Tender For Provn Of Standby Power Supply For Lifts At Gte And Marshall Barrack Married Accns Under Ge(South) Bangalore
Tender Value
34.14 Lakhs
Estimated cost
Bid Submission
22 Oct 2026
18 days left
EMD
68280
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Bengaluru Urban → Karnataka
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provn Of Standby Power Supply For Lifts At Gte And Marshall Barrack Married Accns Under Ge(South) Bangalore
BOQ
| Sl. No. | Item Description |
| 1 | Supply and install commissioning and testing Factory assembled silent Diesel Engine driven generating set along with AMF panel, fully wired alternator AC to give an output of 50 KVA continuously rating at a PF of 0.8 lagging, 415 volts AC 3 phase 4 wire 50 HZ+/- 1% supply, 1500 RPM, confirming to relevent standerd as per CPCB-IV norms including foundation and plinth protection as per OEM recommendation, including extension of exhaust pipe upto outside area with sutaible protection complete all as specified and directed. complete with relay panel and switch gear. The diesel Engine will comprise following :-(a) Air cleaner (b) Exhaust silencer suitable for canopy (c) Expansion bellow(d) lube Oil filter (e) Fuel Filters (f) Radiators with pusher type fan and mounting (g) In-line mono block fuel injection pump(h) Governer and fuel feed pump(j) Flywheel with starer ring and bvell housing suitable for close coupling(k) Electric starter motor as per OEM(l) Micorprocessor based Controller mounted on the Controller Panel (m) Protection system for Low lube oil presssure and High water temprature.(n) 12/24 battery of sutaible for DG set(o) MCCB of sutaible capacityComplete all as specified and as directed by Engr-in-Charge. |
| 2 | All as per Item No 1 above but of DG Set of 40 KVA capacity. |
| 3 | Excavation in trenches in Hard/dense soil not exceeding 1.5 M wide and not exceeding 1.5 M in depth for laying of UG cables and LT Panel board foundation etc and complete all as specified and directed . |
| 4 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cms in any type of soil. |
| 5 | Removing excavated soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 M above the starting point all as directed. |
| 6 | M&L for M & L Sand Cushioning (M sand) in trenches/ducts for protection of UG Cables (below, above and around the UG Cable laid in Trenches) of 23 Cm Spread thickness (8 Cm in depth before laying the Cable and 15 Cm in depth after laying the Cable) and consolidated (punned) upto 180 mm thickness, complete all as specified and as directed. Note : For the purpose of Payment, Punned thickness of Sand Cushioning only shall be measured and paid for.sand cushioning in trenches for bricks of u/g cable with coarse sand laid dry in trenches with uniform thickness. |
| 7 | Supply and lay burnt bricks of sub class 'B' laid dry across in trenches for cable protection all as specified and directed. |
| 8 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 Sqmm x 4 core complete all as specified and directed by Engr-In-Charge. |
| 9 | Supply and fixing in replacement LT Panel board outdoor type fabricated out of 3.15mm thick CRCA Sheet steel factory made vermin proof duly painted with two coat of synthetic enamelled paint over a coat of red oxide primer or powder coated, double door, water proof dust and vermin proof hinged and lockable doors inlcuding rain protection cover on top and complete with interconnections, with copper wires, tapes, opening from both sides with cable entry from bottom, with cable alley and bus bar chamber, bonding to earth and painting, including angle iron frame of size minimum 40x40x6mm having 4 legs 0.60 mtr long including grouting in PCC 1:4:8, to the reqd depth all as specified and directed by Engineer-in-Charge. INCOMING(a) MCCB 100 amps 4 pole 25 KA adjustable thermal and fixed magnetic setting - 01 NoBusbar : - Aluminium busbar 3 phase 4 wire of 200 Amps supported with ebonite insulators -1setOUTGOING(b) MCCB 63 Amps 4 pole 25 KA with adjustable thermal and fixed magnetic setting – 05 Nos(c) Multifuction meter suitable to display voltage, current, frequency, power factor and other relavent parameters for three phase 4 wire 415 Volts System including three nos CTs of appropriate ratio – 01 No(d) LED indicator RYB – 03 Nos |
| 10 | Supply and fixing in replacement LT Panel board outdoor type fabricated out of 3.15mm thick CRCA Sheet steel factory made vermin proof duly painted with two coat of synthetic enamelled paint over a coat of red oxide primer or powder coated, double door, water proof dust and vermin proof hinged and lockable doors inlcuding rain protection cover on top and complete with interconnections, with copper wires, tapes, opening from both sides with cable entry from bottom, with cable alley and bus bar chamber, bonding to earth and painting, including angle iron frame of size minimum 40x40x6mm having 4 legs 0.60 mtr long including grouting in PCC 1:4:8, to the reqd depth all as specified and directed by Engineer-in-Charge. INCOMING(a) MCCB 100 amps 4 pole 25 KA adjustable thermal and fixed magnetic setting - 01 NoBusbar : - Aluminium busbar 3 phase 4 wire of 200 Amps supported with ebonite insulators -1setOUTGOING(b) MCCB 63 Amps 4 pole 25 KA with adjustable thermal and fixed magnetic setting – 04 Nos(c) Multifuction meter suitable to display voltage, current, frequency, power factor and other relavent parameters for three phase 4 wire 415 Volts System including three nos CTs of appropriate ratio – 01 No(d) LED indicator RYB – 03 Nos |
| 11 | M & L earthing complete with GI earth plate Electrode 60 cm x 60 cm x 6 mm thick burried directly in ground (earth plate not less than 2.25 Metre deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to galvanished strip 25 x 4mm as earthing lead means of bolts, nuts check and washers of G I or steel all as shown in electrical plate No. 3 of SSR Pt -I connected to earthing test point all as specified or indicated, including 20 mm dia GI pipe medium grade for watering purpose,necessary excavation, earth work in any type of soil, PCC chamber and RCC cover slab, connecting lead wire from test point to DB complete all as specified and as directed by Engr-In-Charge. |
| 12 | Earthing with earth plate electrode of size 60cm x 60cm x 6mm buried directly in ground vertically at a depth not less than 2.25m below normal ground level with top edge of earth plate at depth not less than 1.5m below normal ground level surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connected to and incl earthing of GI strip 32 x 6mm by means of bolts, nuts, check nuts and washers made of GI and protected by light grade 40mm dia GI pipe connected to main switch board or control board and GI pipe light grade 20mm dia for watering and incl funnel, wire mesh, precast RCC pit cover 40mm thick in cement concrete 1:2:4, type B1 with 8mm dia MS reinforcement at 10cm centre to centre bothways and PCC chamber pit with PCC 1:3:6 type C1 incl excavation and earth work and taking out old u/s eathing material, disposal of surplus soil to a distance not exc 50m all as specified and shown on plate No 3 of SSR Part I 2009. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 01, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 22, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysOct 24, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender