nut compressed fiber bolt pressured rating PN-1.6 confirmed to 14846 including material and labour for jointing flange joint with rubber / fiber jointing ring bolt nut and washers etc complete all as specified. Make: Upadhyay/ Kirlosker/BIR. |
| 192 | Supply and fix CI reflux (non return) valve 80 mm bore as per IS 5312 with GM working parts both ends flanged and suitably machined and drilled for and including required nut, bolts washer rubber/ fiber packing complete all as specified and directed. Make Remco/ Kirlosker. |
| 193 | Taking up GI steel water tubing 15 mm bore from the tranches by necessary excavation or on wall / laid under floor/ ceilings with complete fittings,any grade complete all as specified and directed. ( Note:- excavation and earth work shall be measured and paid separately.) |
| 194 | Same as item No 171 above but 20 mm bore |
| 195 | Same as item No 171 above but 25 mm bore |
| 196 | Same as item No 171 above but 40 mm bore |
| 197 | Same as item No 171 above but 50mm bore |
| 198 | Same as item No 171 above but 80 mm bore |
| 199 | Supplying and laying steel water tubing 15 mm bore medium grade galvanised with all fittings like bend, tees socketes union etc. as required laid in trenches/ or on wall / laid under floor/ ceilings complete all as specified and directed. |
| 200 | Same as item No 172 above but 20 mm bore |
| 201 | Same as item No 172 above but 25 mm bore |
| 202 | Same as item No 172 above but 40mm bore |
| 203 | Same as item No 172 above but 50mm bore |
| 204 | Same as item No 172 above but 80mm bore |
| 205 | Supply and fix in replacement gun metal globe or gate valves with iron wheel head, screwed both ends for iron pipes suitable for 20 mm bore dia of pipe complete all as specified and directed. |
| 206 | Same as item No 173 above but 25 mm bore |
| 207 | Same as item No 173 above but 40 mm bore |
| 208 | Same as item No 173 above but 50 mm bore |
| 209 | S & F chromium plated fancy type bib taps,cast copper alloy with crutch or butterfly handel,screwed down screwed for iron pipe or for brass ferrule and fixed for 15 mm bore dia of pipe complete all as specified and directed. |
| 210 | Dismantling and taking out complete assy of 7.5 HP capacity make Kirloskar submersible pump from bore well keep aside for repairing/assembling by replacemenrt of parts all as specified and directed. Note: Spare Parts required to be measured and paid spearately. |
| 211 | Dismantling of complete bowl assy of 4 stage ,replacement of impellers GM , impeller rings,bearing sleeve ,ruber bushes ,neck rings ,distance bushes, thrust screws,centre guide rings, connection pieces etc as per matching size and sample and requirement of pump complete all as specified and directed. |
| 212 | Dismantling of mortor taking out rotor complete and carrying out rewinding to starter by using supper quality of copper conductor of matching size in guage and weight using best quality of insulation material taping varnishing drying backing complete all as specified and directed. |
| 213 | Assembling fitment with the pump and making fit for lowering with necessary connection with starter / panel and testing complete all as specified and directed. |
| 214 | Supply and lowering / fixing MS coloumn pipe 80mm bore flange type and 7.1 mm thickness ERW steel pipe including jolinting material i.e. rubber packing,nuts, bolts washers etc. |
| 215 | Supply, installation / lowering and commissioning the submersible pump set with strove lined non return valve directly coupled with and including induction motor of 7.5 HP capacity for operation on 415 Volts +/- 10% , three phase , 50 Hz,copper wound & pump having 4 stage complete with necessary accessories specified by manufacturer, suitable for 1200 LPM discharge of water at 48 meter head all as specified and directed. Make : Kirlosker/ KSB / CRI /Crompton . Note :- Rates for lowering of pump & column pipe of size 80 mm bore flanged type & M&L for new jointing material i.e. rubber packing ,nuts, bolts and washer etc.will be measured and paid separately under respective item of schedule. |
| 216 | Supply & fix in replacement fully automatic star delta starter for submersible pump comprising with over load relay, amp meter, volt meter suitable for 7.5 HP capacity Kirlosker/CG make submersible pump complete all as specified and drected. Make of starter: Havells / L&T |
| 217 | Cleaning of OHT having capacity upto ten thousand gallons by removing deposited sand,mud,silt and taking out from the tank, Flushing out the mud water by scraping out deposited mud on surfaces inside the tank by using steel brush complete all as specified and directed & Putting adequate quantites of lime mixed water and removing the same through wash out followed by poring bleaching solution all around the bottom of the tank complete all as specified and directed. |
| 218 | Supply, connecting and testing (in replacement or for extention) of PVC insulated and sheathed water proof cable wih stranded copper conductor flat submersible cable 1100 V grade complete all as specified for cross section area of 6 Sqmm 3 core. |
| 219 | Taking down existing old defective LT Panel / FP Box by disconnecting its all elecetrical connections and by dismantling foundation complete all as specified and directed. |
| 220 | Supply, install, connect & testing cubical outdoor type factory made double door, powder coated LT bus bar feeder pillar box having alluminium bus bar suitable for 200 Amps 3 phase and neutral arrangement of size 500mm x 500mm x 200mm with MCCB 4 pole 125 A as incoming including provision of LED Indicating lamps (RYB) 01 set of 3 complete weather proof and vermin proof conforming to IP-54 made out of 3.15 mm thick CRCA sheet including provisions for ventilation and cable termination alley & two Nos suitable size of aluminum strip for body earthing all as per IS. It should be mounted on 40 x40 x 6mm angle frame with a clearance of at least 0.45 mtrs above GL and 0.30 mtrs below ground including required PCC for foundation complete all as specified and directed. |
| 221 | Supply,fabrication, installation and testing of LT Panel out door type factory made CPRI Approved, water and vermin proof protection of suitable size made out of 3.15 mm thick CRCA sheet dully supported with mild steel angle iron of size 40 x 40 x 5 mm vertical frame and legs with mild steel flat iron 40 x 40 x 5 mm in horizontal sides of the frame with front and back side openable ,single hinged door / shutter with locking arrengement and powder coated finish both internal and external steel surfaces after necessary preparation of steel surfaces including providing PCC (1:3:6) type C2 (using 40 mm graded stone aggregate) foundation of suitable size and connections of all outgoing / incomming cable inclusive of necessary excavation and earthwork as required including the following fitment accessories and also including removal of old exisisting one complete all as specified and as directed. Note: Rate of earthwork and PCC work are deemed to be inclusive in this item. (a) Incoming:-(i) On load Change Over Switch 630 Amps , 4 pole 01 No. (ii) MCCB 630 AMPS 4 pole 415 Vollts 50 KA -01 No. (iii) Digital type Amp Meter 0-800 Amp with CT's 03 Nos. (iv) Digital type voltmeter 0-500 Volts -01 No. (v) Indicating lamps (RYB) 01 set of 3. (vi) Alluminium bus bar rating 1000 Amps 3 phase neutral-01 set. (vii) Chamber for incoming & outgoing cable. (b) Outgoing :- (i) MCCB 400 AMPS 4 pole 415 Vollts 36 KA -02 No. (ii) MCCB 250 AMPS 4 pole 415 Vollts 36 KA -02 No. (iii) MCCB 160 AMPS 4 pole 415 Vollts 36 KA -03 No. |
| 222 | M&L earthing complete with galvanised steel earth plate 600X600X6 mm thick buried directly in ground (earth pit not les than 2.25 M deep below GL with top edge of plate not less than 1.5 m below GL) connected with GI earth strip of 32X6 mm as earthing leads by means of bolts, nuts, check nuts and washers beside brazing at all joints as shown on drawings and including excavation, earth work. GI pipe light grade 40 mm bore for protection of GI earth strip from earth electrode to and including the earth test point, supplying and laying charcoal dust, common salt PCC (1:2:4) type B1chamber and MS angle iron frame of 40mmx40mm x3 mmand RCC cover 40 mm thick (1:2:4) type B1 using 20 mm graded stone aggregate reinforced with 8 mm dia TMT bars @ 75 mm C/C both ways with MS handle 12 mm dia, PGI funnel and wire mesh, 20 mm dia GI pipe light grade for watering all as shown in electrical plate No 3 of SSR Part -I and conected to earth test point including testing complete all as secified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 05, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 26, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 12 daysNov 02, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 19 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender