Tender For Emf Of Sector-18B,Dwarka, Hig Flats Hs-2010. Sh: R/M/O Of 160 Kva D.G. Sets, Sub. P/Sets , Dewatering P/Sets And Common Area Lighting, Fire Fighting Pump Sets, Sprinkler System, Fire Alarm System, Diesel Engine, Lift Pressurization System,
Tender Overview
Project Description
Tender for Emf Of Sector-18B,Dwarka, Hig Flats Hs-2010. Sh: R/M/O Of 160 Kva D.G. Sets, Sub. P/Sets , Dewatering P/Sets And Common Area Lighting, Fire Fighting Pump Sets, Sprinkler System, Fire Alarm System, Diesel Engine, Lift Pressurization System, P.A. System And Intercom System And Monitoring Of Lifts At 490 Ms Hig Houses Pkt-I & 457 Ms Hig Houses Pkt-Ii In Sec 18-B, Dwarka, Ph-Ii.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 07-Oct-2026 | Corrigendum for Date extend | Date | 13-Oct-2026 |
| 2 | 13-Oct-2026 | Corrigendum2 for Date extend | Date | 17-Oct-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Running, maintenance and operation of DG sets, sub. p/set, dewatering pump set & common area lighting, fire fighting pump sets, sprinkler system, fire alarm systems, diesel engine, lift pressurization system, P.A. system & intercom system as per inventory terms & conditions attached. |
| 2 | Rescue & Coordination lift operators for operation of OTIS make lifts as per inventory, terms and condition attached. |
| 3 | Servicing of 160 KVA Crompton Greeves make D.G. sets i/c supply and replacement of following wornout parts complete with testing etc as reqd.(I/c rebate on dismantle materials)a) Diesel filter b) Oil filterc) coolantd) Battery leade) Hose pipe set with clampf) Fuel pipeg) Air cleaner elementh) Self repair & servicingi) Fuel pump repair and calibration and servicing j) Engine oil |
| 4 | Supplying of high speed diesel for operation of DG sets i/c cartage, storage, filling in tank and arrangement of minimum 200 ltrs capacity tank at site etc. complete as required. |
| 5 | Dismantling and rewinding/repairing of 5 HP capacity dewatering pump set kirloskar make suitable for 3 phase 415 volts 50 Hz AC supply and duly varnishing baking , to & fro cartage charges , reassembling and testing etc as regd. .(I/c rebate on dismantle materials) |
| 6 | Supplying, installation, Testing & Commissioning of LED recessed/surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%,Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10%, P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard.Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management:heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). A) Powder coated die cast /Extruded aluminium Body including trim .---22 Watt |
| 7 | Supply and replacement of 12 volts 180 AH battery wih initial charging i/c connections, testing etc as reqd.(i/c rebate for old battery) |
| 8 | Supply and replacement of defective MCCB with following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required . (DSR-2025) A) 100 A,30KA,FPMCCB |
| 9 | Supplying & replacement of faulty CFL bulbs installed in all 60 Nos. lift shafts with following items in the existing light fittings complete with connection, testing etc. as required. a) LED Bulb with Ordinary Holder - 9 Watt |
| 10 | Supply, testing and commissionning of 1 HP Submersible Dewatering Pump set -- Ama Porter 501 SE Model (Vertical monoblock type) suitable for single phase, 50 Hz, 220/240V AC supply having Free Passage: 45 mm , 10 mtr. head & 110 LPM & inlet/outlet dia 50 mm, IP 68 Protection & along with 10 mtrs 3-core, 1.0 sq. mm (3 x 1 mm²) flexible submersible power cable & & inbuilt Float Switch for automatic ON/OFF & test certificate i/c thimbling, connections, testing etc complete as reqd. |
| 11 | Supply & replacement of defective disconnector fuse switch unit with following capacity TP&N disconnector fuse switch unit (DM series ) in Sheet Steel Enclosure with ISI marked HRC fuses including drilling holes , making connections,testing etc. as required. A) 400 A TP&N (i/c rebate for dismantle materials) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
TodayBid Submission Deadline
Online submission via eProcurement portal.
TodayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender