Defence Statutory Bodies & Commissions/Committees Closing in 5 days TDR #57866349

Tender For Repair / Maintenance Of Water Supply Installations Including Cleaninig Of Tanks, Sumps And Other Misc E/M Works At Af Stn Ad Ur

Issued by Statutory Bodies & Commissions/Committees · Jalandhar, Punjab
Tender Value
45 Lakhs
Estimated cost
Bid Submission
22 Oct 2026
5 days left
EMD
90000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Jalandhar → Punjab
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair / Maintenance Of Water Supply Installations Including Cleaninig Of Tanks, Sumps And Other Misc E/M Works At Af Stn Ad Ur

BOQ

Name of Work:- REPAIR / MAINTENANCE OF WATER SUPPLY INSTALLATIONS INCLUDING CLEANINIG OF TANKS, SUMPS AND OTHER MISC E/M WORKS AT AF STN AD UR
Sl. No. Item Description
1Excavation in trenches in soft/loose soil not exceeding 1.50 metre wide and not exceeding 1.50 metre in depth; for foundation, etc. and getting out complete, all as specified & directed.
2Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick each, complete, all as specified & directed.
3Removing excavated spoil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete, all as specified & directed.
4NOTES APPLICABLE TO SERIAL ITEM 1 TO3: (a) Excavation work shall be carried out manually only.(b) LT/HT cable, water supply/ sewage/telephone lines, if any, get damaged during excavation & earthwork, demolition of PCC shall be repaired by the contractor immediately as per existing specifications to the entire satisfaction of Engineer-in-Charge.
5M&L FOR Cleaning of RCC over head tank draining out water / sludge from tank, removing all scales, dirt , algea and other growths from the floor, roof and from mouths of circulating pipes by rubbing with the wire brushes and high pressure cleaning method with rotary sets with approved detergent and sucking out all dirty water by vacuum cleaner, disinfecting the over head tanks with approved chemical solution for making surface bacteria free and finaly cleaning with fresh water to the satisfaction of Engineer-in-Charge including painting MS plate manhole covers suction pipe rugs etc with anti corrosive paint and writing outside tank as ''TANK CLEANED ON'' and capacity on black painted surface including removing all dirt outside MD land complete of following capacity and staging: -
610000 gallon staging up to 15 metre height.
715000 gallon staging up to 15 metre height.
820000 gallon staging up to 20 metre height.
9150000 gallon staging up to 20 metre height.
1025000 gallon staging up to 25 metre height.
1150000 gallon staging up to 25 metre height.
12150000 gallon staging up to 25 metre height.
13Dewatering and cleaning of sewage well / drainge water well any type any shape including removing of dirty muddy / sewage / drainage water along with unwanted nonperishable items i.e polythene bags, PVC scrap, PVC bottles, shells, gum boots, wooden pieces and other floating materials etc and including removing complete wet type sludge formate / wet muddy formate from the inside of under ground well / tank and also connected entrance chamber area & hole area of well any type / size / depth and clean up to the last bottom level of well complete with all respect and disposal out / carrying out by manually or mechenically system to the wet sludge / muddy formate along with all type off floating material burried / carry out outside MD land complete for under ground well sump of size:-
146.5 dia and 9 metre depth.
153.0 dia and 5 metre depth.
16Under ground sewage sump well of size internal dia 5.20m and depth 4.5m at STP 0.25 MLDcomplete all as specified and directed.
17Under ground raw sewage water sump of size 10.0m dia and 2.5 deep at STP 1.2 MLD complete all as specified and directed.
18Under ground sewage sump of size 4.6m x 4.6m x4.6m deep.at STP 0.25 MLD complete all as specified and directed.
19Raw sewage water tank of size 8.3m x 2.5m x2.5m deep at STP 1.2 MLD complete all as specified and directed.
20Raw sewage water tank of size 2.6mx2.4mx1.4m (JCO ORs MAP Qtrs) complete all as specified and directed.
21Chlorine contact tank of size 8.3mx2.5mx2.5 (STP 1.2MLD) complete all as specified and directed.
22Chlorine contact tank of size 2.5mm and 2.50mx1.4m (STP 0.25MLD) complete all as specified and directed.
23NOTE APPLICABLE FOR SERIAL ITEM 4 & 5:- (i) All required T&P for cleaning of RCC over head tank / under ground sewage, water sump and other safety equipment required for working of manpower shall be arrange by contractor under own arrangement without any extra cost to the Dept. (ii) The contractor shall soley responsible for any mishap,accident and other mishappening to workmen during working time and setting all claims of workmen as per the labour commissioner or court law and the rates quoted by the contractor shall deemed to be included for this aspect and nothing extra shall be payble on this account. (iii) The contractor provided sufficient more nos labour for cleaning of overhead tank under ground sump within the given time period by department. No such type of delay reason are not accepted due to shortage of labour for cleaning of over head tank / under ground sump.
24S&F in replacement filter media gravel of size 6.5mm to 15mm for sludge drying bed coarse type including taking out existing filter media 0.25 MLD STPcomplete all as specified and directed.
25Taking out filter media carefully from Daul media filter/activated carbon filter and depositing at a distance not less 50 mtr where directed, cleaning and removing sludge/silt deposited on the vessels and deposited where directed all as specified for daul media filter of size 2100mm dia x 1600mm height at STP 1200 KLD.
26Taking out filter media carefully from Daul media filter/activated carbon filter and depositing at a distance not less 50 mtr where directed, cleaning and removing sludge/silt deposited on the vessels and deposited where directed all as specified for daul media filter of size 1000mm dia x 1600mm height at STP 250 KLD.
27Re-use of gravels of size 40 to 6mm obtained from item above after screening and segregation size wise and washing /cleaning with using suitable non toxic chemical/acid washing and free from any silt , foreign material etc and refilling gravel grade wise to the bed of filtration plant complete all as specified and directed of size 1000mmx1600mm height at 250KLD STP.
28Supply and lay in layers activated carbon compound duly treated in activated carbon filter of size 2200mm dia x 1800mm height at 1200 KLD and 250 KLD STP complete all as specified and as directed.
29Supply and laying in layers pea gravels duly cleaned and washed of following grades complete all as specified and directed
3060mm to 50mm grade
3140mm to 20mm grade
3212mm to 8mm grade
338mm to 4.5mm grade
344.5mm to 2.5mm grade
35Supply and laying in layers filter sand of uniform grading of 16/32 mess size dry and cleaning properly complete all as specified and directed.
36Supply and laying MBBR filter media virgin plastic complete all as specified and directed.
37Supply and laying bacteria culture powder complete all as specified and directed.
38M&L for carrying out maintenance/repairs of Air compresser by removal and dismantling air blower, throughly cleaning,lath work as reqd, correct setting/timing of impellers, correct differential pressures and replacement of defective parts of Usha air blowers including replacement of lubricating oil/grease Cap-800 Cum/hr, type-UGRK-190SS, assembling after repair and reinatallation, testing complete all as specified and directed .Note :- Replacement of defective parts will be paid saperately under respective schedule of work.
39All as per item No 16 above but Cap-185 Cum/hr, type-UGRK-140SS complete all as specified and directed.
40S&F in replacement of following parts for making the air blower (make :Uhsa Air Compressor Pvt Ltd) in fully serviceable condition during the process of repair, as per existing complete all as specified and directed:-.
41Air filter of Usha air blowers cap-800 Cum/hr as per existing
42Air filter of Usha air blowers cap-185 Cum/hr as per existing complete all as specified and directed.
43Supply and filling of oil grade castrol Hypo B 90/servo gear super 90/HP gear oil X-P90 for replacement/top up complete all as specified and directed.
44Air blower Belt size as per existing size (STP .25MLD) complete all as specified and directed.
45Air blower Belt as per existing/size (STP 1.20 MLD) complete all as specified and directed.
46Blower Bearing as per existing, size (STP 0.25MLD) complete all as specified and directed.
47Blower Bearing as per existing, size (STP 1.20MLD complete all as specified and directed.
48Chemical analysis including micro biological examination of water sample obtaining from bore well at pump house No-1 to 14 and 02 Nos STP (raw & clear water test) under GE (AF) Adampur. Collect the sample as per standard operating procedure from bore well and STP as chemical and microbiological as per the IS specification.NOTE:- (i) The complete analysis report should be submitted within specific period. (ii) Bore well should be test by NABL approved lab as approved by GE.
49S&F in repair Cast Iron butter fly valve wafer Type, with SS-304 disc, body S.G iron, lever operated, Nitrile / EPDM rubber lining seat, ISI marked complete all as specified and directed , of size: -
5080 mm dia
51150 mm dia
52S&F in replacement of wire antina with lead system complete as per existing size/type and suitable for signal operation of scada automation slave panel complete all as specified and directed.
53S&F in replacement of Buzzer system with base Electrical connector as per existing size/type and suitable for showing to fault level of scada automstion slave panel complete all as specified and directed.
54S&F in replacement of Pressure switch 0-10 Kg/sq cm with accessories and calibrate with PLC(Programmable logic controler) as per existing sample/size complete all as specified and directed.
55Supply, Reprogramming and Fixing PLC (Programmable Logic Controller) with connected power supply system with controller lead complete as per existing model no. Nexgenie1000/ model suitable for automation Slave panel including comprising of main controller all as specified and directed by Engineer-in-charge. Make : Mitsubishi /Unitronics/Siemens.
56Supply, Reprogramming and Fixing in replacement HMI - GT 21 Series 3.8'' TFT Monochrome ,TFT LCD With 32 Gray Scale 24 vdc Builtin , RS 232 , RS - 485 USB PORT interference for PLC based panel. Make :Unitronics / Mitsubishi /Renu .
57NOTES APPLICABLE TO SERIAL ITEM 24 to 25. Downloading and uploading of the PLC programs carried out only in the presence of Recktronic device & system / Automation and Tech solutions or Integrated control system as approved by GE.
58Relay pin type 4C/O IN REPLACEMENT complete, as per existing model & compatibility of size: -
59220-240 volt AC
6024 volt DC
61Supply and fixing in replacement of wireless communication modem with for communication to the slave panel as well as SCADA system as per exiting sample/ size complete all as specified and directed.
62Supply and fixing in replacement of indicator lamps of colour red / green/ yellow as per exiting sample/ size complete all as specified and directed. Make : ESBEE / Schneider /L&T
63Supply and fixing in replacement of push button with Led indicator red/ green type -240 Volt Ac as per exiting sample/ size complete all as specified and directed. Make : ESBEE / Schneider / L&T
64Supply and fixing in replacement of rust proof, maintenance free magnetic float switch / water level sensor as per exiting sample/ size completeas specified & directed. Make :RDS/ATS or equivalent make
65Supply and fixing in replacement of hand wheel or as per exiting sample/ model for actuator suitable for of size 150mm dia butterfly valve as per exiting sample/ size complete all as specified and directed by EIC. Make : Ritetork/Emtork/Astech
66Supply and fixing in replacement of SMPS unit suitable for out put 24 volt DC and input 230 volt AC of rating 3Amp as per exiting sample/ size complete all as specified and directed by EIC. Make: Schneider / NHP or equivalent make
67Supply , fixing , testing commissioning of motorised valve of size 80/100 mm dia complete single phase motor actated butterfly with gear box valve set with disc material of CI with nylon coating, hand wheel for manual operation, pressure rating of 10 kg/sq cm and having 02 nos limit switches for oper / closed condition and capability of accepting 4-20mA input complete set complete all as specified and direted by EIC MakeRitetork/Astech/Emtork
68Supply , fixing , testing commissioning of motorised valve of size150 mm dia complete single phase motor actuated butterfly with gear box valve set with disc material of CI with nylon coating, hand wheel for manual operation, pressure rating of 10 kg/sq cm and having 02 nos limit switches for oper / closed condition and capability of accepting 4-20mA input complete set complete all as specified and direted. MakeRitetork/Astech/Emtork
69Supply and fixed in replacement of defected/ burn out /unsafe internal control wiring and connection for automation slave panel installed at pump house and including using by FR PVC insulated electric wire with copper conductor wiring having of single core of size 0.5 sqmm to 1.0 sqmm sub wiring as properly electrical connection for smooth controlling panel of scada system including resetting of system complete and testing all as specifed and directed by Engr-in-charge Make: Recktronic Devices & Systems / Automation and Tech Solutions / Integrated Control Systems.
70Supply and fixing in replacement of 4 Core 1.5 sq. mm PVC sheath PVC insulated copper armoured cable as per exiting sample/ size complete all as specified and directed by EIC. Make: Havells/Nicco/Plaza/Polycab
71Supply and fixing in replacement of 2 Core 1.5 sq. mm PVC sheath PVC insulated copper armoured cable as per exiting sample/ size complete all as specified and directed by EIC. Make: Havells/Nicco/Plaza/Polycab
72Supply and fixing in replacement of 5 pair of 0.5 mm dia armoured copper cable suitable for sensoring with suitable size of PVC conduit pipe as per exiting sample/ size duly fixed on wall of over head tank complete all as specified and directed by EIC. Make:-Havells/Nicco/Plaza/Polycab.
73Supply and fixing in replacement of 6 Core 1.5 sq. mm PVC sheath PVC insulated copper armoured cable as per exiting sample/ size complete all as specified and directed by EIC. Make: Havells/Nicco/Plaza/Polycab
74S&F in reapair earthing with and including GI earth plate electrode 6 mm thick of size 600 mm x 600 mm with 25 mm x 4 mm GI strip earthing lead complete all as shown in electrical plate No. 3 and as specified in Particular Specifications of contract.
75NOTES: -(i) The unit rate includes earthing lead and protection pipe upto 7.5 metre from top of earth plate.(b) Factoy fabricated precast PCC pit & cover shall be fixed at least 500 mm away from earth pit. (iv) Earth resistance should not be less than 3Ohm. In case the test results are not found below 3 Ohm, complete earthing will be redone without any extra cost to Govt.
76S&F Aluminium strip 25 mm x 3 mm with saddles and fixing screws on porcelain insulators for roof conductors and down conductors above ground level and in trenches fixed in replacement complete all as specified and directed.
77M&L for , Air termination, single pointed copper rod 12mm dia and 300mm long, including making connection to earthing conductor, fixed as in replacement of old termination rod, complete all as specified and directed.
78S&F, GI pipe 25mm bore light grade (ISI marked), cut piece of 1.0 metre - 1.5 metre length or as directed by Engineer-in-Charge, fixed vertically with bottom end embeded in & including cast-insitu PCC (1:2:4) using 40mm graded aggregate block of size 20cmx20cmx 15cm including use and waste necessary fair finish form work, and other end (at top) fixed to air termination rod with necessary bolts, nuts etc as required, complete all as specified and directed.
79M&L for repairs to taking down the existing Aviation obstrction light and replacing new LED obstruction light as per Make: Bajaj or equivalent fixed on top of OHT with necessary fixing arragement and providing PVC insulated three core flexble copper cable and including non metalic conduit 20mm dia fixed on suface of water tank upto control MCB enclosure with MCB SPN 06A including all as specified and directed by Engineer in charge.
80S&F in replacement of cast iron foot valve of size 150 mm dia bore ISI marked with gun metal flapper and high quality pressure stop gasket, nuts,bolts and washers etc complete all as flanged type or as per existng sample/ model including providing joints and jointing materials as rubber washers/gaskets with suitble type / size of bolts and nuts, etc, including taking down old and removal of old foot complete all as specified and directed.
81All as per above serial item No. 47 here-in-before but 100 mm dia bore
82All as per above serial item No.47 here-in-before but 80 mm dia bore
83All as per above serial item No. 47 here-in-before but 40 mm to 65 mm dia bore Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57866349
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 45 Lakhs
LAST DATE 22-10-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair / Maintenance Of Water Supply Installations Including Cleaninig Of Tanks, Sumps And Other Misc E/M Works At Af Stn Ad Ur
Basic Detail
Tender No GE(AF)/ADM/T-41 OF 2026-27
Bidding Type Tender
Location
City Jalandhar
State Punjab
Key Dates
Publish Date 05 Oct 2026
Submission Date 22 Oct 2026
Open Date 24 Oct 2026
Finance
Tender Value 45 Lakhs
Tender Fee 500
EMD 90000
Exemption Available
Document List
65e786f4-21ab-4371-b705-156c56b2cebe.html
BOQ_888461.xls
tender.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 05, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 22, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 5 days
Oct 24, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 7 days

Tender Documents

Download All (ZIP) ↓
html

65e786f4-21ab-4371-b705-156c56b2cebe.html

xls

BOQ_888461.xls

pdf

tender.pdf

pdf

Tendernotice_1.pdf

Disclaimer