Tender For Maintenance Of Electrical Installation In Non-Residential Building At Chandigarh. (Replacement Of Defective Electrical Accessories In Hockey Stadium Sector-42, Chandigarh In Regarding Organizing The Chandigarh Hockey League For Men From 23
Tender Overview
Project Description
Tender for Maintenance Of Electrical Installation In Non-Residential Building At Chandigarh. (Replacement Of Defective Electrical Accessories In Hockey Stadium Sector-42, Chandigarh In Regarding Organizing The Chandigarh Hockey League For Men From 23.10.2026 To 02.11.2026 At Hockey Stadium, Sector-42, Chandigarh.)
BOQ
| Sl. No. | Item Description |
| 1 | 1.15 Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. |
| 2 | Group-C |
| 3 | DSR item No. 1.17 Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 4 | 3 x 1.5 sq. mm |
| 5 | 3 x 2.5 sq. mm |
| 6 | DSR item No. 1.21 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 7 | 25 mm |
| 8 | DSR 1.23 Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. |
| 9 | 5/6 A switch |
| 10 | 15/16 amps switch |
| 11 | 3 Pin 5/6 A. socket outlet |
| 12 | 6 Pin 15/16 A. socket outlet |
| 13 | DSR item No.1.29 Supplying and fixing metal box of 150mm X 75mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 A socket outlet and 5/6 A piano type switch, connections, painting etc. as required. |
| 14 | DSR item No.1.30 Supplying and fixing metal box of 180 mm X 100 mm X 60 mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 A & 15/16 A socket outlet and 15/16 A piano type switch, connections, painting etc. as required. |
| 15 | DSR Item No.2.5 Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required (Note: Vertical type MCB TPDB is normally used where 3 phase outlets are required). |
| 16 | 8 way (4 + 24), Double door |
| 17 | DSR item No. 2.10 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 18 | Single pole |
| 19 | Double Pole |
| 20 | Triple Pole |
| 21 | Triple Pole & Neutral |
| 22 | S/E of 3mm thick white glazed Bakelite sheet on the existing M.S box. The job includes the cost of sheets and making holes and cutting charges of switches & sockets. The job includes the cost of all labour & petty material required to complete the job. The Bakelite sheet should be of Superhylam/ Greenlam/ Formica make only. |
| 23 | DSR item No.2.2 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 24 | 100 A,30KA,FPMCCB |
| 25 | DSR item No.8.16 LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt).(Please refer DNIT for complete specification of item no.11) |
| 26 | 250 Watt. |
| 27 | Supply and laying of XLPE insulated PVC sheathed Aluminum conductor armoured cable of 1.1 KV grade as per IS 7098 (Part-I) 1988 (amended up to date) of the following sizes to be laid in existing Trench/Ducts/Cable Tray/ RCC/ HUME/ METAL/ DWC pipe / on surface with the help of MS clamps of suitable size/ as required at site to the entire satisfaction of Engineer-in-Charge. The job includes labour charges of laying the cable and making connections with suitable size aluminum lugs/thimbles etc. The cable shall be of Polycab / Havells / R.R. Kabel/ KEI/ Finolex make only. |
| 28 | 16 sq.mm 4 core in pipe |
| 29 | DSR item No.8.9 LED Batten light (System lumen efficacy ≥105 <120 lm/Watt)..(Please refer DNIT for complete specification of item no.13) |
| 30 | 24- 26 Watt |
| 31 | DSR item No.9.2 Brush Less Direct Current (BLDC) Fan without Remote Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al bodyPower Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req. |
| 32 | 1400mm, service value ≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum) |
| 33 | DSR 5.2 Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 34 | DSR item No.5.12 Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 35 | S/E of cement collar and Jn box at the base of the pole with the detailed specifications(Please refer DNIT for complete specification of item no.17) |
| 36 | Supply & Laying of PVC insulated sheathed aluminium conductor un armored cable 10 mm. sq. 2 core flat with 8 SWG G.I. earth wire on existing surface with suitable clamps / hanger etc. including making connection and petty material etc. as required. The cable should be of Polycab/ Havells/ RR Kabel/ KEI/ Finolex make only. |
| 37 | Supply and Erection of LED Post Top Lantern fittings made of cast aluminium housing with power to be mounted on directly on inbuilt Heat sinks. A UV stabilized PC/PMMA clear diffuser is provided for Glare Free Lighting with high visual comfort to complete with Electronic LED Driver Power supply & related accessories with the following specifications to be installed on existing pole with the help of ladder if required which shall be arranged by the firm at his own cost. (Please refer DNIT for complete specification of item no.19) |
| 38 | Spray Painting of steel shutter/ outdoor type pedestal etc. The rusted steel shutter/ other cover of pedestal etc. shall be given anti rust/ anti grease treatment and then spray painted with one coat of primer and 2 coats of superior quality of red/grey paint as approved by EIC of work. The primer and paint should be of Asian Paint/ Nerolac/ Berger/ Akzo Nobel make only. |
| 39 | Painting of existing street light MS poles of following height/ length at site. The painting job should be done after preparation of surface with the application of sand paper etc and then the pole should be painted with aluminium paint of superior quality in two coats after applying one coat of primer. The job including for all type of labour, material, paint, ladder/ Hydraulic Crane with bucket and T&P as required at site to complete the job. The primer and paint should be of Asian Paint/ Nerolac/ Berger/ Akzo Nobel make only |
| 40 | Street light MS pole 4.5 mtr./5 mtr. Long |
| 41 | Painting of cement collar of street light poles with two coats of snowcem and MS junction box with superior quality of paint to give good look. The work should be carried out after the removal of original defective paint from the cantilever/ MS junction box with the help of sand paper etc. The RCC collar surface should be properly cleaned and a smooth surface should be repaired and then 2 coats of superior quality snowsem paint will be done. This also includes necessary repair to the broken cement collar with cement sand mixture. The snowcem/paint should be of Asian/ JK/ Birla/ Nerolac/ Berger make only. |
| 42 | Repair of existing Cubical Pedestal. The job includes welding and fixing of hinges and locking arrangement. The job including all the labour and petty material required to complete the job to the entire satisfaction of Engineer-in-Charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 3 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 3 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender