Tender For Routine Maintenance And Operation Of electrical installation & Fans, Compound Lights, High Masts, Pumps, Fire Fighting System, Afa & Pa System And Sub-Station, Stp Plant, Solar Water Heating System & Dg Sets At Ddu College, Sector-3, Dwark
Tender Overview
Project Description
Tender for Routine Maintenance And Operation Of electrical installation & Fans, Compound Lights, High Masts, Pumps, Fire Fighting System, Afa & Pa System And Sub-Station, Stp Plant, Solar Water Heating System & Dg Sets At Ddu College, Sector-3, Dwarka, New Delhi. (During 2026-27).
BOQ
| Sl. No. | Item Description |
| 1 | SH - I - EI & Fans |
| 2 | Maintenance & operation of various E & M services comprising of following services on all days of the month i/c Sundays and holidays (as mentioned in the BOQ) i/c attending day to day complaint, rectification of fault, up-keeping and preventive maintenance of all electrical & mechanical installation complete etc. as reqd. as per terms & conditions and inventory enclosed - |
| 3 | (i)Internal and External electrical installations i/c compound lighting, etc.ii) 3x1000 KVA, 3x500 KVA DG set with Syncronization panel and SCADA System i/c pump set (drinking water, raw water, Drainage pumps) etciii) Sub station equipment i.e. Transformer, HT, LT & APFC Panels and associated accessories etc.Wireman cum operator– 3 Nos. (Round the clock)(6 AM to 2 PM, 2 PM to 10 PM & 10 PM to 6 AM) |
| 4 | Wireman – 1 Nos. (9 AM to 5 PM - General shift) |
| 5 | Khallasi – 2 Nos. (In General shift)) |
| 6 | Providing the services of Highly skilled supervisor (as per CPWD norms/qualification) on all days of the month i/c Sundays and holidays for supervision of electrical works, maintaining logbooks and ensuring safety standards etc complete as required. |
| 7 | Supervisor - 1 No. (In Genernal shift) |
| 8 | SH - II - Fire Fighting & Fire Alarm System |
| 9 | Fire Fighting System, Fire Alarm System and PA system - i/c Fire Pumps, Fire Engine etc.(i) For Fire Fighting i/c fire pumpOperator cum mechanics– 3 Nos. (Round the clock) (6 AM to 2 PM, 2 PM to 10 PM & 10 PM to 6 AM) |
| 10 | Khallasi - 1 No. (9 AM to 5 PM - General Shift) |
| 11 | (ii) For Fire Alarm System & PA systemOperator cum mechanics– 3 Nos. (One Nos. in each shift) (6 AM to 2 PM, 2 PM to 10 PM & 10 PM to 6 AM) |
| 12 | SH - III - Lifts Operation |
| 13 | Operation of 14 Nos. - Johnson make Lifts installed at different locations. Operation on all days of the month i/c Sundays and holidays:- |
| 14 | For Administrative building,(i) Lift Operator – 04 Nos. (In General shift). |
| 15 | For Utility block, Boys hostel & Girls Hostel(i) Lift Operator – 03 Nos. (Round the clock).(6 AM to 2 PM, 2 PM to 10 PM & 10 PM to 6 AM) |
| 16 | SH- IV- DG Set |
| 17 | Routine & comprehensive maintenance of following capacity 3 x 500 KVA DG set with AMF complete checking by Engineer for smooth running with minor adjustment, Diagnosis of various faults and rectification by providing regular visit of Engineer of mechanics and attending of complaint within 24 hours basis.(Excluding major repair of engine and alternator) 500 KVA DG set ESN.25405225,ESN.25405129 & ESN.25405226 Model-KTA19G10 (Cummins Make)= 3 Nos. DG Set |
| 18 | Servicing and 'B' Check of following capacity DG set complete with changing of engine oil & filters etc as reqd. i/c credit of old dismantled material etc as reqd. |
| 19 | ELEMENT LUB OIL FILTER (Part No. 3889310) |
| 20 | SEPARATOR FUEL WATER (Part No. 3329289 ) |
| 21 | ELEMENT OIL BY PASS FILTER (Part No. 3889311) |
| 22 | ELEMENT CRN RESISTOR (Part No. 3827423 ) |
| 23 | INHIBITOR CORROSION 10 LITERS (Part No. 4926654 ) |
| 24 | FOIL SEALED TEST STRIPS CC2602 (Part No. 3403800 ) |
| 25 | INDICATOR RESTRICTION (Part No. 3872813 ) |
| 26 | KIT AIR CLEANER ELEMENT NTS (Part No. 3238665) |
| 27 | GASKET ROCKER LEVER COVER (Part No. 3629140 ) |
| 28 | RECTIFIER SERVICE KIT - HC 4/5 (Part No. RSK5001 ) |
| 29 | RADIWASH 3 LITERS (Part No. AX1013359 ) |
| 30 | RADIWASH 1 LITERS (Part No. AX1013358) |
| 31 | FUNNEL FUEL FILTER CONDUCTIVE-L(Part No. AX1015647) |
| 32 | DEVICE, SPIKE PROTECTION (Part No. AX1016838 ) |
| 33 | VALVOLINE PREMIUM BLUE 55 LTRS. (Part No. 50655 ) |
| 34 | Service Charges towards cleaning & descaling of radiator/ heat exchanger of 500 KVA DG Set |
| 35 | SH- V- Miscelleneous work |
| 36 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 37 | Group C |
| 38 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. |
| 39 | Group C |
| 40 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 41 | 20 mm |
| 42 | 25 mm |
| 43 | 32 mm |
| 44 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 45 | 3 Module (100mm X 75mm) |
| 46 | 6 Module (200mm X 75mm) |
| 47 | 8 Module (125mm X 125mm) |
| 48 | Supplying, drawing, Testing and commissioning of Cat6A UTP 4 pair, 23 AWG solid copper cable in existing conduit/ on surface, U/FTP, LSZH, Non Plenum, Horizontal (solid) Cable suitable for high-speed data networking application supporting upto 10Gbps over a 100 meter channel. The 4 Unshielded Twisted Pairs (UTP) cable with color coded insulation for easy identification should have FLAME PROPERTIES i.e. Flammability Test - IEC 60332-1, Smoke Density - IEC 61034, LSZH standards compliance: ANSI/TIA-568 C.2, ISO/IEC 11801, IEEE 802.3an, RoHS. Delay Skew should be < 45NS. The outer Cable Diameter should be 7.5 + 2 mm. Cable should have been tested and verified by UL/ ETL etc. complete as required. |
| 49 | 1 Run of cable |
| 50 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 51 | 8 way , Double door |
| 52 | 12 way , Double door |
| 53 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 54 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. (As per site compatibility.) |
| 55 | 100 Amp, 16 KA,TPMCCB |
| 56 | 125 Amp, 16 KA,TPMCCB |
| 57 | 100 Amp, 30KA, FPMCCB |
| 58 | 125 Amp, 36KA, FPMCCB |
| 59 | 250 Amp, 36KA, FPMCCB |
| 60 | 400 Amp, 50KA, FPMCCB |
| 61 | 630 A, 50 KA,TPMCCB |
| 62 | 400 A, 35 KA,TPMCCB |
| 63 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI EMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin),SDCM (Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 64 | 72 watt |
| 65 | Supplying, installation, testing & commissioning of wall mounted 3 watt flexible Goose neck type reading light with SS / aluminium body, adjustable arm of lenght ≥ 30 cm i/c making connection with 3 x 1.5 sq.mm copper wire etc complete as required. |
| 66 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (45 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 67 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 68 | Supplying and Laying of one number PVC insulated and PVC sheathed Aluminium conductor XLPE armoured power cable of 1.1 KV grade of following size direct in existing DWC/ Hume Pipe complete etc. as required. |
| 69 | 4 x 16 sqmm |
| 70 | 4 x 25 sqmm |
| 71 | Supplying and Laying of one number PVC insulated and PVC sheathed Aluminium conductor XLPE armoured power cable of 1.1 KV grade of following size fixing on surface with the help of suitable size saddle complete etc. as required. |
| 72 | 4 x 16 sqmm |
| 73 | 4 x 25 sqmm |
| 74 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). |
| 75 | 4 way (4 + 12), Double door |
| 76 | 8 way (4 + 24), Double door |
| 77 | Rewinding of 1200mm ceiling fan complete with super enemelled copper winding wire i/c varnishing backing testing commissioning and without returning of scrop copper wire etc. as reqd. |
| 78 | Rewinding of 250 mm to 450 mm Exhaust fan/ Desert cooler fan complete with super enemelled copper winding wire i/c varnishing backing testing commissioning and with credit of scrap copper wire etc. as reqd. |
| 79 | Rewinding repair and servicing of following monoblock/Submersible pump set suitable for run 3 phase, 440 volt, 50 Hz AC supply i/c cartrdge (to and fro) testing, commissioning with credit of scrap copper wire etc. as required. |
| 80 | 3/5 HP monoblock pump set/mono submersible pump set |
| 81 | 7.5/10 HP submersible /mono submersible pump set |
| 82 | Withdrawing of all capacity submersible /mono submersible pump set with motor with GI pipes from the existing borewell with the help of chain pully block, tripod and supplying clamp i/c dismantling of GI pipe lengths by opening the nut & bolts, stacking the same etc as reqd |
| 83 | Lowering of all capacity submersible / mono submersible pump set with motor with GI pipes from the existing borewell with the help of chain pully block, tripod and supplying clamp i/c dismantling of GI pipe lengths by opening the nut & bolts, stacking the same etc as reqd |
| 84 | Supplying and fixing of 3x4 sqmm flat submersible cable of copper conductor cable alongwith GI pipe line etc. as required. |
| 85 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 Nos. of 3 pin 5/6 & 1 No. of 6 pin 15/16 amps modular socket outlet and 15/16 amps modular switch and 1 No. blanking plate connection etc. as required. (For computer point) |
| 86 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 87 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 88 | 3½ X 120 sq. mm |
| 89 | 3½ X 300 sq. mm |
| 90 | 3½ X 400 sq. mm |
| 91 | Supplying , Installation, Testing and Commissioning of Air Coole Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section, upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). Inverter Type - Cooling only |
| 92 | 2.0 TR with 5 Star BEE Rating Inverter Type |
| 93 | Supplying, Installation, Testing and Commissioning of Electronic Voltage Stabilizer of Capacity : 4 KVA (Suitable for upto 2 Tr. AC) for Voltage correction, low / high voltage Cut off, overload cut off with automatic reset, fail safe Circuit protection, Main Turn on delay, Wall mounting Cabinet design etc as required. Input Voltage : 140 – 280V ±5% Output Voltage : 200 – 250 V±5% |
| 94 | Providing & fixing of MS powder coated outdoor wall mounting Stand suitable for 1.5/2.0 TR capacity split AC outdoor unit complete as reqd. |
| 95 | Supplying, Installation, testing and commissioning including vaccumization and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : |
| 96 | 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 97 | 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 98 | Supply and installation of control cum transmission wiring of 3 core x 2.5 sqmm copper Unarmoured in suitable fittings between indoor and outdoor units on surface / conduit / pipe / cable tray / open duct etc. complete as required |
| 99 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. |
| 100 | 25 mm nominal outer dia Pipes |
| 101 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 102 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 103 | 80 mm |
| 104 | SITC of 1 HP single phase Dewatering submersible ama-porter pump set or equivalent make conforming to relevant IS : 14536/IS: 11346 suitable for delivering 55 LPM at a head of 15 mtr . i/c lowering pump set in the bore well complete etc as reqd. |
| 105 | SITC of 1 HP Three phase Sewage Dewatering submersible pump set or equivalent make conforming to releveant IS : 14536/IS: 11346 suitable for delivering 30 LPM at a head of 15 mtr . i/c lowering pump set in the bore well complete etc as reqd. |
| 106 | Servicing, cleaning & testing of existing 1000k VA, 11k V/433 Volt cast resin dry type indoor Transformer, dismantling and opening of HT, LT side connection, testing of door opening safeties, testing of temperature rise controller relay i/c following testing of transformer to check the healthiness of transformer –1. Voltage Ratio Test2. Magnetic Balance Test3. Magnetizing Current Test4. Insulation Resistance Test5. PI Value Test |
| 107 | Repairing & Servicing of existing 11kV, 630/800 Amp, 50Hz,3 phase VCB, complete with removal from the HT panel board, dismantling / opening the required parts for servicing, checking, cleaning, testing & rectification of defects, setting right of main contacts, moving contacts, tripping and closing mechanism, repairing and decarbonising the fixed spout of panel after dismantling and refixing the same, oiling, greasing, assembling i/c servicing & repairing complete mechanical and electrical testing of VCB i/c making workable the tripping system workable by replacing and making good the same etc. and replacing minor faulty parts like ammeter, voltmeter, LED indicator, push botton & lock etc complete as reqd. |
| 108 | Repairing, servicing, testing, and commissioning of LT panel with bus coupler, including inspection of bus bars, tightening of electrical connections, replacement of damaged components (if required), cleaning of panel compartments, checking of ACB/MCCB (replacement of ACB/MCCB is not considered) operation, insulation resistance testing, functional testing of interlocks, and restoration of the panel to satisfactory working condition, complete in all respects i/c replacement of minor faulty parts like ammeter, voltmeter, push buttons, led indicator lamp, locks control wiring etc complete as reqd. |
| 109 | Repairing, servicing, testing, and commissioning of essential panel with bus coupler, including inspection of bus bars, tightening of electrical connections, replacement of damaged components (if required), cleaning of panel compartments, checking of ACB/MCCB (replacement of ACB/MCCB is not considered) operation, insulation resistance testing, functional testing of interlocks, and restoration of the panel to satisfactory working condition, complete in all respects i/c replacement of minor faulty parts like ammeter, voltmeter, push buttons, led indicator lamp, locks control wiring etc complete as reqd. |
| 110 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 111 | 4 X 16 sq. mm (28mm) |
| 112 | 4 X 25 sq. mm (28mm) |
| 113 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 114 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 115 | Supplying, installation, testing and commissioning of heavy-duty, noiseless kitchen Exhaust/Chimney fan 450 mm sweep suitable for kitchen ventilation, duct mounted, fitted with dynamically balanced impeller, totally enclosed capacitor start and run type induction motor, operation on 230 V ± 10% 50 Hz, Single phase AC supply, metal louvers/gravity-operated shutters, bird-screen mesh, rawl plugs, structural supports, making cutting in wall and making good damages to match original finish and connections with PVC insulated copper conductor wire etc complete as reqd. |
| 116 | SITC of 2 HP Three phase Sewage Dewatering submersible pump set or equivalent make conforming to relevant IS : 14536/IS: 11346 suitable for delivering 50 mm at a head of 8 mtr to 16 mtr . i/c lowering pump set in the bore well complete etc as reqd. |
| 117 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 118 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 119 | Locating and reviving the buried earthing pit, including cleaning rusted terminals, replacing nuts and bolts, adding charcoal and salt to improve conductivity, watering through the pipe, and providing a new CI cover if required etc complete as required. |
| 120 | Preventive maintenance of ACB includes racking out the breaker, cleaning, inspecting contacts, tightening busbar connections, checking interlocks and trip settings, performing a Megger test, and verifying ON/OFF operation and load current before returning it to service. |
| 121 | Supplying and replacing , Installation, Testing and Commissioning the existing old/outdated ACB with new ACB's, 1600A Four pole, 50KA (RMS), Electrical draw-out type (EDO-motorized), front operated Air Circuit Breaker suitable for 415Volt, 3-Phase, 50Hz AC supply system, rated ultimate breaking capacity under short circuit - ICU at 440 Volt, 50KA ICS=ICU=ICW 100 % for 1 Sec, complete with Microprocessor releases based release for adjustable setting for over current, earth fault & short circuit with LCD displays Current (I1, I2, I3), Voltages (phase to phase, average and unbalanced),power factor, power demand and energy. release should self powered requiring no external power supply. Separate (Individual) faults LEDs indication the type of fault (overload, short-circuit, earth fault, internal fault) : ACB have inbuilt zone selective interlocking feature the breaker shall have minimum breaking capacity of 50kA (RMS Symmetrical) in-built thermal memory, 4NO/4NC auxiliary, confirming to IEC:60947/ IS:13947, Part-II/1993 (latest version), with copper rear terminal , All terminals shall be changeable Handle horizontal to vertical position and the vice versa at site to suit the bus bar orientation. breaker should have electrical interlocking (Incomer and bus couplers) through under voltage release with proper wiring, making modifications in the existing LT Panel and Bus Bar for proper connections/interconnections of new ACB's in existing panel and new ACB's panel door as per given make ACB's as good as same complete etc as reqd. |
| 122 | Servicing of LT panel including cleaning of busbars with vacuum/blower, tightening of electrical connections, servicing of breakers (ACB/MCCB), checking protection releases, and carrying out insulation resistance (Megger) test, all complete etc as reqd. |
| 123 | SH- VI- Fire Fighting System |
| 124 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. |
| 125 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 126 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/Class - I of IS: 3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. |
| 127 | 150 mm. dia |
| 128 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 129 | 32 mm dia |
| 130 | 50 mm dia |
| 131 | 100 mm dia |
| 132 | 150 mm dia |
| 133 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/ Stainless Steel coupling of 63 mm dia with cast iron wheel marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required. |
| 134 | Single headed Stainless steel |
| 135 | Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type with blank Gunmetal/Stainless Steel cap and chain as required : |
| 136 | Single headed Stainless steel |
| 137 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, 27.11.1 washers, gaskets conforming following sizes as required : |
| 138 | 50 mm dia |
| 139 | 80 mm dia |
| 140 | 100 mm dia |
| 141 | 150 mm dia |
| 142 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : |
| 143 | 100 mm dia |
| 144 | 150 mm dia |
| 145 | 200 mm dia |
| 146 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 147 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber washers etc.as required : |
| 148 | 100 mm dia |
| 149 | 150 mm dia |
| 150 | 80 mm dia |
| 151 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : |
| 152 | Stainless Steel (Grade 304) |
| 153 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.(a) 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585(b) 20 mm nominal internal dia gun metal globe valve & nozzle.(c) Drum and brackets for fixing the equipmets on wall.(d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. |
| 154 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required: |
| 155 | Stainless Steel (Grade 304) |
| 156 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required: |
| 157 | 2 way-100 mm dia M.S. Pipe |
| 158 | 4 way - 150 mm dia M.S. Pipe |
| 159 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required. |
| 160 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 0C with required accessories : |
| 161 | Pendent Sprinkler |
| 162 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 163 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. |
| 164 | 100mm dia |
| 165 | Providing and fixing in position industrial type pressure gauges with gun metal / brass valves complete etc. as required. |
| 166 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade: |
| 167 | Two or mote coats on new work over and under coat of suitable shade with ordinary paint of approved brand and manufacturer |
| 168 | Supplying and fixing following size hose cabinet double door fabricated out of 16 SWG thick GI sheet with 6mm thick glazed glass door in front having locking arrangement suitable to accommodate external / internal hydrant with 2 Nos 15 Mtr long hose reels 1 No. branch pipe etc on mounted on wall or raised brick platform & duly powder coated with PO Red paint externally & white paint internally etc complete in all respect as required at site & having following dismantles i/c less credit for worn out damage dismantled material.Size: 900mmX600mmX500mm |
| 169 | Servicing of 15 HP Kirloskar make electric motor coupled Jockey Fire Pump set by removing the old grease from the bearing and putting new replacing graphite gland, packing, stud and gland pushers etc as required. |
| 170 | Servicing of 60 HP/45 KW Kirloskar make electric motor coupled Main Fire Pump set by removing the old grease from the bearing and putting new replacing graphite gland, packing, stud and gland pushers etc as required. |
| 171 | Repairing and servicing the 15 HP/11 KW terrace pump motor-pump set by opening of pump casing replacing grease from the bearing, cleaning of impeller and etc complete as required. |
| 172 | Painting of Electrical Panels/Terrace pump with two coats of synthetic enamel paints of approved brand & manufacturer of required colour to give an even shade including cleaning of surface etc and replacement of faulty/ unserviceable components of panel like, locks, indicator lamp, terminal link, control wiring & all other related accessories etc complete as required. |
| 173 | SH- VII - Supply of material |
| 174 | Following electrical item / accessories suitable for 1/3 phase, 50 Hz, AC supply shall be supply by agency and existing man power shall be used for replacement on day to day maintenance works. All material should be as per compatibility of site. |
| 175 | S.P. 5/6 amps, one way modular switch, ISI marked |
| 176 | 3 pin 5/6 amps modular socket outlet, ISI marked |
| 177 | S.P. 15/16 amps, one way modular switch, ISI marked |
| 178 | 15/16 Amp Modular Socket |
| 179 | 6 to 32 Amp c Curve SP MCB, \\"C\\" curve, 10 kA breaking capacity |
| 180 | 40 Amp DP MCB, C-Curve |
| 181 | 63 Amp DP MCB, C-Curve |
| 182 | 63 amp TPN MCB, C-Curve |
| 183 | 40 amp TPN MCB, C-Curve |
| 184 | 63 amp TP MCB, C-Curve |
| 185 | 1.5 sq. mm ISI marked, FRLS/HFFR PVC insulated, single core copper conductor cable |
| 186 | 4.0 sq. mm ISI marked, FRLS/HFFR PVC insulated, single core copper conductor cable |
| 187 | 6.0 sq. mm ISI marked, FRLS/HFFR PVC insulated, single core copper conductor cable |
| 188 | 10 sq. mm ISI marked, FRLS/HFFR PVC insulated, single core copper conductor cable |
| 189 | Ceiling fan with Brush Less Direct Current (BLDC) Motor, etc. complete as req 1200 mm sweep Ceiling fans (1200 mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 190 | 2.50 mF capacitor |
| 191 | Heavy Duty Exhaust Fan 300 mm Sweep (900 RPM) |
| 192 | 250 mm Air freshner /Ventilator fan |
| 193 | Exhaust fan 380 mm sweep (1400 r.p.m) |
| 194 | 450 mm sweep heavy duty exhaust fans |
| 195 | 600 mm Industrial wall fan 1440 RPM |
| 196 | Elevator Cabin Fan |
| 197 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt) of following body materials. CRCA Sheet Body (Thickness > 0.50 mm)a) 36 watt |
| 198 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt) of following body materials. CRCA Sheet Body (Thickness > 0.50 mm) a) 36 watt |
| 199 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt ) of following body materials. Powder coated die cast /Extruded aluminium Body including trim with Aluminium Reflector 18 watt |
| 200 | 8 - 10 watt |
| 201 | Call bell/ buzzer, single phase |
| 202 | 3 mm thick phenolic laminated sheet |
| 203 | Ceiling rose, 3 pin, 5 A ISI marked |
| 204 | Modular base & cover plate for 3 module |
| 205 | Modular base & cover plate for 4 module |
| 206 | Modular base & cover plate for 8 module |
| 207 | Modular base & cover plate for 12 module |
| 208 | Modular blanking plate |
| 209 | Modular bell push, ISI marked |
| 210 | Stepped type Modular Fan regulator (2 module) |
| 211 | Suitable size PVC Box i/c fixing of 15/16 Amp. combined switch socket. |
| 212 | 15/16 A 3 Pin Plug Top |
| 213 | Supply of LED Bulk Head fitting not more than 10 W, System efficacy not less than 100 lumens / watt, System output not less than 1000 lumens / watt, CRI>80 and CCT= 5500-6500K and IP-66 rated with aluminium die cast housing & frostrated glass diffuser complete as required. |
| 214 | 600 mm long nominal size LED batten mirror light fitting made out with Aluminium die cast housing and Poly carbonate diffuser with all accessories having rating not more than 10 W, System Efficacy not less than 100 lm/W, lumens output not less than 1000, CRI >80 complete etc. as required. |
| 215 | 25 x 16 mm PVC casing capping |
| 216 | SH- VIII - Servicing AC |
| 217 | Servicing of existing installed WTAC / STAC of 1.5 TR & 2.0 TR capacity AC and water coolers of 80/150/250 LPH, checking for unit, inspection, greasing, oiling etc i/c chemical cleaning of the condensing coil with high pressure pump changing the air filter, checking & tightening all electric connection, testing the machine etc as reqd. |
| 218 | Dismantling & Re-installation of existing installed STAC / WTAC of 1.5 TR & 2.0 TR capacity with outdoor unit from its location to another location, unloading for reinstallation checking for unit, inspection and reconnection of drainage pipe, reconnection and tightening the loose connection, testing the machine etc as reqd. |
| 219 | Supplying & fixing of following capacity compressor in the existing WTAC / Split AC making copper pipe connection, brazong pressure testing and supplying and charging M-22 refrigerant gas charging i/c cutting the copper piping dismantling & credit of the old compressor complete as reqd. |
| 220 | Compressor - 1.5 TR |
| 221 | Compressor - 2 TR |
| 222 | Providing and fixing WTAC /STAC fan motor capacity 1/4 to 1/8 HP i/c dismantling & credit the burnt motor from the existing unit & fixing of new motor making connection, testing complete etc as reqd i.c dismantled of old and credit of old material etc. as reqd. |
| 223 | Supplying & charging of M-22 / R-22 gas in the existing WTAC / STAC of 1.5TR unit i/c pressure testing, flushing the system & gas charging complete etc as reqd. |
| 224 | Supplying & charging of M-22 / R-22 gas in the existing WTAC / STAC of 2 TR unit i/c pressure testing, flushing the system & gas charging complete etc as reqd. |
| 225 | Repair of damaged PCB of indoor and outdoor unit i/c tightening the loose connection, testing the machine etc as reqd. |
| 226 | Supplying & fixing of copper refrigerant pipe of size 1/4\\", 5/8\\" with insulation and copper wire 3 core 80-20 i/c all connection in the existing AC units i/c credit of dismantle material as per reqd at site. |
| 227 | Providing & fixing of MS powder coated outdoor wall mounting Stand suitable for 1.5/2.0 TR capcity spilit AC outdoor unit complete as reqd. i.c dismantled of old and credit of old material etc. as reqd. |
| 228 | Supplying and fixing of 1.5 / 2 TR capacity WTAC/ Split AC cooling coils i/c pressure testing after removing the leakage with brazing, flashing the system, vacuuming the system, checking & repairing interconnection complete in all respect as required at site. i.c dismantled of old and credit of old material etc. as reqd. |
| 229 | Supply & Replacement of 1.5 / 2 TR WTAC / STAC burnt out / defective copper condenser coil with new one of the same size and design suitable for 1.5 TR Split type AC Out Door unit i/c breezing the all copper pipe with all distribution joint's and make sure the connections with capillary tube linking dryer duly proper etc. Nitrogen pressure testing, leak detections, vaccumizing the unit, complete as reqd. i.c dismantled of old and credit of old material etc. as reqd. |
| 230 | Comprehensive & Routine maintenance of 144 Nos. WTAC / STAC / Tower AC (as per Inventory attached) i/c attending day to day complaints from 9 AM to 5 PM by deputing minimum following staff (to report to JE(E) daily) and rectify the defects i/c replacement of wornout parts such as starting / running capacitors, starting relays, overload relay, tharmostat, selector switches, sleeves, knobes, connector and associated control wiring, filter, drain pipe, man leads etc which required to be replace during routine maintenance and monthly cleaning of filters etc. (Replacement of compressor, condensor unit, cooling coil unit, blower, fan blower motor, front grill, gas charging etc not covered under routine maintenance) complete as per terms & conditons and Engineer-in-Charge.(a) AC Mechanic - 1 No.(b) Khallasi - 1 No. |
| 231 | Annual Comprehensive Maintenance & repair of Aquaguard make water Purifier of 20-30 LPH capacity i/c 4 visit Per Month which include thorough checking & cleaning of the product & additional visit during the contract period as & when required in the event if any breakdown/malfunctioning of the equipment will be covered free of cost, repair/replacement of all spare parts like booster pump, PP filter, CTO filter, suitable membranes & electrical spare parts etc. & attending complaints withing 24 working hours with other repair & servicing etc complete as required. (Qty. 14 Nos.) |
| 232 | SH-IX:- Credit of Dismantled material |
| 233 | Less Credit cost for following old dismantled materials |
| 234 | Copper winding wire/copper submersible cable/scrap copper wire (1.5/4.0/6/10 Sqmm copper coductor cable) |
| 235 | 1 HP sewage dewatering Submersible p/set |
| 236 | 2 HP sewage dewatering Submersible p/set |
| 237 | 2.5 mfd condensers |
| 238 | 5/6A/ 15/16A Switch/ Socket/ bell push/ 2 way switch/ceiling rose |
| 239 | Call Bell |
| 240 | c' curve SP MCB 6-32A |
| 241 | 40/63A DP MCB 'c' curve |
| 242 | 63 A TP MCB 'c' curve |
| 243 | 40/63A TPN MCB 'c' curve |
| 244 | SP DB/TP DB |
| 245 | MCCB - 100/125/250/400/630 Amp |
| 246 | GI Box - 3/6/8 Module |
| 247 | Ceiling fan |
| 248 | LED Panel light 2x2 ft. |
| 249 | Exhaust Fan |
| 250 | Chimmey Exhaust |
| 251 | Fresh Air Fan |
| 252 | Industrial wall fan |
| 253 | Lift fan |
| 254 | Street light fittings |
| 255 | LED Down lighter |
| 256 | LED Batten light |
| 257 | LED Bulk Head fitting |
| 258 | LED batten mirror light fitting |
| 259 | Modular base & cover plate for 1,2,3,4,5,6,7,8 & 12 module |
| 260 | Modular bell push, ISI marked |
| 261 | Stepped type Modular Fan regulator (2 module) |
| 262 | Butterfly valve/Sluice valve - 50/80/100/150 |
| 263 | NRV - 80/100/150 |
| 264 | Air vessel made of 250 mm dia |
| 265 | Pressure switch /Pressure gauges |
| 266 | Pendent Sprinkler |
| 267 | MS pipe - 25/32/65/80/100/150 mm dia |
| 268 | Internal/external Hydrant valve |
| 269 | RRL hose pipe |
| 270 | Orifice plate |
| 271 | Fire Brigade - 2-3 4 way |
| 272 | Hose reel |
| 273 | Flow switch |
| 274 | SS short branch pipe |
| 275 | 2.0 Tr. Split type Air conditioners complete with Indoor unit, Out door unit |
| 276 | Voltage Stabilizer |
| 277 | CPVC pipe |
| 278 | MS stand |
| 279 | Modular blanking plate |
| 280 | Hose cabinet double door Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
TodayBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 7 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 7 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender