Tender For Construction Work Of 20 Bedded Burn Unit Building In Shri Lal Bahadur Shastri Hospital, Ramnagar, District-Varanasi.
Tender Value
Ref. Documents
Estimated cost
Bid Submission
24 Oct 2026
19 days left
EMD
3 Lakhs
Bank guarantee accepted
Document Fee
5310
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Varanasi → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Construction Work Of 20 Bedded Burn Unit Building In Shri Lal Bahadur Shastri Hospital, Ramnagar, District-Varanasi.
BOQ
| Sl. No. | Item Description |
| 1 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.all kinds of soil DSR 2.8.1 |
| 2 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete. DSR 2.25A |
| 3 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. DSR 2.27 |
| 4 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) DSR 4.1.8 |
| 5 | Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor With Chlorpyriphos/Lindane E.C. 20% with 1% concentration DSR 2.35.3.1 |
| 6 | R.c.c. work with cement approved coarse sand and 2 cm. (3/4\\") guage approved stone ballast in the proportion 1:1.5:3,(1cement :1.5corse sand 3 grit) in Lintel excluding supply of reinforcement and its fixing and bending but including its fixing and binding the same necessary with 24 BWG binding wire and including necessary centering and shuttering etc.and also including supply of all materials, labour and tools and plants etc, required for proper completion of the works. DSR 5.3 |
| 7 | As in item above but for slabs (Using 1:1.5:3 Mix concrete) DSR 5.3 |
| 8 | As in item above for the lighter beams i.e. having spans upto 6 m. (Using 1:1.5:3 Mix concrete) DSR 5.3 |
| 9 | As in item No.8 above but in R.C.C. Raft foundation and footing with approved stone ballast. (Using 1:1.5:3 Mix concrete) DSR 5.1.2 |
| 10 | As in item above but in R.C.C. columns in 1:1.5:3 having strength not less than M-20. DSR 5.2.2 |
| 11 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 150 in .foundation and plinth in :Cement mortar 1:4 (1 cement : 4 coarse sand) DSR 6.1.1 |
| 12 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 150 in .foundation and plinth in :Cement mortar 1:6 (1 cement : 6 coarse sand) DSR 6.1.2 |
| 13 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 150 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand) DSR 6.4.2 |
| 14 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 150 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:4 (1 cement : 4 coarse sand) DSR 6.4.1 |
| 15 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations:(a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment.(b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs.(c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge.(d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep.(e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test.“All above operations to be done in order and as directed and specified by the Engineer-in-Charge :22.7.1 With average thickness of 120 mm and minimum thickness at khurra as 65 mm. DSR 22.7.1 |
| 16 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters:-35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws(SINGLE LEAF) DSR 9.20.1 |
| 17 | DOUBLE LEAF DSR 9.20.1+9.26 |
| 18 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer.Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) DSR 10.15.1 |
| 19 | 30 mm thick Glass Fibre Reinforced Plastic (FRP) panelled door shutter of required colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS: 14856, including fixing to frames. DSR 9.122.1 |
| 20 | Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross-section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminate shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2 mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady] the frame. DSR 9.121 |
| 21 | Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multichambered frame, sash and mullion (where ever required) extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), uPVC extruded glazing beads of appropriate dimension, EPDM gasket, stainless steel (SS 304 grade) friction hinges, zinc alloy (white powder coated) casement handles, G.I fasteners 100 x 8 mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable. Casement cum fixed panel window having both end single casement panel, middle fixed panels and at top completely fixed ventilator with S.S friction hinges (400 x 19 x 1.9) made of (big series) frame 60 x 58 mm, sash 60 x 72 mm , & T mullion 60 x 72 mm all having wall thickness of 2.3 ± 0.2 mm and single glazing bead/double glazing bead of appropriate dimension . (Area of window above 3.00 sqm upto 5.00 sqm). DSR (DSR-9.147.A4.1) |
| 22 | Providing and fixing glazed shutters for doors, windows and clerestory windows using 4 mm thick float glass panes including ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws. (a) 35mm thick Second class teak wood. DSR 9.9.1.1 |
| 23 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to steel windows by welding (hold fast) DSR 9.48.1 |
| 24 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to steel windows by welding (hold fast) DSR 9.48.1 |
| 25 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete.Stainless steel (grade 304) wire gauze of 0.5 mm dia wire and 1.4 mm aperture on both sides DSR 10.29.2 |
| 26 | Providing and fixing chromium plated brass curtain rod having wall thickness of 1.25mm with two chromium plated brass brackets fixed with C.P. brass screws and PVC sleeves etc., wherever necessary complete :25 mm dia DSR 9.46.3 |
| 27 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.Thermo-Mechanically Treated bars of grade Fe-500D or more. DSR 5.22.6 |
| 28 | 12 mm cement plaster in single coat on fair side of single or half brick wall for interior plastering up to floor two level including brick wall for interior plastering upto floor two level including internal rounded angles chamfers, and / or rounded angles not exceeding 80 mm in girth and finished even and smooth No. extra for mixing any additive. (1)1 cement : 6 COARSE sand DSR 13.4.2 |
| 29 | 15 mm cement plaster in single coat on rough side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 cement: coarse sand. F.M. 2.25(1)1 cement : 6 COARSE sand DSR 13.5.2 |
| 30 | 6 mm thick cement plaster of mix 1:3 (1cement:3 fine sand) in ceiling DSR 13.16.1 |
| 31 | Making drip coarse in sunshade or facia with 1:3 cement and fine sand mortar as per direction of Engineer in charge including supply of all materials, labour, tools & plants etc. required for proper complition of work. DSR 5.3 |
| 32 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades,laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm DSR 11.41.2 |
| 33 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. [IN SKIRTING] DSR 11.47.2 |
| 34 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. (40 mm flooring) DSR 11.3.1 |
| 35 | Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. Polished Granite stone slab colour of Black, Cherry/RubyRed or equivalent DSR 11.56.1 |
| 36 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Plain white marble / Udaipur green marble / Zebra black marble. Granite of any colour and shade (a) Area of slab over 0.50 sqm DSR 8.2.2.2 |
| 37 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement slurry @ 3.3 kg/sqm including pointing he joints with white cement and matching pigment etc., complete DSR 11.37 |
| 38 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement slurry @ 3.3 kg/sqm including pointing he joints with white cement and matching pigment etc., complete DSR 11.37 |
| 39 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 25 mm thick DSR 11.26.1 |
| 40 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade. New work (Two or more coats applied @ 1.43 ltr/ 10 sqm. over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm). DSR 13.47.1 |
| 41 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour. New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre . DSR 13.41.1 |
| 42 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. DSR 13.8 |
| 43 | Providing and fixing aluminium sliding door bolts, ISI marked anodised(anodic coating not less than grade AC 10 as per IS : 1868),transparent or dyed to required colour or shade, with nuts and screwsetc. complete 300x16 mm DSR 9.96.1 |
| 44 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodiccoating not less than grade AC 10 as per IS : 1868 ) transparent or dyedto required colour or shade, with necessary screws etc. complete250x10 mm DSR 9.97.3 |
| 45 | Providing and fixing aluminium handles, ISI marked, anodised (anodiccoating not less than grade AC 10 as per IS : 1868) transparent or dyedto required colour or shade, with necessary screws etc. complete DSR 9.100.1 |
| 46 | Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete, on 20 mm thick bed of cement mortar 1:4 (1 cement: 4 coarse sand).Light shade pigment using white cement DSR 11.20.1 |
| 47 | Providing & laying of light cinder filling under floor of toilets & other sunken roofs. DSR MR |
| 48 | Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry. DSR 22.5 |
| 49 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture DSR 13.62.1 |
| 50 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture on new wood surface. DSR 13.62.1 |
| 51 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with : With 4.0 mm thick glass panes. DSR 10.30.1 |
| 52 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railingwith necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). DSR 10.28 |
| 53 | 15 mm cement plaster on rough side of single or half brick wall finished with a floating coat of neat cement of mix : 1:4 (1 cement: 4 coarse sand) DSR 13.5.1 |
| 54 | Centering and shuttering including strutting, propping etc. and removal of form for all heights Foundations, footings, bases of columns, etc. for mass concrete. DSR 5.9.1 |
| 55 | Centering and shuttering including strutting, propping etc. and removal of form for all heights Suspended floors, roofs, landings, balconies and access platform. with water proof ply 12 mm thick. DSR 5.9.20 |
| 56 | Centering and shuttering including strutting, propping etc. and removal of form for all heights Lintels, beams, plinth beams, girders, bressumers and cantilevers. with water proof ply 12 mm thick DSR 5.9.21 |
| 57 | Centering and shuttering including strutting, propping etc. and removal of form for all heights Columns,Pillars, Piers, Abutments, Posts and Struts. DSR 5.9.6 |
| 58 | 20 mm cement plaster finished with a floating coat of neat cement 1:3 (1 cement :3 C. sand) 13.7.1 |
| 59 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C (Light Point) DSR 1.10.3 |
| 60 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C (Fan Point) DSR 1.10.3 |
| 61 | Wiring point for exhaust fan with 1.5 sq.mm FRLSH PVC insulated multistrand single core Copper Conductor cable in PVC conduit pipe partly concealed in wall & partly laid in slab along with the reinforcement before concreting,complete with 1.5 sq.mm. FRLSH PVC insulated multistrand copper conductor cable as earthwire drawn inside the conduit continuity wire, piano type switch & ceiling rose on 3 mm thick phenolic paminated backelite sheet etc complete in all respects as directed, including matching color wash. DSR 1.10.3 |
| 62 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch socket, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.(Plug and conduit) DSR 1.10.3 |
| 63 | Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated, copper conductor single core cable in surface/ recessed medium class PVC conduit as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire. DSR 1.14.3 |
| 64 | Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated, copper conductor single core cable in surface/ recessed medium class PVC conduit as required. 2 x 6 sq.mm. + 1 x 6 sq.mm. Earth wire DSR 1.14.4 |
| 65 | Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated, copper conductor single core cable in surface/ recessed medium class PVC conduit as required. 4 x 10 sq.mm. + 2 x 6 sq.mm. Earth wire DSR 1.14.10 |
| 66 | Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated, copper conductor single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire. DSR 1.14.2 |
| 67 | Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated, copper conductor single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire. DSR 1.14.1 |
| 68 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. DSR 5.15 |
| 69 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface / recessed conduit / submain wiring / cable as required. DSR 5.18 |
| 70 | Supplying and fixing 5 amps. to 32 amps. rating, 240/415 V, 10kA, \\"C\\" curve, miniature circuit breaker (MCB) suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. single pole 6 - 32 amps.Cat. A DSR 2.10.2 |
| 71 | Supply and fixing of 40 Amp. 4 Pole MCB (10KA) DSR 2.14.2CAT A DSR |
| 72 | Supply and fixing of 63 Amp. 4 Pole MCB (10KA) DSR 2.14.3 |
| 73 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . 4 way (4 + 12), Double door DSR 2.5.1 |
| 74 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4 way (4 + 12), Double door DSR 2.4.1 |
| 75 | Supply and fixing of single pole MCB blanking plate DSR 2.10.1 |
| 76 | Supply, Installation, testing and commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with brush less direct current (BLDC) motor, class of installation B, 3 nos. blades, 30 cm long down rod, 2 nos,canoples, shackle kit, safety rope, copper winding, power factor not less than 0.9, service value (CM/M/W) minimum 6.00, ait delivery minimum 210 Cum.min. 350 RPM ( TOERANCE AS PER is : 374-2019), THD less than 10%, remote or electric regulator unit for control and all remaining accessories including safety pin, nut bolts, washers, temperature rise -75 degree C (max), insulation resistance more than2 mega ohm, suitable for 230 v,50Hz, single phase AC, Supply earthing etc. complete as required. DSR 19.1 |
| 77 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep DSR 1.50.1 |
| 78 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required50 sqmm 3.5 core DSR 9.1.22 |
| 79 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required10 sqmm 2.0 core DSR 9.1.2 |
| 80 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required6 sqmm 2.0 core DSR 9.1.1 |
| 81 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required70 sqmm 3.5 core DSR 9.1.23 |
| 82 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required300 sqmm 3.5 core DSR 9.1.30 |
| 83 | Supplying and drawing following pair 0.5 sqmm FRLS PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface/recessed steel/PVC conduit as required.2 Pair DSR 1.18.2 |
| 84 | Supplying and drawing co-axial TV cable RG-6 graded, 0.7 mm solid copper conductor PE insulated,shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. DSR 1.19 |
| 85 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc as required. Telephone socket outlet DSR 1.24.6 |
| 86 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc as required. TV antenna socket outlet DSR 1.24.7 |
| 87 | Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required. 75mm X 75 mm X 60mm Deep DSR 1.22.1 |
| 88 | Supplying and fixing following size/modules, GI box along with modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mm X 75 mm) DSR 1.27.1 |
| 89 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. DSR 1.26 |
| 90 | Extra for fixing the louvers / shutters complete with frame for exhaust fans of all sizes. DSR 1.51 |
| 91 | Supply and installing of following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, jointed with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required 450mm width x 62.5mm depth x 2.0mm thickness DSR 4.1.10 |
| 92 | Supply and fixing of power plug with 15A/250 V flush type switch and 3 Pin 15 A/250V flush type socket in suitable M.S. box of 175mmx100x50mm size Switch bakellite sheet cover 3mm thick fixed with brass machine screws and cup washer. M.R. |
| 93 | Supply & fixing of 16 gauge M.S.drum duly painted including making hole in the wall for exhaust fan and finishing properly etc. complete as required M.R. |
| 94 | Supply & fixing hexagonal/Round G.P. Fan box of approved make made up of 1.0 mm thick ISI marked G.P. Sheet spot welded four to Eight holes of 25.4mm for pipe entry of the box. Holes should be semi-shuttered type with 0.5mm G.P. Sheet made upper & lower cover duly screwed fitted with 300mm round zink coated M.S. Bar x 12mm & brand name should be embossed. Fixing with wiring conduit laid in the R.C.C. roof before concreting alongwith supply of all material labour, T & P etc required for proper completion of the work. M.R. |
| 95 | Supply & fixing ofrecess/Surface/Pendent mounting round 40 watt LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/Reflector and driver set complete in all respects. MR. |
| 96 | Supply and burying of 40mm dia x 4.5 metres long G.I. pipe, vertically for earthing having 12mm dia. holes spaced 75mm apart drilled up to 2 metre from the bottom complete with earthing lead of No.6 to 8SWG G.I.wire in G.I. pipe upto appron (and from apron to switch board the cost of G.I. pipe and G.I. wire will be extra) upto switch board, 30cm. square C.I.box with hinged cover, masonary housing, alternate layers/of charcoal/ coke and salt at least 150mm thick alround etc. complete in all respects. DSR M.R. |
| 97 | Supplying and fixing of Palm / pin type copper tin plated cables sockets (lugs) to the cable leads, insuslating with tape and making of connections etc. complete in all respects as per direction of Engineer-Incharge. M.R.50 Sq.mm DSR |
| 98 | Supply, installation, testing and commissioning of electrical pane, modular type, front accessible only, free floor standing confirming to Minimum IP:43 degree of protection. The panel sheet structure shall undergo seven tank pre-treatment process before painting. The sheet steel shall be all of 2.2mm thick CRCA sheet. All the openable compartments of the panel shall be completely shrouded and provided with padlocking arrangement on all compartments including bus bar and cable alley chambers. The panel height shall not exceed 2200mm and the maximum operating height for any switchgear shall not be more than 1700mm. The panel shall be provided with minimum 75mm base channel frame fabricated from ISMC sections. All bus bar links in the panel shall be solid bus bars with coloured PVC shrinkable sleeves, no wires will be acceptable. Continuous earth bus shall run alround the panel with earthing studs provided at minimum 2 places. The control wiring shall be carried out with minimum 1.5/2.5 sqmm copper wires and adequate number of NO/NC, potential free contacts incorporated for remote operation of the starters. Proper sized cable termination gland plates shall be provided on cable alleys and knockouts for same shall be provided during fabrication stage itself. The panel shall be provided with a thermostatically controlled heating arrangement (200 W) to take care of high humidity conditions. A 5A socket service outlet (single phase) shall be provided in one of the compartments as ervice outlet in the panel. Panel shall be so designed at to have minimum 20% spare feeders/space. Panel shall undergo epoxy powder coated paint, colour as per IS:5 requirement. All cable terminations shall be from top. The complete panel shall be fuse less type, for control circuits 2A/6A MCB's to be used. All bus bars shall be of aluminium, electrolytic grade only. Maximum design density shall not exceed 1 Amps/Sqmm. All bus bars shall be insulated with coloured heat shrinkable PVC sleeved. All bus bar supports shall be non hygroscopic DMC/SMC supports.The panel shall be manufactured in conformance to requirements of local electrical inspector and it shall be contractors responsibility to get initial approval of drawings and also final approval of complete electrical works related to this section. 32 amp SP MCB 3 No. The minimum clearances between bus bars shall be as follows : Phase to phase - minimum 20mm Phase to neutral-minimum 15mm L.T.PANELIncoming One (1) No 200 A 4 pole Metering :One (1) No. (0-500V) 96 x 96 Sqmm voltmeter with control fuse & selector switch. One (1) No. (0-200A) 96 x 96 Sqmm CT operated Ammeter with selector switch, CTs etc. One (1) Set of Phase Indication Lamp. Bus Bar :One (1) No.200 A, TPN aluminimum bus bar of suitable length. Outgoing : Phase indication lamps on each outgoing to be provided. 100Amps TPN - 1No. 63Amps TPN - 3Nos OR outgoing as per site requirment |
| 99 | SUB DISTRIBUTION BOARD 6 Way VERTICAL TPN Incoming 80 amp TPN MCB 1 No.Outgoing: 40 amp TP MCB 1 No. 32 amp SP MCB 3 No. |
| 100 | Supply & fixing of 7/9 W LED BULB complete in all respect. Make:C&S Electric or Eq N.S |
| 101 | Supply and Fixing of LED Tube Light with batten suitable for up to 1X20/22 watt LED tube light fitting complete including tube on surface complete in all respect. Make:C&S Electric or Eq DSR N.S |
| 102 | Supply & erection of AC 230/250 Volts, 50 Hz exhaust fans including providing nuts, bolts, mounting frame and other accessories including connections etc. complete as required-Make: USHA Cat No. TURBO JET DLX DSR 300mm sweep. N.S |
| 103 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required.Same as above but for European type W.C. pan with white plastic seat and lid.Make- Cera,Hindware. DSR DSR-17.1.1 |
| 104 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require. a) White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tappillar tap. DSR 17.7.4 |
| 105 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. Flexible pipeSemi rigid pipe b) 40mm dia DSR 17.28.1.2 |
| 106 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. DSR 17.31 |
| 107 | Providing & fixing PTMT towl rail complete with brackets fixed to wooden cleats with cp brass screws with concealed fitting arrangement of approved quality and colour. 600 mm. long towl rail length of 645 mm. width 78 mm. and effective height of 88 mm, weighing not less than 190 gms. DSR 17.73.2 |
| 108 | Providing and fixing PTMT Liquid soap container 109 mm wide ,125 mm high and 112 mm distance from wall of standerd shape with bracket of the same material with snap fittings of approved quality and colour weighing not less than 105 gms DSR 17.71 |
| 109 | Providing and fixing CP Brass 32mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in-charge. DSR 17.22 A |
| 110 | Providing & fixing soil, waste and vent pipes.b) 100mm dia centrifugally cast iron S & S pipe. DSR 17.35.1 |
| 111 | Providing & fixing soil, waste and vent pipes.b) 75mm dia centrifugally cast iron S & S pipe. DSR 17.35.2 |
| 112 | Providing lead caulked joints to sand cast iron/centrifugally cast (spun) iron pipes & fitting of diameters.a) 100mm DSR 17.58.1 |
| 113 | Providing lead caulked joints to sand cast iron/centrifugally cast (spun) iron pipes & fitting of diameters.b) 75mm DSR 17.58.2 |
| 114 | Providing & fixing M.S. holder bat clamps of approved design to sand cast iron/centrifugally cast (Spun) iron S & S pipe embeded in & including cement concrete blocks 10x10x10cm. of 1:2:4 mix (1 cement : 2 coarse : 4 graded stone aggregate 20mm nominal .size). Including cost of cutting holes & making good the walls etc.a) for 100mm dia pipe. DSR 17.37.1 |
| 115 | Providing & fixing M.S. holder bat clamps of approved design to sand cast iron/centrifugally cast (Spun) iron S & S pipe embeded in & including cement concrete blocks 10x10x10cm. of 1:2:4 mix (1 cement : 2 coarse : 4 graded stone aggregate 20mm nominal .size). Including cost of cutting holes & making good the walls etc.b) for 75mm dia pipe. DSR 17.37.2 |
| 116 | Providing & fixing cast iron trap of self cleansing design with or without ventarm complete, including cost of cutting & making good the walls & floors.a) 100mm inlet & 75mm outlet. DSR 17.60.1 |
| 117 | Providing & fixing cast iron coller.a) 100mm dia. DSR 17.57.1 |
| 118 | Providing & fixing cast iron coller.b) 75mm dia. DSR 17.57.2 |
| 119 | Providing and fixing plain cast iron S & S sanitary bend.a) 100mm DSR 17.39.1 |
| 120 | Providing and fixing plain cast iron S & S sanitary bend.b) 75mm DSR 17.39.2 |
| 121 | Providing and fixing bend of required degree with access door, insertion rubber washer 3mm thick, bolts and nuts complete.a) 100mm DSR 17.38.1.1 |
| 122 | Providing and fixing bend of required degree with access door, insertion rubber washer 3mm thick, bolts and nuts complete.b) 75mm DSR 17.38.2.1 |
| 123 | Providing and fixing centrifugaly cast iron single equal plain junction of required degree.a) 100x100x100mm DSR 17.44.1.2 |
| 124 | Providing and fixing centrifugaly cast iron single equal plain junction of required degree.b) 75x75x75mm DSR 17.44.2.2 |
| 125 | Providing and fixing cast iron single unequal plain junction of required degree.a) 100x100x75mm DSR 17.47.1.2 |
| 126 | Providing and fixing cast iron terminal guard.a) 100mm DSR 17.56.1 |
| 127 | Providing and fixing cast iron terminal guard.b) 75mm DSR 17.56.2 |
| 128 | Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50mm hard wood plugs, screwed with M.S. screws of required length including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete.a) 110mm DSR 12.43.2 |
| 129 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.(Internal work)Exposed on walla) 25mm dia nominal bore (medium duty) DSR 18.7.3 |
| 130 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.(Internal work)Exposed on wallb) 32mm dia nominal bore (medium duty) DSR 18.7.4 |
| 131 | Concealed pipe including painting with anticorrosive bitumatic paint, cutting chases and making good the wall.a) 15mm dia nominal bore DSR 18.8.1 |
| 132 | Concealed pipe including painting with anticorrosive bitumatic paint, cutting chases and making good the wall.b) 20mm dia nominal bore DSR 18.8.2 |
| 133 | Providing and fixing 45 cm long unplasticised PVC connection pipe with brass unions.a) 15mm nominal bore DSR 18.21.2.1 |
| 134 | Providing & fixing CP brass bib cock of approved quality conforming to IS 8931 a) 15mm nominal bore DSR 18.49.1 |
| 135 | Providing & fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.a) 15mm nominal bore DSR 18.51.1 |
| 136 | Providing & fixing C.P. brass angle valve for basin mixer and gyser points of approved quality conforming to IS 8931a) 15mm nominal bore DSR 18.53.1 |
| 137 | Providing and fixing gun metal gate valve with wheel of approved quality.a) 25mm dia nominal bore DSR 18.17.1 |
| 138 | Providing and fixing brass stop cock of approved quality.a) 15 mm nominal bore DSR 18.16.1 |
| 139 | Providing and fixing brass stop cock of approved quality.b) 20 mm nominal bore DSR 18.16.2 |
| 140 | Excavating trenches in all kind of soil of required width for pipes, cables etc. including excavation for sockets and dressing of sides, ramming of bottoms, depth upto 1.5 m. including getting out the excavated soil & then returning the soil as required,in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering, etc & disposig of surplus excavated soil as directed within a lead of 50m.a) Pipes 80mm to 300mm diameter. DSR 2.10.1.2 |
| 141 | Providing, laying and joining glazed stone ware pipes grade 'A' with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete.a) 100mm diameter DSR 19.1.1 |
| 142 | Providing, laying and joining glazed stone ware pipes grade 'A' with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete.b) 150mm diameter DSR 19.1.2 |
| 143 | Providing, laying and joining glazed stone ware pipes grade 'A' with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete.c) 200mm diameter DSR 19.1.3 |
| 144 | Providing & laying cement concrete 1:5:10 (1 cement :5 coarse sand :10 graded stone aggregate 40mm nominal size) alround S.W. Pipes including bed concrete as per standard design.a) 100mm diameter S.W. Pipe DSR 19.2.1 |
| 145 | Providing & laying cement concrete 1:5:10 (1 cement :5 coarse sand :10 graded stone aggregate 40mm nominal size) alround S.W. Pipes including bed concrete as per standard design.b) 150mm diameter S.W. Pipe DSR 19.2.2 |
| 146 | Providing & laying cement concrete 1:5:10 (1 cement :5 coarse sand :10 graded stone aggregate 40mm nominal size) alround S.W. Pipes including bed concrete as per standard design.c) 200mm diameter S.W. Pipe DSR 19.2.3 |
| 147 | Providing and fixing square mouth S.W. Gully trap grade 'A' complete with C.I. grating brick masonry chamber with F.P.S. bricks of class designation 75 and water tight C.I. cover with frame of 300 x 300mm. size (inside) the weight of cover to be not less than 4.50 Kg and frame to be not less than 2.70 Kg as per standard design.a) 150 x 100 mm. size P typeWith bricks class 150 conforming to IS : 4885 DSR 19.4.1.2 |
| 148 | Constructing brick masonry manhole in cement mortar 1:4 (1 cement :4 coarse sand) RCC top slab with 1:2:4 mix (1 cement :2 coarse sand :4 graded stone aggregate 20mm nominal size), foundation concrete 1:4:8 mix (1 cement :4 coarse sand :8 graded stone aggregate 40mm nominal size) inside plastering 12mm thick with cement mortar 1:3 (1 cement :3 coarse sand) finished with floating coat fo neat cement and making channels in cement concrete 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 20mm nminal size) finished with a floating coat of neat cement complete as per standard design Inside size 90x80cms and 45cms deep including CI cover with frame (light duty) 455x610mm internal diamensions total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15kg).With FPS bricks of class designation 150(i) For Sewer Line DSR 19.7.1 |
| 149 | SITC of Singal Headed Hydrant Landing Valve comprising of 80 mm dia flanged Bend 63 mm dia, with cap and chain conforming to IS:5290(Make : Newage/Minimax/Safex/Firex) DSR-18.9.1 |
| 150 | SITC of RRL Hose Pipe 63 mm dia × 15 Mtr. Long with GM Coupling conforming to IS : 636(Make - Newage/Jayshree/CRC) DSR- 18.16.1 |
| 151 | SITC of Short Branch Pipe as per IS:903(Make : Newage/Safex/Firex) DSR-18.18.1 |
| 152 | SITC of Hose Cabinet Box of 18 SWG M.S.Sheet with glass to accommodate Hose Reel Drum with Ruber Pipe with Nozzle. 2 Nos. RRL Hose and 1 No. Branch Pipe with Nozzle MR |
| 153 | Providing and fixing MS Pipes conforming to IS:1239 (Medium- B class) including all fittings like anchor fasteners, brick masonry supports, couplings, bends, elbows, tees and flanges etc. welded or screwed joints as required, cutting holes and chases in brick or RCC walls and making good complete. (For Riser) DSR-18.8.7100mm dia |
| 154 | Supply, installation, testing and commissioning of Manual Swing Type First aid Fire Hose Reel conforming to IS: 444 complete with all other necessary fixing accessories. DSR -18.17.2 |
| 155 | Supply of Fire Man Axe. |
| 156 | SITC of Air cushion Tank (2000x1000)mm. |
| 157 | SITC of Air Release Valve. |
| 158 | Supply, Installation, Testing & Commissioning of NRV complete with flanges, gasket and nut bolts. DSR -16.11.2.2150 mm |
| 159 | SITC of Butterfly Valve complete with all respect. DSR-16.11.1.2150 mm |
| 160 | Supply, Installation, Testing & Commissioning of Pressure Gauge with gauge cock DSR-16.8 |
| 161 | Supply, Installation, Testing & Commissioning of Fire brigade inlet with 63 MM dia instantaneous inlet complete with all necessary fittings and MS enclosure with glass door made of 18/16 SWG sheet.2 way |
| 162 | Supply, fixing , testing & commissioning of electrical motor driven fire pump suitable for automatic operation consisting of following : (Terrace Pump) (Make : Kirloskar/Mather+Platt)(a) Horozontally mounted, split casing, Centrifugal fire pump complete for delivery of under mentioned discharge against desired mentioned head so as to ensure a minimum pressure of 30 meter at the highest and farthest outlet at the specified flow cmplete with necessary strainers, pressure gauge including bypass arrangement for periodic testing of the working of the pumpset with required length and size of medium class GI pipe and control valves for proper completion of work. The pump shall be capable of giving 150% of rated discharge at head not less than 65% of rated head. The pump shall be provided with Mechanical seals. The impeller shall be enclosed type and accurately blanced dynamically. The pump casing shall be of cast iron, impeller shall be of bronze and shaft shall be of stainless steel.(b) Squirrel cage, TEFC induction motor suitable for 415 V, 3 phase having IP 55 protection and class 'B' insulation for the above pump and flexible coupling with the pump. The motor shall b rated for continuous duty and shall have HP rating necessary to drive th pump at 150% of it's rated discharge at 65% of rated head.© Common bed plate of fabricated mild steel channel or cast iron type.(d) Suitable cement concrete pump foundation and vibration clamping arrangement as required with foundation bolts, anti vibration pads, washers etc.(e) Pressure switch for automatic operation of motor including necessary wiring upto control panel.(f) Electrical Control panel with starter, 3 Pole motor protection category current limiting type MCCB, indicating light, ammeter, voltmeter, selector switches, CT's protective fuses, single phasing protection, dry suction cut off etc as requrd as per standard details.Discharge :450 liter per minuteHead : 35 meter DSR - 18.4.2 |
| 163 | Supply and fixing of ABC type (4 kg.) ISI Marked 1131 |
| 164 | Supply and fixing of CO2 gas type (4.5 kg.) ISI Marked 1132 |
| 165 | Supply and fixing of self glow type exit signage |
| 166 | Construction of granular sub-base by providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge. With material conforming to Grade-I (size range 75 mm to 0.075 mm) having CBR Value-30 16.78.1 |
| 167 | Providing and laying 60mm thick faciory made cement concret interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with line sand etc. all complete as per the direction of Engineer-in-charge.DSR 16.68 |
| 168 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and for all lift, as dire (2.6.1) |
| 169 | First class brick work in 1:4 cement and coarse sand of 2.25 fineness modulus) mortar in foundation & plinth including supply of all materials, labour and T & P etc. (6.4.1) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 30, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 24, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysOct 24, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 19 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender