Bids Are invited for Supply Installation Commissioning And Testing Of Silent Type Diesel Engine Driven Generating Set
Tender Overview
Project Description
Bids Are invited for Supply Installation Commissioning Testing Of Silent Type Diesel Engine Driven Generating Set Of Cap 320Kva Or 256Kw 0 Point 8Pf 415V 3Phase 4 Wire System Engine As Per Atc , Eart Hing Complete With Galvanized Steel Earth Plate Electrode 60Cm X 60Cm X 6Mm Thick Buried Directly In Ground Earth Pit Not Less Than 2 Point 25M Deep Below Ground Level With Top As Per Atc , Supplying Laying Passing Through Trench Wall Pipe Connecting And Testing Ub Cable Xlpe Insulated Armoured Heavy Duty Electric Cable With Aluminium Conductor 1100V Grade For The Size As Per Atc , Excavation In Trenches In Soft Or Loose Soil Not Exc 1 Point 5 Meter Wide And Not Exc 1 Point 5 Meter Deep And Getting Out In Soft Or Loose Soil For Laying Of Cableor Foundation Of Pole As Per Atc , Returning Filling In Soil Including Spreading Levelling Watering And Well Ramming In Layers N Exc 25 Cm , Removing Surplus Excavated Materials Not Exceeding 50 Mtr And Depositing Where Directed At A Level Not Exceeding 1 Point 5 Mtr Above Ground Level From Starting Point , M And L Tibba Sand For Cushioning To Under Ground Cable In Trenches Or Existing Cable Trenches Or Ducts In Layers Of 8 Cm Deep Before Laying The Cable And 15 Cm Deep After Laying As Per Atc , Supplying And Laying Un Reinforced Precast Concrete Cable Cover Class Lv Type I Flat Size 250Mm X 150Mm X 40 Mm All As Specified And Directed
BOQ
| Sl. No. | Item Title | Item Description |
| 1 | Supply installation commissioning testing of silent type Diesel Engine driven generating set of cap 320KVA or 256KW 0 point 8PF 415V 3Phase 4 wire system engine as per ATC | Supply installation commissioning testing of silent type Diesel Engine driven generating set of cap 320KVA or 256KW 0 point 8PF 415V 3Phase 4 wire system engine as per ATC |
| 2 | Eart hing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground Earth pit not less than 2 point 25M deep below ground level with top as per ATC | Eart hing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground Earth pit not less than 2 point 25M deep below ground level with top as per ATC |
| 3 | Supplying laying passing through trench wall pipe connecting and testing UB cable XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100V grade for the size as per ATC | Supplying laying passing through trench wall pipe connecting and testing UB cable XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100V grade for the size as per ATC |
| 4 | Excavation in trenches in soft or loose soil not exc 1 point 5 meter wide and not exc 1 point 5 meter deep and getting out in soft or loose soil for laying of cableor foundation of pole as per ATC | Excavation in trenches in soft or loose soil not exc 1 point 5 meter wide and not exc 1 point 5 meter deep and getting out in soft or loose soil for laying of cableor foundation of pole as per ATC |
| 5 | Returning filling in soil including spreading levelling watering and well ramming in layers n exc 25 cm | Returning filling in soil including spreading levelling watering and well ramming in layers n exc 25 cm |
| 6 | Removing surplus excavated materials not exceeding 50 mtr and depositing where directed at a level not exceeding 1 point 5 mtr above ground level from starting point | Removing surplus excavated materials not exceeding 50 mtr and depositing where directed at a level not exceeding 1 point 5 mtr above ground level from starting point |
| 7 | M and L tibba sand for cushioning to under ground cable in trenches or existing cable trenches or ducts in layers of 8 cm deep before laying the cable and 15 cm deep after laying as per ATC | M and L tibba sand for cushioning to under ground cable in trenches or existing cable trenches or ducts in layers of 8 cm deep before laying the cable and 15 cm deep after laying as per ATC |
| 8 | Supplying and laying un reinforced precast concrete cable cover Class LV Type I flat size 250mm x 150mm x 40 mm all as specified and directed | Supplying and laying un reinforced precast concrete cable cover Class LV Type I flat size 250mm x 150mm x 40 mm all as specified and directed |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 7 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender