Tender For Shifting Of 02 X Cemented Pole, Three Phase Connection At Uro & 10 Security Light In Mt Garage Of Tk Tptr Pl Asc And special Repair Of Submersible Pump Set And Other Connected Items Against Ber Under Ge (East) Ferozepur Cantt
Tender Overview
Project Description
Tender for Shifting Of 02 X Cemented Pole, Three Phase Connection At Uro & 10 Security Light In Mt Garage Of Tk Tptr Pl Asc And special Repair Of Submersible Pump Set And Other Connected Items Against Ber Under Ge (East) Ferozepur Cantt
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 16-Oct-2026 | BOQ corrigendum | BOQ | 26-Oct-2026 |
| 2 | 26-Oct-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 02-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Supply and fix Prestressed concrete poles of 9 meter long having 102mm x 152mm at top and 102mm x 289mm at bottom, class 10, including foundation and coping, complete all as specified and directed. |
| 2 | Supply and fixing LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection, complete all as specified and directed. |
| 3 | Supply & fixing street light pole cable junction box IP-65 with box size of 200x160x98 with 4 Nos of terminal block, 1 Nos of earth terminal metnic knockouts for cable entry and the box made out of thermal plastic material suitable for 16/25 UG sqmm cable including clamps bolts, nuts duly painted and MCB SP 6 Amp etc. complete all as specified & directed. |
| 4 | Supply & fixing 3 core 1.5 sqmm PVC insulated and FR PVC round sheathed copper conductor flexible 1100 volts for connection from Junction Box to street light fittings including clamps for FR PVC wire as specified & directed by Engr-in-Charge. |
| 5 | Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area of size 4 core 16 sqmm including taking out old u/s cable complete all as specified and directed. |
| 6 | Supply and fixing GI pipe light grade 40mm dia upto 1.5 Mtr from surface to junction box with all fittings for cable protection all as specified and directed by Engr-in-charge. |
| 7 | Supply and fixing GI pipe bracket for street light fittings made out of 40 mm dia GI pipe medium grade 1.2 mtr long bent to required angle/shape with and 2 x pair of MS clamps made out 40mmx5mm MS flat iron bolts,nuts complete including two coat of synthetic enamel paint (first grade) over a coat of red oxide complete all as specified and directed by Engr-in-charge |
| 8 | M&L Painting of LT PCC pole upto 1.5 mtr height from PCC, of synthetic enamel paint with black and white strips and including wiriting pole No all as specified and directed by Engr-in-Charge. |
| 9 | Material & labour for boring hole under the road/payment/ hard standing upto 150 mm Bore Pipe not less than one metre below ground level complete all as specified and directed. |
| 10 | Supply, installation, testing and commissioning in replacement of CPRI approved, factory made, LT panel board cubical, Outdoor type, floor mounted single door, Front & Rear openable with locking arrangement, suitable for AC, 3 phase, 4 wire, 50 cycles, 415 Volts. The panel board shall be made of 3.15 thick CRCA / Powder coated with of suitable size. The panel have to provide proper compartment as per IS specification and wiring of panel with suitable size of copper conductor FRLS cable of suitable size with thimbles,Base frame of the panel shall be made of angle iron of size 50 x50 x 6mm of upto 1/2 mtr hight from GL& 1/2 mtr for Below GL in PCC (1:3:6) type C-2 using 40 mm stone aggregates comprising of following:-(i) Panel having common aluminium bus bar of capacity 200 Amp TPN each and suitable capacity TPN bus bar for outgoing MCCB's,including aluminium lugs to connect the cable and cable gland for Each cable entry as per cable size.(ii) Incoming:-(a) MCCB 4 Pole, 230 V, 63 Amps, Adjustable type with breaking capacity 16 KA - 02 Nos(b) Indicator lamp RYB :01 Nos Set. |
| 11 | M&L Stay assembly complete with accessories as shown in electrical plate No. 1 (loop type insulator, stay clamps, excavation and concrete measured separately) all as specified and directed by Engr-in-Charge. |
| 12 | M&L Galvanised stay strand, 7/4mm all as specified and directed by Engr-in-Charge. |
| 13 | M&L Loop type insulator, vitreous porcelain, white, brown or green, Large size with overall dimensions 90mmx140mm, clearance of hole 25.5mm all as specified and directed by Engr-in-Charge. |
| 14 | M&L Shackle Type, Porcelain, vitreous, white, brown or green insulator Size working pressure In volts 1100, 75mm Height, 90mm Max. dia, Section of straps 31x3, Dia of bolts 12mm, including galvanised mild steel straps, washers, insulator bolts, washers and nuts, all as specified and directed by Engr-in-Charge. |
| 15 | M&L Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia for 1100 volts grade, complete all as specified and directed. |
| 16 | M&L Aluminium conductor, steel reinforced all as specified and directed by Engr-in-Charge. |
| 17 | M&L Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint all as specified and directed by Engr-in-Charge. |
| 18 | Supply and lay Tubes, 'light grade'galvanised, with all fitting and fixed complete to walls and ceilings or laid in floors 80 mm (3”) dia all as specified and directed by Engr-in-Charge. |
| 19 | Supply and lay Tubes, 'light grade'galvanised, with all fitting and fixed complete to walls and ceilings or laid in floors 50 mm (2”) dia all as specified and directed by Engr-in-Charge. |
| 20 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core all as specified and directed by Engr-in-Charge. |
| 21 | M&L XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sq. mm X 3.5 core all as specified and directed by Engr-in-Charge. |
| 22 | M&L XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 sq. mm X 3.5 core all as specified and directed by Engr-in-Charge. |
| 23 | M&L XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 150 sq. mm X 3.5 core all as specified and directed by Engr-in-Charge. |
| 24 | Excavation in trenches n. exc 1.5mm wide and n.exc 1.5m deep for foundation of poles/stays/cable etc and getting out in soft /loose soil complete all as specified and directed by Engr-in-Charge. |
| 25 | Excavation in trenches exc 1.5mm wide and exc 1.5m deep for foundation of poles/stays/cable etc and getting out in soft /loose soil complete all as specified and directed by Engr-in-Charge. |
| 26 | Returning , filling in and incl spreading, levelling watering and well ramming in layers each n.exc 25cm thick in soft/loose soils complete all as specified and directed. |
| 27 | Removing surplus soil to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above the starting point etc complete all as specified and directed. |
| 28 | M & L dry and clean fine sand for cable cushioning for cable protection complete all as directed.Note : Punned down thickness shall be measured. |
| 29 | Supply and laying well burnt, sub class 'B' brick old size for cable protection complete all as specified and directed. |
| 30 | M&L for cement concreted (1:4:8) type D-2 using 40 mm graded stone aggregate as in foundation of poles filling and mass concreting complete all as specified and directed. |
| 31 | M&L for cement concreted (1:3:6) type C-2 using 40 mm graded crushed stone aggregate in foundation of pole/ stay assembly/feeder pillar box/LT panel,etc, incl necessary form work and fair finsh to exposed surfaces without using extra cement etc, complete all as specified and directed. |
| 32 | M&L Cement concreted (1:2:4) type B-1 using 20 mm graded stone aggregate as in foundation of electric poles/struts/ etc including necessary form work, fair finished surfaces without using extra cement, complete all as specified and directed. |
| 33 | Supply, installation, commissioning and testing of submersible pump set V-8 Multistage (As per mfg design stage ( min 4 stage)) electric driven 2900 RPM of capacity not less than 780 LPM at not less than 90mtr head water lubricated suitable for 200/250mm bore and 150 mm dia discharge pipe coupled with squirrel cage induction electric motor 3 phase 415 volts of capacity not less than 30 HP having CI casing & Gun Metal impeller fitted with delivery pipe etc as reqd at site with suitable electric motor, B class insulation, IP-68 Protection and electric connection With following MOC: Stainless Steel Impeller, Stainless Steel Pump Shaft, LTB Pump Bushes, Cast Iron Bowl/Stage Casing; complete all as specified and directed. |
| 34 | M&L Testing and developing the bore well by means of air compressor 5000 PSI till sand free clear water discharge is obtained to achieve maximum yield of suitable capacity for first 24 hours running complete all as specified (All equipments shall be arranged by contractor at his own cost), complete all as specified and directed. |
| 35 | M&L MS clamps made out of flat iron 125mmx12mm and 01 metre long with nut, bolts of 22mm dia of suitable length for 350mm bore housing pipe, complete all as specified and directed. |
| 36 | M&L Mild steel structural steel E-250 grade 410W (ISMB-150) fixed independently without connecting plate including two coats of black paint over a coat of red oxide complete all as specified and directed. |
| 37 | Supply and fixing Sluice valve for 100 mm dia pipe ISI marked flanged type, class PN 1.6 with Stainless steel spindle, necesary bolts & nuts of suitable size with and including rubber gasket for flanged joints and testing complete of following sizes all as specified and directed. |
| 38 | Supply and fixing CI Non return valves for 100mm dia pipe ISI marked, flanged type class PN 1.6 with necesary bolts & nuts of following size with and including rubber gasket for flanged joints and testing complete of following sizes all as specified and directed. |
| 39 | S&F Flat Submersible cable PVC multistrandard copper conductor 3 core 25 sqmm from LT Panel/ star-delta starter to pump motors, complete all as specified and directed. |
| 40 | S&F Mild steel Column pipe heavy duty 5.4 mm wall thickness 100 mm dia in 3 m length including flanged both side including provn of nuts, bolts, gasket etc including lowering and fixing, complete all as specified and directed. |
| 41 | Supply and laying Ductile iron pipe of 100mm bore with spigot and socket ends centrifugally cement mortar lined complete as per IS8329/2000 class K -7 with including suitable for tyton joint and jointing material / joints laid in trenches complete all as specified and directed. Note:-DI specials and earth work shall be measured and paid separately. |
| 42 | Supplying, installing, commissioning and testing Chemical Dozing pump installed directly on water line; suction injecting electric pump of suitable capacity, ready to use solution, dosage proportional to water flow (no influence of water flow variations), can tolerate variations of pressure from the water line, no pump damage even when the additive tank is empty, no overdozing risk/ no pure chemical injection risk when water supply is off. It can work on a suction lift of upto 4mtr, suction line with foot valve strainer. The dosing pump coupled with single phase electric motor of suitable capacity,assembly with agitator in one motor , agitator with SS sweep blade duly FRP coated and PVC tank of Cap 100 ltrs complete all as specified and directed by Engineer in Charge. |
| 43 | Supply and Fixing of Fully automatic star delta starter type MUG 30, suitable for 30 HP Submersible pumps/ motor 415 volts, 50 Hz with relay range 23-33 Amps in sheet metal enclosure with Voltmeter/Ameter CT's, short circuit protection, auto unit, single pahse preventer IP55 box & selecter switch. Make:- L&T / Seimens/BCH. |
| 44 | M&L Earthing complete with GI earth plate electrode 600 mm x 600mm x 6.3 mm thick burried directly in ground vertically to a depth not less than 2.25 m below ground level with the top edge of earth plate at depth not less than 1.5 m below ground level connected to galvanised iron strip 32 x 6 mm earthing lead by means of bolts, nuts, check nuts and washers protected by 40 mm bore light grade GI pipe, funnel with 20mm bore GI medium grade pipe for watering, wire mesh, including concrete pit in PCC (1:3:6) type C-1, pre-cast RCC 1:2:4 type B-1 cover slab of size 350x350x50mm reinforced with 8mm dia TMT steel bars @15cm centre to centre both direction and 10mm dia MS handle of suitable size, charcoal or coke and salt in alternative layers,necessary excavation & earth work in soft/loose soil all as shown in Electrical Plate No 3 of MES Schedule Part I and testing complete all as specified and as directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 4 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender