Tender For Providing, Installation & Commissioning Of 45 Kw Vfd In Place Of Damaged Vfd, Servicing Of Complete Electric Panel And Scada At 04 Mld Stp, Omara, Udh Ur.
Tender Value
5.50 Lakhs
Estimated cost
Bid Submission
14 Oct 2026
8 days left
EMD
11000
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Udhampur → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Providing, Installation & Commissioning Of 45 Kw Vfd In Place Of Damaged Vfd, Servicing Of Complete Electric Panel And Scada At 04 Mld Stp, Omara, Udh Ur.
BOQ
| Sl. No. | Item Description |
| 1 | A. SUPPLY OF EQUIPMENT & MATERIAL (VFD) |
| 2 | Supply of VFD, 45 kW (60 HP) at normal duty, output current not less than 88 A, 380-480 V 3-ph 50/60 Hz, IP20/IP21 for panel mounting, integrated EMC filter (C3 or better), built-in Modbus RTU, 0-500 Hz, PID, suitable for pump/blower duty, ambient not less than 45 °C without derating. Make/model: Schneider Altivar Easy 610 ATV610D45N4 (as per existing damaged unit) or equivalent (ABB ACS580-01-088A-4 / Danfoss VLT AQUA FC-202 / Siemens SINAMICS G120X). |
| 3 | Supply of multifunction meter (V, A, kW, kWh, PF, Hz) with CTs 100/5 A. |
| 4 | Supply of selector switch (Auto/Manual/VFD/Bypass), push buttons, indicating lamps, control relays, SMPS, MCBs, terminal blocks, ferrules and internal wiring (lump sum). |
| 5 | B. INSTALLATION, TESTING & COMMISSIONING OF VFD |
| 6 | Dismantling and removal of damaged VFD from existing panel, disconnection of cables and handing over to department store. |
| 7 | Erection, fixing and alignment of new 45 kW VFD in existing panel (mounting plate/brackets, ventilation clearance). |
| 8 | Laying, dressing and termination of power, motor and control cables including ferruling. |
| 9 | Programming, parameter setting, motor auto-tuning, PID/4-20 mA loop configuration, interlock checks and commissioning by OEM/authorised service engineer, including training of operators. |
| 10 | C. SERVICING OF COMPLETE ELECTRIC PANEL |
| 11 | Shutdown, dust removal (blower/vacuum) and cleaning of complete electric panel, cubicles and busbar chambers; general inspection. |
| 12 | Replacement of defective indicating lamps, push buttons, selector switches, fuses, MCBs and panel meters (allowance). |
| 13 | Servicing/overhauling of MCCBs, contactors, relays and timers; replacement of worn contacts/coils where required. |
| 14 | Painting touch-up, danger/identification plates etc |
| 15 | Labelling, ferruling and neat re-dressing of cables inside panel. |
| 16 | D. SERVICING OF SCADA – CONTROL HARDWARE |
| 17 | Servicing of SCADA server/workstation PC: cleaning, disk clean-up, OS and hardware health check, antivirus update. |
| 18 | Servicing of PLC panel: cleaning, tightening of terminals, checking of power supply, CPU/IO modules and communication modules, PLC back-up battery check/replacement. |
| 19 | Servicing and testing of HMI/operator panel, including touch calibration and display check. |
| 20 | Checking and servicing of industrial Ethernet switch, network/communication cabling and Modbus links (including VFD link). |
| 21 | Servicing of UPS with battery health/backup test. |
| 22 | E. SERVICING OF SCADA – CALIBRATION OF FIELD INSTRUMENTS / LOOP CHECKS |
| 23 | Cleaning, servicing and calibration of ultrasonic/submersible level transmitters. |
| 24 | Servicing and calibration of flow meters (electromagnetic/ultrasonic) with verification of totaliser. |
| 25 | Cleaning and calibration of online analysers (pH/DO/turbidity) using standard buffer/reference solutions. |
| 26 | Calibration of pressure transmitters using calibrator. |
| 27 | I/O loop checking (4-20 mA analog and digital) from field to SCADA screen with calibrator; correction of tag scaling. |
| 28 | F. SERVICING OF SCADA – SOFTWARE, BACKUP, DOCUMENTATION & CONSUMABLES |
| 29 | SCADA software health check,Licence renewal fee: tag verification, alarm, trend and report checking, database clean-up and archiving. |
| 30 | Backup of PLC program, HMI and SCADA project on external media; restore-point creation; licence verification. |
| 31 | Replacement allowance for relays, fuses, 24 V DC SMPS, terminal blocks and other minor spares (as required). |
| 32 | Preparation of service report, updated I/O list and network diagram; operator briefing. |
| 33 | Mobilisation, transport of tools and calibration equipment to site. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 03, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 14, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 8 daysOct 15, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 9 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender