Housing Urban and Rular Development Government Departments Closing in 2 days TDR #57830962

Tender For B.O.Q For Providing Of Internal Electrification Facility To Mrf Site At Solid Waste Management Plant Mc Awantipora

Issued by Government Departments · Pulwama, Jammu and Kashmir
Tender Value
13.19 Lakhs
Estimated cost
Bid Submission
20 Oct 2026
2 days left
EMD
26391
Bank guarantee accepted
Document Fee
600
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Pulwama → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for B.O.Q For Providing Of Internal Electrification Facility To Mrf Site At Solid Waste Management Plant Mc Awantipora

BOQ

Name of Work:- B.O.Q for Providing of internal electrification facility to MRF site at SWM Plant MC Awantipora
Sl. No. Item Description
1Wiring for light point/ fan point/ exhaust fan point/ call bell point with 2X 1.5 sq.mm FRLS PVC insulated copper conductor ( Havell/Polycab/ paraflex/ Anchor/ APAR/eq. standard make as desired by engineer incharge ) single core cable in surface / recessed medium class PVC conduit, (cutting the wall and making good the same in case of recessed conduit including painting as required with cement plaster, wall putty , paint, complete)with modular switch ( Anchor roma plus/Legrand Mylinc /SSK NV/schneider Livia /ABB Tvisha make.), modular plate,suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
2Wiring for light/ power plug with 2X4 sq. mm + 1X 4 sq. mm earth wire , FRLS PVC insulated copper conductor ( Havell/Polycab/ paraflex/Anchor/ APAR/equivalent as directed by engineer incharge.) single core cable in surface/recessed medium class PVC conduit.(cutting the wall and making good the same in case of recessed conduit including painting as required with cement plaster, wall putty , paint, complete)
3Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch,modular plate, suitable GI box , connections etc. as required. Modular Switch & Socket:- ( Anchor roma plus/Legrand Mylinc /SSK NV/schneider Leiva /ABB Tvisha make make.)
4Wiring for lighting circuits/ 6- 10 amp power plugwith 2X2.5 sq. mm FRLS PVC insulated copper conductor ( Havell/Polycab/ Fenolex/Anchor/ equivalent as directed by engineer incharge.) single core cable in surface/recessed medium class PVC conduit (cutting the wall and making good the same in case of recessed conduit including painting as required with cement plaster, wall putty , paint, complete) alongwith 1 No. 2.5 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
5Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). Modular Switch & Socket:- ( Anchor roma plus/Legrand Mylinc /SSK NV/schneider Livia /ABB Tvisha make.)
6Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
7Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor ( Havell/Polycab/ paraflex/ Anchor/ APAR/equivalent as directed by engineer incharge.), single core cable in surface/ recessed medium class PVC conduit as required.(cutting the wall and making good the same in case of recessed conduit including painting as required with cement plaster, wall putty , paint, complete)
8(a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
9(a ) 2 X6 sq. mm + 1 X 6 sq. mm earth wire
10( b )2 X 10 sq. mm + 1 X 6 sq. mm earth wire
11( b )4 X 10 sq. mm + 2 X 6 sq. mm earth wire
12(f) 4 X 16 sq. mm + 2 X 6 sq. mm earth wire
13Supplying and fixing of following sizes of medium class PVC conduit( Anchor/ Ravindra/ Eq. make)along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required, with cement plaster, wall putty , paint, complete
14Providing and fixing of 6-16mm Cu thimbles duly cramped at cable ends.
15Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
16Supply installation testing and commissioning of Indicator of Anchor roma plus/Legrand Mylinc /SSK NV/schneider Livia /Crabtree athena make.)
17Sub Head-2 - Fixtures and Fittings
18Supply installation testing and commissioning of 18 W + LED Surface/recess, square or round Mounted light luminary fitting shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium body and Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70, seperate driver, heat sink, earthing provision.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV. Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/ government of India. The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years ,which includes replacement of fixtures of Wipro/Havell/ Helonix make / sample to be approved before installation..
19Supply installation testing and comm. of flood light ( warm, white ), Epoxy powder coated die-cast aluminium housing (LM24) with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant. PG9 gland is used for cable entry and provision for loopin-loopout class 1, IP66, IK 07, , with high power LED's as light source with Built-In Potted IP67 electronic LED driver with APFC,lower THD, toughned glass and secondary lens,Open Circuit Protection, Over Voltage Protection, Surge Voltage Protection upto 10kV With Built In SPD & other safety test as per IS 15885 Part-2/Sec 13, IEC60598-1. Preferred make: Philips/ Havell /Wipro/Crompton make.
2050 WATT
21100 WATT
22S/F testing and comm. Of 20 Watt 4 ft. wall mounted LED batten with powdered coated aluminum housing & integrated electronic driver with THD<10%.( commercial series) Philips / Trulux/ wipro/ Havell make/ eq. standard make as directed by engineer incharge.
23Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 3 star rated, ceiling fan ( Atomberg/USHA/Orient /Bajaj/Crompton/equivalent make as directed by engineer incharge,) with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS: 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise-75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
24Supply and fixing of 6 amp/250 V A.C fan dimmer step type 2 module with cover plate Anchor roma plus/Legrand Mylinc /ABB Tivsha/schneider Livia /Havell Coral make.
25Supply installation testing and comm. Of 200mm -250mm sweep exhaust fan Shutter type of havell /USHA/Crompton/equivalent make as directed by engineer incharge, including making of space in wall/ window as per site requirement and necessary connections.
26Supply installation testing and comm. Of 400mm sweep exhaust fan Heavy duty industrial type steel body of havell /USHA/Crompton/equivalent make as directed by engineer incharge, including making of space in wall/ window as per site requirement and necessary connections.
27Supplying and fixing following way, Triple pole and neutral, sheet steel, MCB distribution board,( legrand/ Shinider/Hager/ABB make) 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar,din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator)
286 way (4 + 24), Double door TPN
2910 way, Double door ( 8+2) SPN
30S/F testing and comm. Of MCBs 10 K of the below mentioned capacities in sub main controls legrand C curve/ Schinider/ ABB ./L&T equivalent make as directed by engineer incharge.
31a) 6-32 Amp SP MCB
32b) 40-63amp DP MCB
33c) 40-63amp TPN MCB
34Supplying and fixing 20 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 20 amps \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
35Providing of Chemical earthing as per IS standards by way of digging 10' deep pit then embedding 3 meter G.I Earthing electrode , 80mm dia. connecting the plate with main control board by8- 10 SWG G.I wire with 1/2\\" dia. Full thread brass nut and bolt and washers. Refilling of pit with chemical compound.
36S/L , testing and commissioning of PVC XLPE insulated alluminium armoured cable 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments.Havell/Eq. standard make as directed by engineer incharge and making end termination with brass compression gland and aluminium lugs of required size.
37a)95 sq.mm 3.5 core
38b)50 sq.mm 3.5 core
39b)16 sq.mm 4 core
40Earth work excavation for cable trench, 2 ft deep with an average breadth of 1.5ft and refilling of trench with excavated earth after laying of cable and ramming it properly excluding cost of cable.
41Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting,jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
4290 mm dia (OD-90 mm & ID-76 mm nominal)
43Supplying,Installation,Testing and Commissioning of CO2 Type Fire Extinguisher 4.5 Kg. Capacity ISI Mark(IS:15683)suitable for 'B' and 'C' class fires - inflammable liquids, gaseous fires like L.P.G. and acetylene, and electrical. Ceasefire/ equivalent make as desired by engineer incharge.
44SERVO STABILISER : Supply, installation, testing, and commissioning of three phase 10 kVA servo-controlled automatic voltage stabilizer with a digital microprocessor-based controller, conforming to IS 9815. The stabilizer shall be copper wound (EC grade), oil cooled with minimum 100 litres of insulating oil as per IS 335:2018 (UN type), and of the unbalanced type with a bypass arrangement. It shall operate within an input voltage range of 240–485 V (P-P) and 138.5–380 V (P-N), and provide a stable output voltage of 415 V AC ±1%. The unit shall have an overload capacity of up to 120% and operate at a frequency of 50 Hz with deviation as per IS. It shall include all necessary protection mechanisms as detailed in the technical specifications (Annexure A) and be supplied along with appropriately rated cables on both input and output sides. Make: Hindustan Power Products, PureVolt New Delhi, Jindal electric Faridabad, Servocon, Electric Field, Sen & Pandit Systems, Moto line Electronics, Chinar, Cosco , Power Bank (AMPLE) India, Baid Power Services Pvt ltd. Automatic Electric (AE) ,Fiji Electronics Pvt Ltd
45a) 0-500V moving iron type voltmeter with selector switch.
46b) A three phase change over switch to read voltage on incoming and output side
47c) indicating lights 6 No two numbers for each of the motorised units, one for lower limit and other for higher limit.
48d) six push button control for movement operation of three motorised dimmer units two for each unit i.e one for raise operation and one for lower operation under the conditions of adjustment of auto/mannual selector switch (DPDT)
49e) Single phase Preventer ( contactor Switch of required rating) Legrand make.
50f) six potential meter resistance with lock meter two for each phase control, one for sensitivity and other for level control.
51g) two sets of indication lamps three numbers each to indicate output and input indication
52h) 20 % over load bearing capacity for one hour.
53Design, Fabrication, Supplying, Installation, Testing and Commissioning of following panel , duly manufactured from CPRI approved manufacturer, made out of 2mm thick M.S. sheet steel , floor/wall mounted, vermin and dust proof, indoor type with suitable size of angle iron legs for grouting in the ground, with lockable type hinged doors, duly painted with provision for fixing of following switch gears, , Aluminium Bus Bar of various ratings after taking Derating factor into account, and other allied accessories etc. as required.( As per approved design,size may vary as per site requirement)
54Providing and fixing of following protection equipments and other allied accessories including connections, inter connections, with suitable size of PVC insulated copper conductor cable including earthing etc. as required.
55Normal INCOMING:
56(a) 160 amp TPN MCCB 36 K including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB make.
57b) 4 No. of Aluminium Bus Bar of 200 Amp.
58c)Digital meters and phase indicators -1 set.
59d) Off load Change over switch 100 Amp for generator.Front operated.
60e) 4 No. of Aluminium Bus Bar of 200 Amp.
61c)Digital meters and phase indicators -1 set.
62Inverter Incommer
63(a) 63 amp DP MCB 16 K including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB make.
64(b) 100 Amp 2 strip bus bar
65c)Digital meters and phase indicators -1 set.
66OUTGOING:
67c) 40-63amp DP MCB
68c) 40-63amp TPN MCB
69c) space for 16 way MCB's
70Supply and errection of 9.0 mt long(410SP-33) steel tubular poles, sawaged type conforming to IS-2713, (Part-II) ,planting depth 1.5 mt .Pole shall have 2 no bolts welded at a distance of 3 mt. from bottom of pole and suitable holes shall be drilled in pole for service connection and lum. earth wires.
71Supply and fixing of four arm bracket ( square type 2.5'x2.5') for mounting the luminaire on the top of the pole fabricated out of 75 mm diameter M.S. pipe welded and supported with a triangular MS gasset plate 6mm thick , with a provision of cast iron cap.
72Supply and installation of Spiral Earthing through 10 swg GI wire and GI pipe 2ft. after driving in ground up to a depth of 3' in the ground from the base of the pole.
73Providing of service connection and earthings to luminaire from the junction box in 1.5 mm PVC insulated, multicolour copper wire .
74Painting of pole with one coat of red oxide and two coats of Al. paint.
75Erection of metallic pole 8.0 metre and upto 10.0 metre in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation , refilling and concrete jaketing above ground etc. as required.
76Supply, installation , testing and commissioning of LED based Flood light, housing made up of pressure die cast aluminum Alloy with effective thermal management,sturdiness and embossed brand name/logo name of manufacturer. The fixture should have a minimum system efficacy of greater than 120 lumen/Watt and a minimum system lumen output of 18000 lumens and maximum system wattage of 150 Watts.The fixture shall have a CRI of minimum 70, SDCM<5. The fixture shall be designed for a system life of 50,000 hours @70% lumen maintenance. Ingress Protection of IP66 (lamp and gear Compartment) and Mechanical Impact Resistance Rating of IK >=07 with toughened glass cover.The fixture driver should have an operating voltage range of 140-270 V, inner surge protection of >=4KV, PF >0.95 and THD<10% at full load. Driver should cut off at high voltage of 320volt for safety. The fixture should comply with the parameters as per IS10322. The LED driver should comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics. Manufacturer shall have inhouse lab approved by NABL. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Philips/ Havell ( Jeta Aris)/ Wipro/ Eq, standard make ( sample to be approved before installation)
77S/L , testing and commissioning of, XLPE Insulated, PVC Alluminium un-armoured cable 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments.Havell/Eq. standard make as directed by engineer incharge and making end termination with brass compression gland and aluminium lugs of required size.
78a) 16 sq.mm 2 core
79Supply installation testing and comm.of invertor battery 180 AH/12 V Exide invatubular/ eq. standard make as directed by engineer incharge.
80Supply installation testing and commissioning of Sine Wave Inverter Capacity 1400VA+ ( Plus), supporting 2 batteries,24 Month Warranty Safe for sensitive appliances with Sine wave out-put, Auto over-load handling capacity Installation and maintenance friendly Offers high quality and reliable power back-up solution for office and homes ,MCB for protection from Input mains,Bypass switch for supplying output directly from grid in case of Home UPS fault.Noiseless Operations with the help of low harmonic distortion, Intuitive Display to easily understand status of mains availability, battery status, etc.Comprehensive protection against short-circuit, reverse polarity, battery over-charge, deep-discharge etc.Adaptive Battery charging control system technology (ABCC) ensures faster battery charging and enhances battery life by around 70%.Supports a wide battery range, i.e. Flat Plate, Tubular & VRLA (SMF).praffered make Luminous/ Microtek/Exide.the job also includes 1 No. trolley for housing 2 No battries and inverter. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57830962
AUTHORITY Government Departments
TENDER VALUE 13.19 Lakhs
LAST DATE 20-10-2026
Authority
Authority Name Public Works Department
Work Description Tender for B.O.Q For Providing Of Internal Electrification Facility To Mrf Site At Solid Waste Management Plant Mc Awantipora
Basic Detail
Tender No NIT No.Fresh/181/2026-27 Dt 01/10/2026
Bidding Type Tender
Location
City Pulwama
State Jammu and Kashmir
Key Dates
Publish Date 01 Oct 2026
Submission Date 20 Oct 2026
Open Date 21 Oct 2026
Finance
Tender Value 13.19 Lakhs
Tender Fee 600
EMD 26391
Exemption Not Available
Document List
8baad82d-b6de-484c-aed6-2e9b5f2c3a63.html
BOQ_1105475.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 01, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 20, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 2 days
Oct 21, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 3 days

Tender Documents

Download All (ZIP) ↓
html

8baad82d-b6de-484c-aed6-2e9b5f2c3a63.html

xls

BOQ_1105475.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender