Tender For Supply Installation Testing and Commissioning of Power Supply Cable From Switch Room To Mess Of Hall-5 And Supply Installation Testing and Commissioning of Flood Light And Allied Electrical Works In Tennis Court Complex And Elsewhere In Ii
Tender Overview
Project Description
Tender for Supply Installation Testing and Commissioning of Power Supply Cable From Switch Room To Mess Of Hall-5 And Supply Installation Testing and Commissioning of Flood Light And Allied Electrical Works In Tennis Court Complex And Elsewhere In Iit Kanpur.
BOQ
| Sl. No. | Item Description |
| 1 | Laying of one no. PVC insulated, PVC sheathed / XLPE power cable of 1.1kV grade of size above 35 sqmm and upto 95 sq.mm. |
| 2 | Direct in ground I/c excavation, sand cushioning, protective covering and refilling the trench etc. as reqd. |
| 3 | In pipe |
| 4 | In open duct |
| 5 | On surface with MS clamp (clamped with 25 X3 mm MS flat clamp ) |
| 6 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted/welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 7 | Supplying and making end termination with brass compression gland, aluminium lugs for following size of PVC insulated & PVC sheathed / XLPE aluminium cable of 1.1kV grade as reqd. |
| 8 | 3.5 x 50 sq.mm. |
| 9 | Supply & Laying of 50 mm dia, 8Kg / cm², minimum 2.0 mm thick HDPE pipe, ISI mark in following manners as required complete. |
| 10 | In ground i/c excavation sand cushioning protective covering, refilling of earth as reqd. |
| 11 | Laying charges In Pipe |
| 12 | Laying charges On Surface |
| 13 | Laying charges in open duct |
| 14 | Supply of one number PVC insulated & PVC sheathed/XLPE aluminium conductor steel armoured power cable of following sizes 1.1kV grade as per IS 7098 (part 1) 1988. |
| 15 | 3.5 x 50 sq.mm. |
| 16 | Supplying & drawing following sizes of FRLS PVC insulated copper conductor single core cable in / on the existing surface / recessed, PVC / steel conduit as reqd. |
| 17 | 3 x 1.5 Sq.mm.. |
| 18 | S & F MCB of following pole and rating 240/415 volts, 10kA, 'C' series in the existing MCB DB complete with connection, testing & commissioning etc as reqd. |
| 19 | Single Pole 6 amp to 32 amp |
| 20 | LED Flood Light, powder coated pressure die cast aluminium (System umen efficacy >135lm/Watt): Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC,frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI>70, under voltage and over voltage protection EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM 21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) ,SDCM(Standard Deviation Colour Matching) <5,Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR,PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 21 | 250 watt |
| 22 | Supply and drawing steel armoured, XLPE insulated, PVC intersheathed copper conductor 3 core round cable 1100 volt grade as per IS 7098 (Part 1) 1988 Complete as required. |
| 23 | 3 core armoured 1.5 sq.mm |
| 24 | Dismantling and fixing/refixing of LED light fittings integrated (with lamps) including connection,nut bolts, washer and screw etc. after removing old complete and depositing the dismantle in store as required. |
| 25 | Above 9 meter and upto 12 Meter |
| 26 | Locating fault in wiring rectifying removing & restoring supply the same & making good the damages etc as reqd. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline