Tender For Renewal And Rewiring Of Electrical Installation, Fans, Ac, Light Fittings And Ups For District Health Office At Nagapttinam In Nagapattinam District.
Tender Value
7.85 Lakhs
Estimated cost
Bid Submission
15 Oct 2026
11 days left
EMD
7850
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Nagapattinam → Tamil Nadu
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Renewal And Rewiring Of Electrical Installation, Fans, Ac, Light Fittings And Ups For District Health Office At Nagapttinam In Nagapattinam District.
BOQ
| Sl. No. | Item Description |
| 1 | Rewiring with 2 x1.5sq.mm PVC insulated single core unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe on wall and ceiling with PVC accessories with Module GI switch box on wall with 6A one way module switch with module front plate with continuous earth wire connection of 1.5sq.mm copper wire with painting of suitable colour for open PVC light point / fan point. (for electronic regulator) (5 points / coil) (Higher End) |
| 2 | Rewiring with 2 x1.5sq.mm PVC insulated single core unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe on wall and ceiling with PVC accessories with Module GI switch box on wall with 6A one way module switch with module front plate with continuous earth wire connection of 1.5sq.mm copper wire with painting of suitable colour for open PVC light point / fan point. (for electronic regulator) (6 points / coil) (Higher End) |
| 3 | Renewal by supply and fixing of 4feet LED 20W fitting with LED 20W tube (Higher End) complete with TW round blocks on wall or ceiling with PVC unsheathed FRLS copper leads from terminals to the fitting. |
| 4 | Renewal by supply and fixing of 4feet LED 20W fitting with LED 20W tube (Higher End) complete with conduit pipe suspension from the ceiling with PVC unsheathed FRLS copper leads from terminals to the fitting with tube. |
| 5 | Renewal by supply and fixing of WT bulk head fitting with guard suitable with 7W / 9W LED bulb. |
| 6 | Renewal by supply and fixing of 1200mm (48\\") sweep AC ceiling fan complete ( Higher end) with 2 module 100W fan step regulator (Higher end) with 600mm down rod with fan clamp with side plates and cross arm of size 450mm. (18\\") |
| 7 | Renewal by supply and fixing of 12mm MS fan hook suitable for AC ceiling fan in Roof concreating. |
| 8 | Renewal by supply and fixing of 300mm (12\\") sweep (light duty) AC exhaust fan complete with necessary wall opening and making good of the wall. |
| 9 | Renewal by supply and fixing of light trap arrangements for 300mm (12\\") sweep (light duty) AC exhaust fan. |
| 10 | Renewal by supply and fixing of 3Nos 6A two module 3pin socket, 3Nos 6A one module switch on suitable module surface mounting box (GI) with module cover plate (plastic) on wall with connections. (Higher End) |
| 11 | Renewal by supply and fixing of 1No 6/16A two module socket, 1No 16A one module switch with module cover plate (plastic) on suitable module concealed box (GI) in flush with wall with connections. (Higher End) |
| 12 | Renewal by supply and run of 2 of 2.5sq.mm PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe on wall and ceiling with continuous earth wire connection of 2.5sq.mm copper wire with painting of suitable colour. |
| 13 | Supply, Erection, testing and commissioning of 1.5TR (4500 K.cal/Hr) ABS Plastic Split type Air conditioner conforming with Rotory compressor operating on Non CFC Refrigerant suitable for wall mounting for operation on 230V, 50Hz single phase AC supply with 3 Star rating of as per BEE specification and capable of performing the functions of1) Cooling 2) Dehumidifying3) Air circulation4) Filtering5) HeatingThe installation works for the above split type AC units includes the following.1.Mounting / Fitting Indoor and outdoor units at their respective locations.2. Laying refrigerant pipeline of required length connecting not exceeding 3 Mtrs length and both units after drilling hole / holes in the wall if required.3. Insulating the suction pipe with expanded polyeurethene foam 5mm tubing.4. Laying 25mm dia flexible PVC drain pipe to throw out the condensate water being formed within the indoor unit.5. Leakage testing the entire system unit.6. Charging refrigerant gas in the unit.7. Suitable electric wiring to be provided with 2.5sq.mm PVC insulated copper wire between indoor and outdoor units up to 6 Mtrs length and up to switch within 3 Mtrs of location of indoor unit. |
| 14 | supply and fixing of 4 KVA electronic automatic voltage stabilizers V. Guard make model VGS 400 with input range of 170-270V and output range 200-240 V with high and low voltage cut off and 3 minutes time delay relay with demonstration. |
| 15 | Renewal by supply, erection, testing and commissioning of 2.0 TR (6000 K. cal/ hr) ABS plastic split type Air conditioner conforming to IS: 1391 (Part-2) 1992 with Amdt No.1 to 2 fitted with Rotary compressor operating on Non CFC refrigerant suitable for wall mounting for operation on 230V, 50 HZ single phase AC supply with 5 star rating as per BEE specification and capable of performing the functions of1) Cooling 2) Dehumidifying 3) Air circulating 4) FilteringThe installation works for the above split type A.C units includes the following.1. Mounting / Fitting indoor and outdoor units at their respective locations.2. Laying refrigerant pipe line of 6 metres length, both units after drilling hole / holes in the wall if required. Thickness of the copper tubing shall Not be less than 0.7mm.3. Insulating the suction pipe with expanded polyurethelene foam 5mm thick tubing.4) Laying 25mm dia flexible PVC drain pipe of 6 mtrs. Length to drain out the condensate water being formed in the indoor unit.5) Leak testing the entire gas unit.6) Charging refrigerant gas in the unit.7) Suitable electric wiring to be provided with 3 core 2.5sq.mm PVC insulated copper wire between indoor and outdoor units up to 4 meters length and up to switch within 3 meters of location of indoor unit.(Reputed Make only) |
| 16 | Renewal by supply and fixing of 5 KVA electronic automatic voltage stabilizer with input range of 170-270V and output range 200-240 V with high and low voltage cut off and 3 minutes time delay relay with demonstration suitable for operation on 230V,50Hz single phase AC supply. |
| 17 | Renewal by supply and fixing of MS stand wall clamp support for mounting outdoor unit of split type AC unit complete. |
| 18 | Renewal by supply and fixing of 5/8” and 3/8” copper pipes with insulation foam of 6mm thickness suitable for split type AC unit. |
| 19 | Renewal by supply and fixing water drain pipe line (1\\" PVC pipe) |
| 20 | Renewal by supply and fixing of 20A flush type wall socket 32A DP MCB complete set for AC plug in flush with wall with earth connection. (For AC plug) |
| 21 | Renewal by supply and run of 2 of 4sq.mm PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe on wall and ceiling with continuous earth wire connection of 4sq.mm copper wire with painting of suitable colour. |
| 22 | Renewal by supply, erection, testing, commissioning uninterrupted power supply (sinewave) with copper wound transformer of 2000VA with input supply of 230V, 50Hz AC supply with 150AH Tubular battery to work at full load capacity including transportation with following specification. 1.Input voltage: 230V, 50Hz single phase AC supply2.Output voltage: 210V ± 10% 50Hz AC supply3.Battery charging device of suitable rating4.Circuit board of suitable capacity5.Over load and short circuit protection6.Visual Indication for ON/OFF/Trip/battery charging/mains failure/low battery etc.,7.Mode setting for By pass/Reset8.12V 150AH battery - 2 Nos.9.Trolly for heavy UPS & Battery. |
| 23 | Renewal by supply and run of 2 of 1.5sq.mm PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe on wall and ceiling with continuous earth wire connection 1.5sq.mm copper wire with painting of suitable colour. |
| 24 | Renewal by supply and fixing of 8 way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1No 32A DP MCB as incoming and 6Nos 6A to 32A SP MCB as outgoing on suitable angle iron frame on wall with earth connection only. (Higher End) |
| 25 | Renewal by supply and run of 2 of 6sq.mm PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe on wall and ceiling with continuous earth wire connection of 6 sq.mm copper wire with painting of suitable colour. |
| 26 | Renewal by supply and fixing of 4 way Vertical Triple pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1No 63A 4P MCB as incoming and 12Nos 6A to 32A SP MCB as outgoing on wall with earth connection only. (Higher End) |
| 27 | Renewal by supply and Run of 4 of 10sq.mm PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigd pipe on wall and ceiling with continuous earth wire connection of 10sq.mm copper wire with painting of suitable colour. |
| 28 | Renewal by supply and fixing of 63A TPN switch disconnector fuse units in sheet steel enclosure with HRC fuses double break on suitable angle iron frame work with MS cable entry boxes with Earth connection only. |
| 29 | Renewal by supply and clamping of 3½ x 35sq.mm PVC LTUG armoured cable on post or on wall with MS clamps. |
| 30 | Renewal by supply and fixing of brass cable gland for 3½ x 35sq.mm PVC armoured LTUG cable with earth connection. |
| 31 | Renewal by supply and providing cable end termination of 3½ x 35sq.mm PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete. |
| 32 | Earthing as per PWD standard with an earth electrode of 2 metres Class'B' GI pipe of dia Not less than 32mm complete with necessary masonry work. |
| 33 | Renewal by supply and Run of 1 of No.8 SWG copper wire in suitable PVC rigid pipe on wall / floor / ground for earth connection. |
| 34 | LESS CREDIT for Old materials |
| 35 | GST 18% Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 01, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 15, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 11 daysOct 15, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender