Tender For Construction Of Restrooms For Athletes At Amone Canacona (Electrical Work).
Tender Overview
Project Description
Tender for Construction Of Restrooms For Athletes At Amone Canacona (Electrical Work).
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 21-Oct-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 26-Oct-2026 |
| 2 | 14-Oct-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 21-Oct-2026 |
| 3 | 26-Oct-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 29-Oct-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor single core cable in the independent surface PVC conduit ( medium)of appropriate size as required. (b) 2 x 2.5 sq.mm + 1 x 2.5 sq.mm earthwire (20mm Conduit) |
| 2 | (c) 2 x 4 sq.mm + 1 x 4 sq.mm earthwire (20mm Conduit) |
| 3 | (j) 4 x 6 sq.mm + 2 x 6 sq.mm earthwire (32mm Conduit) |
| 4 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface PVC conduit( medium) with modular switch, modular plates, suitable size modular GI box of specified Category and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. (a) Group A -- with Cat A Modular Accessories |
| 5 | Wiring for group controlled light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface PVC conduit( medium) and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 6 | Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required Cat A |
| 7 | Supplying and fixing suitable size modular GI box with modular plate and cover in front on surface or in recess including providing and fixing 3 pin 5/6 A modular socket outlet and 5/ 6 A modular switch connection painting etc. as required. Cat A |
| 8 | Supplying and fixing suitable size modular GI box with modular plate and cover in front on surface or in recess including providing and fixing 6 pin 15/16 A and 5/6 A modular socket outlet modular socket outlet and 15/16 A modular switch connection painting etc. as required. Cat A |
| 9 | Supplying and fixing following modular switch/ socket on the existing modular plate and switch box including connections but excluding modular plate etc. as required (a) 5/6 A switch Cat A |
| 10 | (c) 15/16 A switch Cat A |
| 11 | (d) 3 pin 5/6 A socket outlet Cat A |
| 12 | (e) 6 pin 15/16 A socket outlet Cat A |
| 13 | Supplying and fixing following size modular GI box alongwith modular base and cover plate for modulator switches in recess etc. as required (b) 4 Module ( 125 mm x 7 mm) Cat A |
| 14 | (c) 6 Module (200mm x 75 mm) Cat A |
| 15 | Supply and erecting of 56 inch (1400mm sweep) ceiling fan, double ball bearing type, , complete with all accessories. Cat A |
| 16 | Supply and erecting of 9 inch (225 mm sweep) exhaust fan with double ball bearings, 1400 rpm, complete with all accessories.. |
| 17 | Supplying and erecting LED square / circular Max. 18 W down lighter /Panel Light having pressure die-cast aluminium housing, polystyrene diffuserhaving system lumens output of Min. 2000 Lumens, min. efficacy of 110lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5kV, Life class of 50,000 Hrs at L70B0 including driver, having mountingarrangement with board for surface type or spring loaded mounting clipscomplete with minimum 2 years warranty of make Philips/Leksa/ Wipro/Havells |
| 18 | Supplying and erecting anodized aluminium light LED fitting (4 feet) Max.22W with high transitivity diffuser with system lumens output of Min.2200lumens , min. efficacy of 100 lumen/W, CRI>80, CCT upto 6000K, Beam Angleof 110 deg., Ripple<5%, THD<20%, p.f. >0.95, operating range of 200-270V,surge protection of 2 kV, Life class of 50,000 Hrs at L70B50 including driver with end caps on provided PVC Block/wooded board with minimum 2 years warranty of make Philips/Leksa/ Wipro/Havells |
| 19 | Supplying and erecting exhaust fan heavy duty 230 V A.C. 50 cycles 450 mm. 1400 RPM complete erected in position |
| 20 | Supplying and fixing following way TPN sheet steel, double door, Horizontal type MCB distribution board 415 V on surface/ recess complete with tinned copper busbar neutral busbar earth bar dinnbar detachable gland plate interconnections phosphotized and powder painted including earthing etc. as required ( but without MCB/RCCB/Isolator) 4 way (8+12), double door, Horizontal type Cat A |
| 21 | Supplying and fixing 6 A to 32 A, C series MCB suitable for lighting and other loads of following poles in the existing MCB DB complete with connections testing and commissioning etc as required. SP, Cat A |
| 22 | TPN, Cat A |
| 23 | Earthing with GI earth pipe 2 mts long 40 mm dia medium class with ISI mark, of approved brands including accessories and providing masonry enclosure with CI/RCC cover having locking /Lifting arrangement and watering pipe etc. (but without charcoal or coke and salt) as required as per the Earthing Drawing provided by the Engineer-Incharge.The scope of work includes the following: a) Excavation of pit of size not less than 1.0x1.0x 2.0 mtrs(min) and disposal of excavated soil. b) Class B GI pipe, 40mm diameter as per specifications. c) Charcoal/salt as per specs ( paid seperately). d) Refilling the pit of size not less than 1.0x1.0x 2.0 mtrs(min) with soft black soil of minimum resistivity i/c transportation. e)Masonary chamber with proper foundation, cover plate and locking arrangement. f) Testing of earth value with earth megger and certifications of its value. Aluminium tag with embossed earthing value to be attached to the pipe. g)watering arrangement(plumbing will be paid seperately). (a) In Soily strata |
| 24 | Extra for using salt and charcoal for pipe earth electrode as required( 65 Kgs of Charcoal and 5 Kgs of Salt). |
| 25 | Supplying and laying 25 mm x 5 mm GI strip at 0.5 m below ground as strip earth electrode including soldering etc. as required |
| 26 | Supply of 3 1/2 core armoured PVC/XLPE insulated, PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS:1554(Part I) ,IS:7098(Part I) with latest amendments of following size 3 1/2 Core 70 sq.mm |
| 27 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 120 sq.mm direct in ground including excavation in the form of a trench as per Cable Trench Drawing provided by the Engineer-Incharge,sand cushioning with screened sand bed of 20mm thick , protective covering with bricks placed breadth-wise on top of cable all over the run( the brick protection shall cover the cable and project atleast 5 cms over the sides of the cable) and backfilling the excavated earth without stones or hard material and making the surface proper with 15 cm crown on the top complete as required. In soily strata |
| 28 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size not exceeding 75 sq.mm on surface, etc. complete as required |
| 29 | Supplying and making cable end terminations with brass compression gland and copper lugs for folowing sizes of 3 1/2 Core PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade, complete as required. 3 1/2 x 70 Sq. mm. |
| 30 | Supplying and fixing 20 A 240 V SPN industrial type socket outlet with 2 pole and earth metal enclosed plug top alon with 20 A, C series SP MCB in sheet steel enclosure in surface or in recess with chained metal cover for the socket outlet and complete with connections testing and commissioning etc. as required\\" |
| 31 | Supply and erecting meter box suitable for three phase energy meter and incoming SP/DP MCB, fabricated out of 16 SWG sheet steel, powder coated, complete as required and conforming to the requirements of Goa Electricity Department. |
| 32 | Supply, installation, testing and commissioning of electronic type three phase energy meter (KWh), 4 wire, ISI marked, in polycarbonate or sgheet steel body ( base mounting type) with counter display/LCD display, with ELT, in Class 1.0, 50 Hz, 240 V. AC duly tested by MRT along with Test Certificates, complete as required of following capacity of make L & T only. |
| 33 | Supplying, erecting, testing & commisioning bus bar chamber triple pole with neutral with four aluminium bars, 500V 200A having 25mm ( width) X 5 mm(thickness), with 99.9 % aluminium purity as per E91E grade & current density 0.8 A per sq mm compliance to IS 5082 and enclosure fabricated with 16SWG CRCA sheet and epoxy paint, with suitable number of ways and withSMC/DMC Insulators and accessories of suitable rating and two nos of separateearthing terminals complete |
| 34 | Providing and fixing following capacity TPN disconnector fuse switch unit in SS enclosure without HRC fuses including drilling holes in cubicle panel making connections etc as required. 100 A TPN, CAT A |
| 35 | Supply of 3 core unarmoured PVC/XLPE insulated, PVC sheathed copper conductor cable of 1.1 KV grade with ISI mark conforming to IS:1554(Part I) ,IS:7098(Part I) with latest amendments of following size. 3 Core 2.5 sq.mm |
| 36 | Supplying and erecting integrated LED flood light fitting Max. 150W IP65 & IK07 class having pressure die-cast aluminium housing, having system lumens output of Min. 18600 Lumens, min. efficacy of 120 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.90, operating range of 140-270V, inbuilt surge protection of 4 kV, Life class of 50,000 Hrs at L70B50 including driver with U shaped bracket with minimum 2 Years warranty of make Leksa/Wipro/Philips Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-3 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 2 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 2 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 3 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender