Tender For Repair To Miscellaneous Em Items At Kohlapur Mil Stn Under Ge(N) Pune
Tender Overview
Project Description
Tender For Repair To Miscellaneous Em Items At Kohlapur Mil Stn Under Ge(N) Pune 1. Aking Down Old Unserviceable Feeder Pillar Box 2 (A) Mccb, 4 Pole, 415 Volts, 350 Amp (Dn3B-400D), (Cm98403Ooqo)-02 Nos, Adjustable Thermal Magnetic Relay With Breaking Capacity 25 Ka At 415 Volts Ics=100% Icu With On/Off/Trip Indicator ,Mcb.And Standard Extended Rotary Handle Dn3B, Dn3 (Cm99861Oooo)-02 Nos, Spreaders Terminal Dn3B/Dn3-400-4 Pole (Set Of 8)-02 Nos, Phase Barrier-02 No Auxiliary 1 C/O +Tac1 C/O Dn2, Dn3B, Dn3, Dn4-Right -04 Nos (Cm99804Oooo) 3 (B) Copper Bus Bar Of Suitable Size 500 Amps, Tpn -01 Set 4 (C) Digital Voltemeter(1Ph Led Cl-1-Secure) 0-500 Volts With Selector Switch 6A - 01 No 5 (D) Digital Amp Meter (1Ph Led Cl-1-Secure)0-200 Amp With Selector Switch 6A - 01 No 6 (E) Indicator Lamp Led Type (R,Y,B &R-G-O) Complete With Bakalite Fuse Fitting - 01 Set 7 (F) 6A Sp C Mcb-Lk (Bb10060C)-08 Nos 8 B) Manual Changeover Open Execution: (For Shifting Of Load Between Two X-Mer) (To Act As Bus Coupler) 9 350A, Mccb -Do- All As (A) Above- 1No. 10 Outgoing 11 (A) Mccb 4 Pole, 160 Amp,Adjustable Thermal Magnetic Relay With Breaking Capacity 25 Ka At 415 Volts Ics=100% Icu - 02 Nos 12 (B ) Mccb 4 Pole, 100 Amp, Adjustable Thermal Magnetic Relay With Breaking Capacity 25 Ka At 415 Volts Ics=100% Icu - 01 Nos 13 ( C ) Mccb 4 Pole, 63 Amp, Adjustable Thermal Magnetic Relay With Breaking Capacity 25 Ka At 415 Volts Ics=100% Icu - 02 Nos 14 (D) Automatic Timer Switch With Switches On/Off The Street Lights Base On Lux Level Of Natural Light Current Rating 40 Amps,Fp, C Mcb -01 Nos (Bb40400C), 40A Tp Contactor (Mnx 40) -01 Nos, Digital Time Switch Crono-01 Nos (67Ddt0), Green Indication Lamp-01 Nos, Red-Green Push Button -01 Nos, Selector Switch 1P2W6A 61151 6 -01 Nos, 6A Sp C Mcb-01 Nos (Bb10060C) 15 (E) Provision For Space To Be Kept Blank For Fixing Of Mccb - 01 No 16 Note :- Installation, Testing, Commissioning And Connecting Of Incoming And Outgoing Cables Connections Lt Feeder Pillar Panel Is Included In Rates Quoted. All Fixing Material Like Thimble, Glands, Nuts & Bolts Are Included In Unit Rate. Earthing Strip To Be Connected With Feeder Pillar Box With Suitable Size Nuts & Bolts. Etc.
BOQ
| Sl. No. | Item Description |
| 1 | Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI approved ((TTA Panels complying to IEC 61439)) double door floor mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body and inner compartments/ Protective door of 2.00 mm of suitable size with Copper bus bar 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Main Sub Stn Panel at Kolhapur)Note : CPRI approved of makes approved by CEPZ. |
| 2 | (a) MCCB, 4 Pole, 415 Volts, 350 Amp (DN3B-400D), (CM98403OOQO)-02 Nos, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN3B, DN3 (CM99861OOOO)-02 Nos, Spreaders Terminal DN3B/DN3-400-4 Pole (set of 8)-02 Nos, Phase Barrier-02 No Auxiliary 1 c/o +TAC1 C/O DN2, DN3B, DN3, DN4-Right -04 Nos (CM99804OOOO) |
| 3 | (b) Copper bus bar of suitable size 500 Amps, TPN -01 Set |
| 4 | (c) Digital Voltemeter(1Ph LED CL-1-Secure) 0-500 volts with selector switch 6A - 01 No |
| 5 | (d) Digital Amp meter (1Ph LED CL-1-Secure)0-200 Amp with selector switch 6A - 01 No |
| 6 | (e) Indicator lamp LED type (R,Y,B &R-G-O) complete with bakalite fuse fitting - 01 Set |
| 7 | (f) 6A SP 'C' MCB-LK (BB10060C)-08 Nos |
| 8 | b) Manual Changeover Open Execution: (for shifting of load between two x-mer) (to act as bus Coupler) |
| 9 | 350A, MCCB -do- all as (a) above- 1No. |
| 10 | Outgoing |
| 11 | (a) MCCB 4 pole, 160 Amp,adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos |
| 12 | (b ) MCCB 4 pole, 100 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 01 Nos |
| 13 | ( c ) MCCB 4 pole, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos |
| 14 | (d) Automatic timer switch with switches ON/OFF the street lights base on lux level of natural light current rating 40 Amps,FP, 'C' MCB -01 Nos (BB40400C), 40A TP Contactor (MNX 40) -01 Nos, Digital Time switch Crono-01 Nos (67DDT0), green indication lamp-01 Nos, Red-green push button -01 Nos, selector Switch 1P2W6A 61151 6 -01 Nos, 6A SP 'C' MCB-01 Nos (BB10060C) |
| 15 | (e) Provision for space to be kept blank for fixing of MCCB - 01 No |
| 16 | Note :- Installation, testing, commissioning and connecting of incoming and outgoing cables connections LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Glands, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts. |
| 17 | Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel ((TTA Panels complying to IEC 61439))double door floor mounted outdoor type, CPRI Approved as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (50x 10 mm ) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers including connection of spider of various capacity of MCCB complete with comprising of following and including: (Location : MES colony and JCO/OR Sub Stn) Note : CPRI approved of makes approved by CEPZ. |
| 18 | Incoming |
| 19 | (a) MCCB, 4 Pole, 415 Volts, 320 Amp, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu -01 No |
| 20 | (b) Alum bus bar (10 x 50 mm) 500 Amps TPN -01 Set |
| 21 | (ii) Ammeter 0-500 Amps with CTs & selector switch -01 No. |
| 22 | (iii) Voltmeter 0-500 volts with selector switch -01 No |
| 23 | (iv) Indicating lamp LED type - 01 set of three |
| 24 | (B) Outgoing |
| 25 | (a) MCCB 4 pole, 100 Amp,adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 01 Nos |
| 26 | (b ) MCCB 4 pole, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 04 Nos |
| 27 | ( c ) MCB DP 40 Amps -04 |
| 28 | (d) Automatic timer switch with switches ON/OFF the street lights base on lux level of natural light current rating 40 Amps,FP, 'C' MCB -01 Nos (BB40400C), 40A TP Contactor (MNX 40) -01 Nos, Digital Time switch Crono-01 Nos (67DDT0), green indication lamp-01 Nos, Red-green push button -01 Nos, selector Switch 1P2W6A 61151 6 -01 Nos, 6A SP 'C' MCB-01 Nos (BB10060C) |
| 29 | (e) Provision for space to be kept blank for fixing of MCCB - 01 No |
| 30 | Note :- Installation, testing, commissioning and connecting of incoming and outgoing cables connections LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Glands, Nuts & Bolts , LT cable Joint kits (16sqmm, 25 sqmm, 35 sqmm, 50 sqmm, 70 sqmm, 70 sqmm, 95 sqmm) of various sizes are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts. |
| 31 | Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI approved ((TTA Panels complying to IEC 61439)) double door floor mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15mm thick of outer body and inner compartments/ Protective door of 2.00 mm of suitable size with Copper bus bar 300 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (ECHS Pump House Panel)Note : CPRI approved of makes approved by CEPZ. |
| 32 | Incoming |
| 33 | (a) MCCB, 4 Pole, 415 Volts, 200 Amp (DZ1F0200DXD1AOOOO)-01 Nos, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu With on/off/trip indicator ,MCB and Standard Extended Rotary Handle DN2 (CM99830OOOO)-01 Nos, Spreaders terminal DN1, DN2-4 Pole (Set of 8) (CM92007OOOO)-01 Nos, Phase Barrier-02 No, Auxiliary 1 c/o +TAC1 C/O DN2, DN3, DN4,-Right (CM99804OOOO)-01 Nos |
| 34 | (b) Copper bus bar of suitable size 300 Amp TPN -01 Set |
| 35 | (c) Digital Voltemeter 1Ph LED Cl-1-Secure 0-500 volts with selector switch 6A (61325) - 01 No |
| 36 | (d) Digital Amp meter 1Ph LED Cl-1-Secure 0-200 Amp with selector switch (6A61312) - 01 No |
| 37 | (e) Indicator lamp LED type (R,Y,B &R-G-O) complete with bakalite fuse fitting - 01 Set |
| 38 | (f) 200/5 DIN TypeCl-1 VA-5 CT -03 Nos |
| 39 | (g) 6A SP 'C' MCB-LK (BB10060C)-08 Nos |
| 40 | Outgoing |
| 41 | (a) MCCB 4 pole, 100 Amp (DN0-100C) (CM91612OOKO)-02 Nos , adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN0 (CM97896OOO)-02 Nos, Spreaders terminal DN0-3 Pole (set of 6) (CM97785OOOO)-02 Nos, Phase Barrier- 02 Nos, Auxiliary 1 c/o +TAC1 C/O DN0, DN1-Right (CM97890OOOO)-02 Nos, R-G-O Indication Lamp-02 Nos, 6A SP'C' MCB (BB10060C)-04 Nos |
| 42 | (b) MCB DP 32 Amps - 02 Nos |
| 43 | (d) Automatic timer switch with switches ON/OFF the street lights base on lux level of natural light current rating 40 Amps,FP, 'C' MCB -01 Nos (BB40400C), 40A TP Contactor (MNX 40) -01 Nos, Digital Time switch Crono-01 Nos (67DDT0), green indication lamp-01 Nos, Red-green push button -01 Nos, selector Switch 1P2W6A 61151 6 -01 Nos, 6A SP 'C' MCB-01 Nos (BB10060C) |
| 44 | (d) Provision for space to be kept blank for fixing of MCCB - 01 No |
| 45 | Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts. |
| 46 | Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI approved d (TTA Panels complying to IEC 61439) double door floor mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Copper bus bar 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Stn HQ/Offr Accn Panel)Note : CPRI approved of makes approved by CEPZ. |
| 47 | Incoming |
| 48 | (a) MCCB, 4 Pole, 415 Volts, 160Amp, (CM90642OOMO)-01 Nos adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN1 (CM98041OOOO)-01 Nos, Spreaders terminal DN1, DN2, -04 Pole (set of 8)-(CM92007OOOO)-01 Nos, Phase Barrier01 No, Auxiliary 1 c/o +TAC1 C/O DN0, DN1-Right -01 Nos |
| 49 | (b) Copper bus bar of suitable size 250 Amps TPN -01 Set |
| 50 | (c) Digital Voltemeter 1 Ph LED Voltmeter Cl-1 Secure 0-500 volts with selector switch - 01 No |
| 51 | (d) Digital Amp meter 1 Ph LED Voltmeter Cl-1 Secure 0-200 Amp with selector switch - 01 No |
| 52 | (e) Indicator lamp LED type (R,Y,B & R-G-O) complete with bakalite fuse fitting - 01 Set |
| 53 | (f) 6A SP 'C' MCB (CM91612OOKO)-01 Nos |
| 54 | (f) 150/5 DIN Type CL-1 VA 5CT-03 Nos |
| 55 | Outgoing |
| 56 | (a) MCCB 4P, 100 Amp (CM91612OOKO)-01 Nos, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle Extended DN0-01 Nos, Spreaders Terminal DN0-3 Pole (set of 06) (CM97785OOOO)-01 Nos , Phase Barrier 01 Nos, Auxiliary 1 C/o+TAC1 c/o DN0, Dn1-Right (CM97890OOOO)-01 Nos, R-GO-Indication Lamp-01 Nos, 6A SP 'C' MCB LK (BB10060C)-02 Nos |
| 57 | (b) MCCB 4P, 63 Amp (DN0-100C)(CM91612OOHO)-02 Nos, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN0-02 Nos, Spreaders Terminal DN0-3 Pole (set of 6) (CM97785OOOO)-02 Nos, Phase Barrier 02 Nos,Auxiliary 1 C/o+TAC1 c/o DN0, Dn1-Right (CM97890OOOO)-02 Nos, R-G-O Indication Lamp-02 Nos,6A SP 'C' MCB-04Nos |
| 58 | (c) Provision for space to be kept blank for fixing of MCCB - 01 No |
| 59 | (d) Automatic timer switch with switches ON/OFF the street lights base on lux level of natural light current rating 40 Amps,FP, 'C' MCB -01 Nos (BB40400C), 40A TP Contactor (MNX 40) -01 Nos, Digital Time switch Crono-01 Nos (67DDT0), green indication lamp-01 Nos, Red-green push button -01 Nos, selector Switch 1P2W6A 61151 6 -01 Nos, 6A SP 'C' MCB-01 Nos (BB10060C) |
| 60 | Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts. |
| 61 | Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel (TTA Panels complying to IEC 61439) double door floor mounted outdoor type, CPRI Approved as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar ( 50 x 10 mm) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (JCOs/OR Accn)Note : CPRI approved of makes approved by CEPZ. |
| 62 | Incoming |
| 63 | (a) MCCB, 4 Pole, 415 Volts, 125 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu -01 No |
| 64 | (b) Copper bus bar ( 50 x 5 mm) 300 Amps, TPN -01 Set |
| 65 | (c) Digital Voltemeter 0-500 volts with selector switch - 01 No |
| 66 | (d) Digital Amp meter 0-200 Amp with selector switch - 01 No |
| 67 | (e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set |
| 68 | Outgoing |
| 69 | (a) MCCB 4P, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu- 01 Nos |
| 70 | (b) MCB DP 40 Amp, 16 KA, 415 V AC - 04 Nos |
| 71 | (d) Automatic timer switch with switches ON/OFF the street lights base on lux level of natural light current rating 40 Amps,FP, 'C' MCB -01 Nos (BB40400C), 40A TP Contactor (MNX 40) -01 Nos, Digital Time switch Crono-01 Nos (67DDT0), green indication lamp-01 Nos, Red-green push button -01 Nos, selector Switch 1P2W6A 61151 6 -01 Nos, 6A SP 'C' MCB-01 Nos (BB10060C) |
| 72 | (c) Provision for space to be kept blank for fixing of MCCB - 01 No |
| 73 | Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts. |
| 74 | Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel (TTA Panels complying to IEC 61439)double door floor mounted outdoor type, CPRI Approved as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar ( 50 x 10 mm) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (MES colony Accn)Note : CPRI approved of makes approved by CEPZ. |
| 75 | Incoming |
| 76 | (a) MCCB, 4 Pole, 415 Volts, 100 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu -02 No |
| 77 | (b) Copper bus bar ( 50 x 5 mm) 300 Amps, TPN -01 Set |
| 78 | (c) Digital Voltemeter 0-500 volts with selector switch - 01 No |
| 79 | (d) Digital Amp meter 0-200 Amp with selector switch - 01 No |
| 80 | (e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set |
| 81 | Outgoing |
| 82 | (a) MCCB 4P, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu- 01 Nos |
| 83 | (b) MCB DP 40 Amp, 16 KA, 415 V AC - 09 Nos |
| 84 | (c) Provision for space to be kept blank for fixing of MCCB - 01 No |
| 85 | Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts. Please Enable Macros to View BoQ information |
| 86 | Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 24 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender