Educational and Research Institute Boards / Undertakings / PSU Closing in 2 days TDR #57847350

Tender For Shifting Of Main Lt Panel D Block & Ups Panel Kidney Block Alongwith Replacement Of 01 Nos. Acb In Old Lt Panel, A Block Including Rewiring With Replacement Of Electrical Fixtures In Lt Canteen,Nehru Hospital, Pgimer, Chandigarh

Issued by Boards / Undertakings / PSU · Chandigarh, Chandigarh
Tender Value
31.41 Lakhs
Estimated cost
Bid Submission
20 Oct 2026
2 days left
EMD
62840
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Chandigarh → Chandigarh
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Shifting Of Main Lt Panel D Block & Ups Panel Kidney Block Alongwith Replacement Of 01 Nos. Acb In Old Lt Panel, A Block Including Rewiring With Replacement Of Electrical Fixtures In Lt Canteen,Nehru Hospital, Pgimer, Chandigarh

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 15-Oct-2026 The item No. 30 of the BOQ may be read and considered Technical Bid 20-Oct-2026
2 15-Oct-2026 Extended for more participation Date 20-Oct-2026

BOQ

Name of Work:- Shifting of main LT panel D Block & UPS Panel Kidney Block alongwith Replacement of 01 Nos. ACB in old LT Panel, A Block including Rewiring with replacement of electrical fixtures in LT canteen,Nehru Hospital, PGIMER, Chandigarh
Sl. No. Item Description
1Part-A: Shifting of main LT panel D Block & UPS Panel Kidney Block
2Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required
33½ X 185 sq. mm
43½ X 400 sq. mm
5Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following sizes in masonry open duct as required.
6Above 95 sq. mm and upto 185 sq. mm
7Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
8Above 35 sq. mm and upto 95 sq. mm (clamped with 25/3mm MS flat clamp)
9Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
10Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
11Above 35 sq. mm and upto 95 sq. mm (clamped with 25/3mm MS flat clamp)
12Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
13Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
14Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
15300 mm width X 50 mm depth X 1.6 mm thickness
16Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
17300 mm width X 50 mm depth X 1.6 mm thickness
18Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
19Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
20Supplying and making end termination with brass compression gland and Aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE Aluminium conductor cable of 1.1 kV grade as required.
213.5x50 sqmm (35mm)
223.5x120 sqmm (45mm)
233.5x185 sqmm (57mm)
243.5x400 sqmm (82mm)
25NS ITEMS
26Removal of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.
27Above 95 sq. mm and upto 185 sq. mm
28LT Panel
29Supplying installation, testing & commissioning of suitable size modular cubicle type LT panel, min. IP54, outdoor type with canopy structure on top, suitable for 415 V, 3Phase, 4 Wire 50 Hz AC supply , compartmentalized made from CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland plates, complete with 7 tank process for powder coating in approved shade, Panel shall be minimum Form 3B. Panel shall be Tested for IK 10, Internal Arc protection and Fault Level of Minimum 50 A for 1 sec as per IS/IEC 61439. Panel Busbar rating shall be as per test report of OEM as per IS/IEC 61439 ( same shall be verified on drawings and during inspection). All switchgear used shall have Fault level Ics =Icw=100 %Ics .
30Panel should be designed such that it has a curved MS shed at top for external use. Cable entry from botton after construction of suitable base. Bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 2.5 sq. mm. PVC insulated copper conductor cable, providing with following switch gears :-
31Incomer 1&2
32MCCB FP 630A, 36KA, Microprocessor based with O/L S/C protection - 2 Nos.
33Spreader set
34Extended rotary handle
35Undervoltage release
36Mechanical lock
37Digital ammeter with ASS
38Digital voltmeter with VSS
39R,Y Phase indicating lamp 240V AC
40B Phase indicating lamp 240V AC
416A. SP Control MCB
42CT`s 630/5A. CL-1 15VA Resin cast/nylon casing
43CT Shorting link
44Neutral link
45BUS COUPLER
46MCCB FP 400A, 36KA, Microprocessor based with O/L & S/C Protection - 1 Nos
47Spreader set
48Extended rotary handle
49Mechanical Interlock
50OUTGOING SECTION -1
51For MS LV1 LEFT SIDE TO MS LV5 LEFT SIDE
52MCCB TP 250A, 36KA, Thermomagetic based With O/L, & S/C Protection - 5Nos.
53Spreader set
54Extended rotary handle
55For VTPN1, VTPN2 PROCUREMENT BRANCH
56MCCB TP 200A, 36KA, Thermomagetic based With O/L, & S/C Protection - 2Nos.
57Spreader set
58Extended rotary handle
59For VTPN3 CNO OFFICE SIDE
60MCCB TP 160A, 36KA, Thermomagetic based With O/L, & S/C Protection - 1 Nos.
61Spreader set
62Extended rotary handle
63MCCB 125A
64MCCB TP 125A, 36KA, Thermomagetic based With O/L, & S/C Protection - 2 Nos.
65Spreader set
66Extended rotary handle
67OUTGOING SECTION -2
68For DATA CENTER
69MCCB TP 400A, 36KA. Microprocessor based with O/L & S/C Protection - 1 Nos.
70Spreader set
71Extended rotary handle
72MS LV1 RIGHT SIDE TO MS LV5 RIGHT SIDE
73MCCB TP 250A, 36KA, Thermomagetic based With O/L, & S/C Protection - 5 Nos.
74Spreader set
75Extended rotary handle
76PVT GRANT CELL
77MCCB TP 160A, 36KA, Thermomagetic based With O/L, & S/C Protection - 1 Nos.
78Spreader set
79Extended rotary handle
80AHU PANEL SUPPLY
81MCCB TP 160A, 36KA, Thermomagetic based With O/L, & S/C Protection - 1 Nos.
82Spreader set
83Extended rotary handle
84MCCB 125A.
85MCCB TP 125A, 36KA, Thermomagetic based With O/L, & S/C Protection - 2 Nos.
86Spreader set
87Extended rotary handle
88ENCLOSURE & ACCESSORIES
89FABRICATION IN 2.0/1.6MM CRCA SHEET POWDER COATING IN SIEMENS GRAY SHADE, CABLE ENTRY WILL BE TOP & BOTTOM SUITABLE FOR CABLE,LOCK, RUBBER GASKET, HARDWARE ETC.
90BUS BAR & HARDWARE
91600A. TPN ALUMIMIUM MAIN BUS BAR,LOAD WISE SUB FEEDER BUS BAR COLOUR COATED HEAT SHRINK BUS BAR SLEAVE NUT-BOLT,WASHER,HARDWARE ETC.
92WIRING & ACCESSORIES
93POWER & CONTROL WIRING WILL BE (ISI 1100V) FLAME RETARDENT LOW SMOKE PVC SINGLE CORE COPPER WIRE,COPPER LUGGS, PVC SLEEVE, FERRULES, NUMBERS, HARDWARE & LABOUR ETC.
94Shifting and reinstallation of UPS changeover assembly from existing UPS room to appropriate location after opening connections and mounting on a wall surface after drilling and fixing with bolts/fastners etc as required and providing earthing connection with full satisfaction of Engineer in charge. Testing and commsioning of this assembly after connecting cables needs to be done before handover to EIC.
95Supply of copper conductor XLPE insulated armoured and served cable to be laid as per requirement at the site of work including all petty material required to complete the job. upto entire satisfaction of the Engineer-in-charge.
9650sqmm , 3.5 core cable
97120 sqmm, 3.5 core cable
98185 sqmm, 3.5 core cable
99400 sqmm, 3.5 core cable
100Part-B: Replacement of 01 Nos. ACB in old LT Panel, A Block
101Supply,installation in existing panel, testing and commissioning of 800A , EDO type, MP based ACB having Icu=Ics=Icw(1sec)= 50KA and conforming to IS/IEC 60947-2&3 standard. Job inludes installation and fabrication if any, in existing LT panel with all materials and spares required with full satisfaction of Engineer in charge.
102800A 4P ACB having Mircroprocessor based releases for O/L, S/C & E/F. SITC of Indicator RYB, On,Off,trip, current transformer, CT shorting Terminals, MCB , Neutral Link, Auxiliary Contractor, Terminal Blocks, Wiring for feeder, Busbar Link for ,etc as required at site.
103ACB shall have one set of the following items:
104Intelligent multi function digital meter Datalog (8 MB),Analog I/O, digital I/O variants available, Meter with Ethernet port available Parameters: V, A, F, kW, KVA, kVAr, kWh, kVAh, kVArh, PF, Runhr, Onhr, Interupts,Phase angle, THD, Neutral current, Max Demand (with RTC), Events (high-low) with time stamp,Individual Harmonics upto 31st.
1051 Set Indication Lamps, LED type, for RYB with2 Amp control MCB.& breaker 'ON', 'OFF', 'TRIP' & spring charged lamps with 2 Amp MCB for controlling alonwith SITC of TNC switch.
106De-termination and dismantling of following material from existing panel including transportation from PGI for rebate
107Old ACB
108Part-C: Rewiring with replacement of electrical fixtures in LT canteen,Nehru Hospital
109Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
110Group C
111Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
112Supplying and drawing following sizes of FRLS PVC insulated copper conductor single core cable in the existing surface / recessed steel / PVC conduit as required.
1133x1.5mm2
1143x4mm2
115Supplying and fixing following size / modules, GI box along with modular base and cover plate for modular switches in recess etc. as reqd.
1166 module(200mmx75mm)
117Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
1185/6 A switch
11915/16 A switch
1203 pin 5/6 A socket outlet
1216 pin 15/16 A socket outlet
122Supplying and fixing following way, horizontal type three phase and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
1236 way (4 + 18), Double door
124Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
125Single pole
126Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep
127Extra for fixing the alumiium louvers/ shutters complete with frame for a exhaust fan of all sizes.
128Supplying, installation,testing and commissioning of Passive Infrared(PIR) technology based occupancy sensor having high preformance, non regulating programmable type, suitable for connected load upto 10Amp , for mounting height up to 3 mtr and for 5 m diameter coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required.
129Supplying, installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round/square/ Rectangular) COB type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10%, P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard.
13018 watt
131Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
132Upto 35 sq. mm (clamped with 1mm thick saddle)
133Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size oncable tray as required.
134Upto 35 sq. mm (clamped with 1mm thick saddle)
135Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
1364 X 16 sq. mm (28mm)
137Supply of 380 mm Exhaust Fan heavy duty 900 rpm inlcuding Al louvers and all accessories to complete the job making the connections etc as require at site upto the complete satisfaction of Engineer Incharge.
138Supply Installation, testing and commissioning of Led fixture 1200mmX300mm (approx) 36W Surface Mounted Led luminaire having minimum system lumen efficacy of 120lm/W with P.F.>0.95 with THD<10% ,CRI>80,CCT = 5700K, efficency of driver >85% and shall have under voltage and over voltage protection, Glare index shall be <23 complete with all accessories, and mounting of light in ceiling as per the satisafaction of the Engineer Incharge.
139Supply of copper conductor XLPE insulated armoured and served cable to be laid as per requirement at the site of work including all petty material required to complete the job. upto entire satisfaction of the Engineer-in-charge.
14016 sqmm, 4 core cable
141Supplying and fixing following rating, TPN, 415 volts,MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required.
14263 amps TPN
143Dismentling of existing light fixtures, switch/sockets, celing fans, light point etc complete in all respect.
144Rebate of the old Dismentled material i.e. Old Panel, old light fixtures, wiring points, switch sockets, etc complete in all respect including removal of the same prom PGI premises.The serviceable material like MCCBs, lights/Ceiling fan shall be retained by the department. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57847350
AUTHORITY Boards / Undertakings / PSU
TENDER VALUE 31.41 Lakhs
LAST DATE 20-10-2026
Authority
Authority Name Post Graduate Institute Of Medical Education And Research
Work Description Tender for Shifting Of Main Lt Panel D Block & Ups Panel Kidney Block Alongwith Replacement Of 01 Nos. Acb In Old Lt Panel, A Block Including Rewiring With Replacement Of Electrical Fixtures In Lt Canteen,Nehru Hospital, Pgimer, Chandigarh
Basic Detail
Tender No PGI/Engg./Elect./2026-27/32
Bidding Type Tender
Location
City Chandigarh
State Chandigarh
Key Dates
Publish Date 15 Oct 2026
Submission Date 20 Oct 2026
Open Date 01 Jan 0001
Finance
Tender Value 31.41 Lakhs
Tender Fee Ref. Documents
EMD 62840
Exemption Available
Document List
3a4bcfb5-e11a-43a9-9fb7-52d73d16cafb.html
BOQ_975999.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 15, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 20, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 2 days
Oct 20, 2026
18:00 IST

Corrigendum-2 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 2 days
Oct 20, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 2 days

Tender Documents

Download All (ZIP) ↓
html

3a4bcfb5-e11a-43a9-9fb7-52d73d16cafb.html

xls

BOQ_975999.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender