Housing Urban and Rular Development Government Departments Closing in 5 days TDR #57811322

Tender For Electrification Work In Library And Bar Room For The Court Of Acjm Sheoganj Sirohi

Issued by Government Departments · Jodhpur, Rajasthan
Tender Value
4.25 Lakhs
Estimated cost
Bid Submission
08 Oct 2026
5 days left
EMD
8500
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Jodhpur → Rajasthan
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Electrification Work In Library And Bar Room For The Court Of Acjm Sheoganj Sirohi

BOQ

Name of Work:- Electrification work in Library and Bar Room for The Court of ACJM Sheoganj Sirohi
Sl. No. Item Description
1Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminum round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 6 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required.
2Short point (up to 3 mtr.)
3Medium point (up to 6 mtr.)
4Long point (up to 10 mtr.)
5Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 6 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required.
6On board
7S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including making jhiri in the wall,clamps at suitable spacing, covering conduit and making good the same as required.
820 mm
925 mm
10Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required.
113x 1.5 sq.mm
122 x 2.5 sq. mm. + 1x1.5sqmm
132 x 4.0 sq. mm. + 1 x 2.5 sq. mm.
142 x 6.0 sq. mm. + 1 x 2.5 sq. mm.
15Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required.
16Single pole MCB (With B / C curve tripping characteristics)
176 A to 32 A rating
18Double pole MCB (With B / C curve tripping characteristics)
196 A to 32 A rating
20Four pole MCB (With B / C curve tripping characteristics)
2150/63 A rating
22Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door (Metal / Glazed / Acrylic) Distribution board with Metal end box made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, complete with 100 amp. insulated copper bus bar/shorting link , brass neutral link with shrouds, brass earth link , door earthing arrangement, color coded interconnecting wire set of minimum 10.0 sqmm size and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required.
23Metal door (single phase) IK-09 and IP-43 with Metal end box
248 Way
25Metal door (Three phase) IK-09 and IP-43 with Metal end box
264 Way (8 incomer + 12 Outgoing)
27Providing & Fixing of ISI marked (IS:302) ding dong/musical chime bell including making connection testing etc. as required.
28Providing & Fixing of modular type 100W Step Fan regulator duly ISI marked (IS 11037) with CM/L no. printed made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including making connections, testing etc as required.
295 step fan regulator 2 Module
30Supplying and fixing of power plug point with Modular accessories on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required.
31Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size.
3216.0 Sq. mm
334 core
34SITC of Copper Bonded rod Earthing with high tensile strength (more than 600 N / sq.mm low carbon steel rod molecularly bonded with Copper thickness (250 microns) and confirming to UL 467 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-
35(a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole
36(b)Earth enhancing compound to ensure the moisture content and electrical conductivity, 25 kg for 3000 mm. The compound shall be tested form NABL accredited lab for low resistivity (less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content in accordance with IEC 62561-7
37© Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt
38(d) Place Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm.
39(e) Testing of earth resistance for value of 5 ohms or less as required.
40(f) Test certificates for confirming above standards from OEM is mandatory.
4117.2 mm thick and 3 Mtr. Long
42Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.
4320mm x 3mm G.I. ( Hot Dipped ) Strip
44Supply & Fixing of phenolic laminated board of 6.0 mm thick for fresh air fan/exhaust fan up to size of 300 mm on existing window frame including cost of board, cutting of hole , Nut bolts etc. as required.
45Providing & Fixing of BEE Star rated copper wounded with class of Insulation 'F', double ball bearing capacitor start, aluminium body & aluminium blade ceiling fan conforming to all the performance requirements laid down in IS 374:2019 with down rod up to 30 cm with secondary support safety cable ( steel rope) , cotter pin, shackle kit with 3 x 1.5 sq.mm pvc insulated flexible copper conductor and making connection testing etc. as required.
461200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 )
47P & F 1.2 mm thick M.S. Recessed fan box and top lid screwed on Box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 150 mm length extended on each side as required.
48Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 marked in existing opening including making connections testing etc. as required.
49300 mm sweep(900 RPM)
50Providing & Fixing of 450 mm Sweep Oscillating type Wall mounting / Pedestal type fans with Three speed, ON and OFF position, Sintered Iron bush oil impregnated, with metal front and back 120 or more ribs guard; Three no. Aluminium blades, minimum Air delivery 100 Cum. / Minute , Minimum Service Value 1.11 Cum./min/watt, noise level should be <= 75 dB, power consumption <= 120 watts, motor protection through thermal overload protection device, including fixing with anchor bolts, making connection testing etc. as required.
51Wall mounting type with Adjustable Vertical Angle
52SITC of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output only at CW (5700K to 6500K) , internal surge protection of 4.0 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required.
531170mm(+/-10%) LED batten with min. lumen output 2200 lm
54SITC of IP-20 LED Recessed / Surface Mounted, Round / Sqaure backlit & SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS complience 4.0 KV surge protected Isolated driver, with Short & Open circuit protection input 320VAC-48 hr protection, input 350VAC-2 hr protection), having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt,at CW (5700K to 6500K) , THD < 10 % , Pf.≥0.95, CRI >80, UGR (unified glare rating)<19, fliker free (current ripple should be below 5%), SDCm (standard deviation colour matching)<5.life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) as required.
55Surface Mounting (with extruded alumn. Housing )
56Minimum lumen output 1950 lm
57Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass with suitable lenses on LED / integrated lens diffuser to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated metal case potted driver as a unique BIS R number (as per IS 15885) having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate(Fitting & driver both have separate BIS R number). The System level Luminaire efficacy >=130 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , LED driving output current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K as required.
58High Power LED Flood Light Minimum lumen output 10400 lm
59Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED/ integrated lens diffuser & should be High power LED of 3 to 5 watt each . The System efficacy >=125 lm/ wt and integrated metal case potted driver & has a unique BIS R number ( as per IS 15885) with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . LED driving output current <750mA. The luminaire shall be BIS certified (Fitting & driver both have separte BIS R number) and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs as required.
60LED Street Light fixture with Minimum lumen output 11250 lm
61Providing & Fixing of Street light bracket made out from following size of ' B ' class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required.
6232 mm Dia.
63Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, U/UTP (Unscreened/Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by LSZH Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies ranging from 250 to 500 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect.
64Supply and Installation of unshielded/360 degree shielded PCB based Information outlets made of high impact plastic body with ABS, Flammability rating UL 94 V-0 with provision for protection against dust in jack or Faceplate, suitable for Cat 6/6A application complying to latest amendments, According. to Cat. 6/6A channel, It should support channel as well as components requirements of Cat 6/6A standards at frequencies 250/ 500 MHz. Cat 6/6A unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack should have toolless/impact termination on reliable copper tin plated Insulation displacement contact, with easy lock mechanism, It supports IEC 60603-7-4 and complied with ANSI/TIA 568 C.2 & ISO/IEC 11801 or latest standard. jack should be RJ11,RJ12 & RJ45 compatible. Should support Ethernet 1.2 Gb/s ATM,Digital video and broadband/baseband analog video, Voice over internet protocol (VOIP) Specifications in existing modular/MS Boxes along with necessary connections as required. All as per pre approved by Engineer in charge.
65Cat 6, Un-sheilded Information Outlet
66Supply & fixing of square Faceplate for Flush / Surface Mount Information Outlets Single/Dual or Quad Aperture with dust cover, material should be High-impact, flame retardant, thermoplastic, UL listed material, Suitable for RJ45 unshielded/shielded connection modules. Should match with I. O. OEM. Dimensions should be 86mm X 86mm as required complete in all respect. All as per pre approved by Engineer in charge.
67Single Aperture
68SITC of Single Stage, water cooled, High Speed (2880 RPM), Horizontal, Centrifugal, Openwell Submersible pumps set pre filled with coolent water and fitted with mechanical seal. The motor body of single phase pump shall be of SS and rest of all shall be of cast iron. Shaft of three phase pump shall be of SS 410 grade. All casting parts should be cathod electro deposition (CED) coated. Motor winding shall be 100% copper wire material. Dynamically balanced rotating parts to ensure min. vibration etc. All labour for testing of submersible pumps set and supply of water to water mains, complete in all respect.
691.0 HP, 1-Ø, (12 -27) Mtr, (200- 30) LPM
70SITC of IP 54 OEM Fabricated DOL/Star-Delta Starter panel with switchgear selection as per Type-2 Coordination Chart and made out from 1.6 mm thick powder coated CRCA sheet, enclosure comprising of over load protection relay, short circuit & single phasing protection(for three phase pumps), Illuminated ON / OFF push buttons, ammeter, voltmeter, indicating lamps, 2P/4P MCB etc. suitable for following rating motors complete in all respect.
71For single phase Submersible / Monoblock pump
720.5 HP to 1.5 HP (DOL starter) Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57811322
AUTHORITY Government Departments
TENDER VALUE 4.25 Lakhs
LAST DATE 08-10-2026
Authority
Authority Name Public Works Department
Work Description Tender for Electrification Work In Library And Bar Room For The Court Of Acjm Sheoganj Sirohi
Basic Detail
Tender No NIT No.36/2026-27 of EE PWD Elect.Dn.II Jodhpur
Bidding Type Tender
Location
City Jodhpur
State Rajasthan
Key Dates
Publish Date 01 Oct 2026
Submission Date 08 Oct 2026
Open Date 09 Oct 2026
Finance
Tender Value 4.25 Lakhs
Tender Fee 500
EMD 8500
Exemption Available
Document List
BOQ_1067821.xls
ded84cf3-33ad-4c8f-a2e0-16223917d3ad.html
Tendernotice_1.pdf
Tendernotice_2.pdf
Tendernotice_3.pdf
Tendernotice_4.pdf
Tendernotice_5.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 01, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 08, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 5 days
Oct 09, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 6 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_1067821.xls

html

ded84cf3-33ad-4c8f-a2e0-16223917d3ad.html

pdf

Tendernotice_1.pdf

pdf

Tendernotice_2.pdf

pdf

Tendernotice_3.pdf

pdf

Tendernotice_4.pdf

pdf

Tendernotice_5.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender