Power Government Departments Closing in 6 days TDR #57794603

Tender For Construction Of 220/132Kv, 160Mva And 132/33Kv, 31.5Mva Substation At Palana (Distt.-Bikaner) Including Survey Supply Of All Equipments/Materials, Erection (Including Civil Works), Testing And Commissioning On Turnkey Basis Against Specifi

Issued by Government Departments · Jaipur, Rajasthan
Tender Value
43.98 Crore
Estimated cost
Bid Submission
18 Nov 2026
6 days left
EMD
87.95 Lakhs
Bank guarantee accepted
Document Fee
17700
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Jaipur → Rajasthan
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Construction Of 220/132Kv, 160Mva And 132/33Kv, 31.5Mva Substation At Palana (Distt.-Bikaner) Including Survey Supply Of All Equipments/Materials, Erection (Including Civil Works), Testing And Commissioning On Turnkey Basis Against Specification No. Rvpn/Ehv/Bn-9019002602.

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 03-Nov-2026 Extension in due dates Date 18-Nov-2026

BOQ

Name of Work:- Construction of 220/132kV, 160MVA and 132/33kV, 31.5MVA substation at PALANA (Distt.-Bikaner) INCLUDING SURVEY SUPPLY OF ALL EQUIPMENTS/MATERIALS, ERECTION (INCLUDING CIVIL WORKS), TESTING AND COMMISSIONING on Turnkey basis AGAINST SPECIFICATION NO. RVPN/EHV/BN-9019002602.
Sl. No. Item Description
1MAIN MATERIAL/ ITEMS
2Circuit Breaker
3220kV circuit breakers (3 Ph.) Along with support Structure
4220kV circuit breakers (3 Ph.) Along with support Structure
5132 kV Circuit Breakers
6132 kV circuit breakers (3 Ph.) Along with support Structure
71250 A, 40 kA
833 kV Circuit Breakers
933 kV circuit breakers (3 Ph.) Along with support Structure
101600 A, 31.5kA
11Instrument Transformers
12Capacitor Voltage Transformer
13Single-Phase, 220 kV, 4400 pf CVT
14Single Phase 132 kV , 4400 pf CVT
1533 kV Potential Transformer
1633/√3 kV /110-110√3
17Current Transformer (1-Phase)
18220 kV CT
191000/1 A, 5C
20132 kV CT
211000/1 A, 3C
22500/1 A, 3C
2333 kV CT
241000/1 A, 4C
25500/1A, 2C
26C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II)
27New Substation
28Control Panel for 220 kV Transformer (220 kV Side) Type: SAS-THCB
29Relay Panel for 220 kV Transformer (for both HV & MV) Type: SAS-THRB
30Control Panel for 220 kV Feeder Type: SAS-FCB
31Relay Panel for 220 kV Feeder Type: SAS-FRB
32Control Panel for 220 kV Bus Coupler Type: SAS-BCCB
33Relay Panel for 220 kV Bus Coupler Type: SAS-BCRB
34220 kV Busbar Protection Relay Panel Type: SAS-BBRB
35Control Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLCB
36Relay Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLRB
37Control and Relay Panel for 1x 50/31.5/25 MVA, 132/33 kV Power Transformer Type SAS-TCRA
38Control Panel for 132 kV Feeder Type SAS-FCA
39Relay Panel for 132 kV Feeder Type SAS-FRA
40Control and Relay Panel for 132 kV Bus-Coupler Type SAS-BCRA
41Control and Protection Panel for 33 kV Feeder (I/C, O/G)/Bus-coupler/ Capacitor Bank [For TWIN FEEDER/BAY] Type-FCRD
42Station HMI [Industrial grade Computer with 21\\"TFT monitor as per specification requirements]
43Station HMI (Hot Standby)[Industrial grade Computer with 21\\"TFT monitor as per specification requirements]
44HMI View Node[Industrial grad Computer with 21\\"TFT monitor as per specification requirements]
45A3 Size B&W Laser Printer
46Substation Automation System Network Panel Type SAS-NW
47Modems (both sending and Receiving End) for communication to RCC & Sub SLDC for PLCC]
48Data Concentrator Unit (DCU) at Substation for RAS mounted in suitable enclosure & fully wired
49Software: Application as well as System Software as per specification requirements for various hardware elements for meeting of functional requirement of the specification.
50Substation Auxiliary Monitoring Panel Type SAS-SAMP
51Other Items:
52Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the Substation LAN as per specification requirements.
53Transducers, Sensors etc. (if not considered in the respective equipment/ items) for accumulating monitoring data as per the specification requirements for switchyards.
54Surge Arresters
55220 kV LA
56132 kV LA
5733 kV LA
58Substation LT Transformer
5933/ 0.433 kV, 250 kVA LT transformer complete with all accessories, fittings, terminal connectors etc as specified filled with transformer oil
60Batteries & Battery Charger
61Batteries (Sizing shall be as per requirement of technical specification)
62220 V [Min. 600 AH]
6348 V [Min. 600 AH]
64Battery Charger System
65220 V Float and Boost
6650 V Float and Boost
67Lighting System
68Outdoor Lighting & other Works
69Lighting Fixture Type FL-1
70Lighting Fixture Type FL-2
71Outdoor Receptacle
72Type-RP
73Type-RO
74Substation Premises Lighting
75Lighting poles
76Type-L1
77Type-D1
78Street Lighting Type-SL-L1 for mounting on poles
79Street Lighting Type-SL-D1 for mounting on Poles
80Sub-Lighting Boxes/Panels Type -SLP at Lighting Mast and Other Loaction as designated complete with all controgears and accessories, items etc.
81Lighting Panel Type ACP-2 as per technical specification
82Lighting Panel Type ACP-3 as per technical specification
83Indoor Lighting & Other Works
84Electrification
85Electric Fitting (if not covered under Civil Works) with G.I. Conduit, Junction Boxes, pull out boxes, copper wiring, Modular Switchboards, Modular Switches, GI Wire (16SWG) etc. for control room, Hall and administrative office building as per the requirements of the specifications
86Illumiation
87Lighting fixtures and Receptacles (including accessories/ materials etc. as per requirement alongwith complete accessories and mounting arrangements)
88Indoor Lignting Panels
89Lighting Panel (Indoor) Type ACP-1 as per technical specification
90Lighting Panel (Indoor) Type DCP as per technical specification
91Wall mounted fans Approx. 400 mm sweep
92Ceiling Fan - Approx. 1400mm sweep with electronic Step regulator
93Exhaust Fans
94Fire Extinguisher DCP Type
95i) 5 Kg.
96ii) 10 Kg.
97Carbon di oxide type – 6 Liters.
98Foam Type- 9 Liters
99Sand type
100i) GI Buckets 9 liters capacity
101ii) Steel Stands for four buckets
102Air Conditioning System
103Air Conditioning for the Rooms specified in the specifications
1041.1kV Grade PVC insulated Al. conductor FRLS power cables and copper conductor armoured FRLS control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room and other building]
105Power Cables(XLPE)
1061Cx630 sq.mm
1073.5Cx300 sq.mm
108Power Cable(PVC)
1091Cx150 sq.mm
1103.5Cx70 sq.mm
1113.5Cx35 sq.mm
1124Cx16 sq.mm
1134C x 6 Sq. mm
1142C x 6 Sq. mm
115Control Cable (PVC)
1164 CX4 Sq. mm
1173Cx2.5 sq.mm
1185Cx2.5 sq.mm
1197Cx2.5 sq.mm
12010Cx2.5 sq.mm
12114Cx2.5 sq.mm
12219Cx2.5 sq.mm
123Substation Structures
124Standard Lattice Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for lattice steel structure as per specification requirements]:
125NON Standard Pipe support Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for Pipe support structure as per specification requirements]:
126Isolators (Moterized)
127220 kV (3-Phase) (Horizontal DOUBLE BREAK)
1281600A, 50KA, isolator with one E/S
129Post insulators for above Isolator
1301600A, 50KA, isolator with two E/S
131Post insulators for above Isolator
1321600A, 50KA, isolator without E/S
133Post insulators for above Isolator
1341600A, 50KA, isolator without E/S (TANDEM Type)
135Post insulators for above Isolator
136132 kV (3-Phase) (Horizontal DOUBLE BREAK)
1371250A, isolator with two E/S
138Post insulators for above Isolator
1391250A, isolator with one E/S
140Post insulators for above Isolator
1411250A isolator without E/S
142Post insulators for above Isolator
14333 kV (3-Phase) (Horizontal DOUBLE BREAK)
1441250A, isolator without E/S
145Post insulators for above Isolator
146800 A isolator without E/S
147Post insulators for above Isolator
148800A isolator withE/S
149Post insulators for above Isolator
150Switchyard Erection
151Busbar & Interconnections
152New Substation/ Switchyard
153220 kV Switchyard Works:
154Main-I Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/Porcelain Long Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
155Main-II Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Pocelain Long Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
156Aux Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string(DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
157220 kV Overhead Jack Bus (for DMT Layout) on Twin ACSR Zebra(Bus-Coupler Bay)/ Single ACSR Zebra (Transformer/ Line on ACSR Zebra) with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
158Twin ACSR Zebra
159Single ACSR Zebra
160Equipment Interconnections to Main Bus, Overhead Bus including Single ACSR Zebra (for Line), Twin ACSR Zebra (forTransformer bay & B/C Bay), bus-bar materials, clamps, connectors, spacers, corona shields, including equipment connectors, Junction box including of all accessories etc. for the following:
161220 kV DMT-type layout
162Line bay
163Transformer bay
164Bus-Coupler
165Bus CVT Interconnections to Main Buses including Single ACSR Zebra, clamps, connectors, junction box including of all accessories etc.
166132 kV Switchyard Works:
167Main Bus: 132 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulator, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays]
168Aux Bus: 132 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays]
169132 kV Overhead Jack Bus (for Main & Aux Layout) on Twin ACSR Zebra(220 kV Transformer/Bus-Coupler Bay), Single ACSR Zebra(132 kV Transformer/Bus-Coupler Bay) Single ACSR Panther (Line on ACSR Panther) on Single Panther ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
170Twin ACSR Zebra
171Single ACSR Zebra
172Single Panther
173Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Zebra (Bus Sectionalizer/ 220 kV Transformer /Bus-Coupler Bay)/ Single ACSR Zebra (132 kV Transformer Bay) Single ACSR Panther ( Line on ACSR Panther), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
174132 kV Main & Aux-type layout
175Line bay
176Transformer bay
177Sectionlizer
178Bus-Coupler
179Bus CVT Interconnections to Main Bus including Single ACSR Zebra, clamps, connectors, junction box including of all accessories etc.
18033 kV Switchyard Works:
181Main Bus: 33 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays+ Bus Coupler]
182Aux Bus: 33 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays+ Bus Coupler]]
18333 kV Overhead Jack Bus for Transformer Incomer (for Main & Aux Layout) on Twin Zebra ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
184Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Panther ( Transformer /Bus-Coupler Bay)/ Single ACSR Panther ( Line bays), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
18533 kV Main & Aux-type layout
186Line bay
187Transformer bay
188Sectionlaizer
189Bus-Coupler
190LT Transformer connection with ACSR Panter conductor, 33 kV DO Fuse Set alongwith required Clamp/connectors
191Bus PT Interconnections to Main Bus including Single ACSR Panter , clamps, connectors, junction box including of all accessories etc.
192Bus Post Insulators (BPI)
193220 kV
194132 kV
19533 kV
196Earthing & Lightning Protection System
197Main, Auxilary Earthmats, Risers etc. for complete earthing in the Switchyard Area
19828 mm Dia MS Rod
19928mm Dia, 3.2 M Long MS Rod Earth Electrodes Directly Driven.
20028mm Dia, 8 M Long MS Rod Earth Electrodes Directly Driven.
20128mm Dia, 3.2M Long MS Rod Earth Electrode in untreated pit with test link
20228 mm dia, 3000 mm long GS pipe electrodes with test links and treated earth pits with C.I. cover hinged to C.I. frame alongwith all associated civil works
20350X12 mm GS Flat
20450X6 mm GS Flat
205Earth Enhancing Compound for treated pits as above and other requirement as per specification
206Cleat type clamps(8mm thick) for earthing down conductor (10.98 mm dia), 50x12 mm GS Flat and 50x6 mm GS flat
207Cu/Al Flexible braids Grounding Conductor connection to MS/GS Flats
208Earth Wire for Shielding Protection of Switchyard
2097/3.15 Galvenized Steel Wire
210Earthwire tension clamps with D Shackle assembly
211PG calmp to suit 7/3.15 mm GS earth wire
212Cleat clamp on structure to suit 7/3.15 mm GS earth wire/ 50 X 12 mm GS Flat
213Pad clamp on structure to suit 7/3.15 mm earth wire and 75 x 12 GS flat
214Lug to suit 7/3.15 mm earth wire
215Other Clamps, Copper Earth Bond etc. as per layout diagram for erection of Earth Wire
216Bay Marshalling KIOSK
217200 way (Stud Type Connectors)
218AC Distribution Boxes (Outdoor Type)
219Outdoor AC Distbibution Box (Double Front type)
220Outdoor AC Distbibution Box (Single Front type)
221Conduits, Cable Trays [Perforated and Ladder Type], Cable Tags, Cable Clamps, Cable Lugs,Cable sealing system, Gland Plates, Junction Boxes, PVC pipes, hume Pipes, Nylon type Trefoil Clamps etc.[Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room and other building]
222Other Steel Structures/ members [items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washers etc. considered for this component of price schedule] to be designed/ provided by the bidder for the completion of project [This shall not include the steel to be used in the civil works]
223LT Switchgear
224LT AC Main Panel
225LT AC Distribution Board
226Main Lighting Distribution Board
227Emergency Lighting Distribution Board
228220V DCDB
22948V DCDB
230PLCC EQUIPMENTS
231220 kV Wave trap (1250A, 0.5 mH, 40 kA)
232132 kV wave trap (1000A, 0.2 mH, 40 kA)
2334 kH to 16 kHz Channel Digitial PLCC Carrier terminal with digital protection coupler (DTPC) IEC/101/104 data and 4 W E&M speech applications .
2344 kH to 16 kHz Channel Digitial PLCC Carrier terminal with out digital protection coupler (DTPC) IEC/101/104 data and 4 W E&M speech applications .
235VFT equipment (Modem) suitable for transmission of Data through PLCC links based on frequency shift keying modulation techniques programmable for both baud rate from 50 Baud to 2400 Baud and center frequency through switches or jumpers (A.F. Shift Channel)
236Coupling Devices for Phase to Phase coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level.
237Coupling Devices for Phase to Ground coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level.
238HF Armoured Coaxial cable having 75 Ohms unbalanced impendance.
239Microprocessor based 24/8 line Electronic Private Automatic Exchange (EPAX) with PLCC interphasing facility
240Telephone Sets (Push Button Type)
24110 pair Jelly Filled and armoured telephone cable with copper conductor of 0.5 mm
2425 Pair jelly filled armoured telephone cable having copper conductor of Dia. 0.5 mm
2435 Pair jelly filled un armoured telephone cable having copper conductor of Dia. 0.5 mm
244TESTING & MEASURING INSTRUMENTS, TOOLS & TACKLES AND MISCELLANEOUS ITEMS
245(A) TESTING EQUIPMENT/ INSTRUMENTS [This shall consist of all the standard accessories, cables, software etc. required for satisfactory operation of equipment meeting functional requirements]
246Insulation Tester (5000 Volts, Digital)
247SF6 Leakage Detector
248Digital Multimeter
249Digital Clamp Meter
250Level meter cum Generator incliding impedance return loss
2514-1/2 digit LCD Multimeter with input impedance of 10Mohm & with a range of 0.1 mV to 1000 V DC, 0.1mV to 600v AC, 0-10 AMP AC,(40hz to 10KHz) & 0-20 Mohm With builtin power –supply.
252(B) Maintenance Tools& Tackles
253Oil Sampling Bottle (1 Liter Capacity)
254Vaccum Cleaner
255Telescopic ladder aluminium 6 meter height
256Ring spanner set
257Tube spanner set
258Pipe wrench 24 inch
259Pipe wrench 18 inch
260Hydraulic crimping tools up to 630 sq.mm
261Threading die set for pipe threading
262Welding machine (arc welding) 10kVA
263Heavy duty drilling machine
264Bench Vice
265Insulated cuttingplier 12 inch
266Insulated cuttingplier 8 inch
267Screw driver 18 inch
268Screw driver 12 inch
269Hammer 8 lbs
270Hammer 2 lbs
271Chain pulley block 5 ton
272Pipe derrick
273Allen Keys
274Box Spanners
275(C )Office and Miscellaneous Equipments/ Items
276Insulation Rubber mat (1mX2mX 12 mm)
277Isulation Rubber Gloves (33 kV Tested)
278Furniture for Control Room Building:
279SCADA Room Furniture (Control Desk for specified consoles and Revolving Chair) matching with the overall interiors as per specification
280Executive Desk bulit in wood and steel with lockable drawings on both side (6 feetX2 ½ feetx 2 ½ feet)
281Junior executive table with three drawings on right side One Cup board left side with prelaminated decolam top 20mm thick over painted M.S. Frame ( 4 ½ feet x 2 ½ feetx 2 ½ feet).
282Library Shelf with Glass Door (min 4 Shelf)
283Steel tubular “S” type with continuous and one feet dia 14guage pipe, cane seat backing, teak wood with quality cane.
284Archival Storage 4 Drive Type
285Lateral Filing Cabinets
2863 Drawer Unit
2874 Drawer Unit
288Steel Almirah of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 22 guage or better with two way locking system.
289Steel Almirah (with Glass doors) of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 22 guage or better with two way locking system.
290Minor Almirah of size 4 ½ feet x30 inch x 17 inch with three shelves making four compartments in 22 guage or better with two waylocking system.
291Steel rack of size 5 feet x 3 feet x 16 inches with six shelves making five compartments (22 guage).
292Steel file trays of size 16 inches x11 inches x 3 inches of guage 14 SWG.
293Steel stools of size 15 inch x15 inch x 18 inch square pipe 16 guage
294Steel waste paper baskets of size 12 inch (H) and Approx. 10 inch Dia Round.
295Key board (wooden) with Glass door
296First Aid Box
297Shock Treatment Chart [Laminated with Frame]
298Safety Instruction Boards [ Laminated with Frame]
299(D) Drinking Water Arrangement
300Water Cooler (Storage type, Storage Capacity 40 Ltr, Cooling Capcity 20 Ltr./hr)
301RO/ Water Purifier
302Refrigirator (380 Lt.)
303Substation Name Board [1 No. Glow Type & 1 No. Painted Type] [Size and Color etc. be got approved from owner]
304Danger Plate [Size and Color etc. be got approved from owner]
305MANDATORY SPARES
306(A )Circuit Breakers
307220 KV
308(One pole of circuit breaker complete with pole column and interrupter with M.B. but without support structure and operating mechanism.
309Rubber gaskets, ‘O’ rings and seals
310Fixed Contacts
311Moving Contacts
312Terminal pads and connectors
313Closing Assembly Valve
314Trip Assembly Valve
315Auxiliary Switch Assembly
316Operation Counter
317Closing Coils
318Tripping coils
319Support insulator complete for one pole of breaker
320145 kV
321One pole of circuit breaker without support structure and operating mechanism.
322Rubber gaskets, ‘O’ rings and seals
323Fixed Contacts
324Moving Contacts
325Terminal pads and connectors
326Closing assembly valve
327Trip assembly valve
328Auxiliary switch assembly
329Operation counter
330Closing Coils
331Tripping coils
332Support insulator (set complete for one pole of breaker)
333Instrument Transformer
334Spare of 245kV Capacitive Voltage Transformer
335(i) Complete CVT
336Spare of 145kV Capacitive Voltage Transformer
337(i) Complete CVT
338Spare of 245kV Current Transformer
339(i) Complete CT [1 No. each type supplied)
340Spare of 145kV Current Transformer
341(i) Complete CT (1 No. each type supplied)
342Spare of 33 kV Current Transformer
343(i) Complete CT (1 No. each type supplied)
344(E) C&R panels (similar items as used in the quoted panels)
345Bay Control Unit (220 kV Side of offered type)
346Bay Control Unit (132 kV Side of offered type)
347Bay Control & Protection Unit (33 kV Side of offered type)
348Bay Unit (For 220 kV Busbar Protection of offered type)
349Bay Protection Unit (Distance for 220 kV Feeders of offered type)
350Bay Protection Unit (Line Distance cum Differential for 220 kV Feeders of offered type)
351Bay Protection Unit (Distance for 132 kV Feeders of offered type)
352Bay Protection Unit (Differential for 220 kV Transformers of offered type Main-I)
353Bay Protection Unit (Differential for 220 kV Transformers of offered type-Main-II)
354Bay Protection Unit (Differential for 132 kV Transformers of offered type)
355Bay Protection Unit (Back-up Overcurrent & E/F of offered type)
356Breaker failure relay (numerical type)
357Trip circuit supervision relay
358Self reset trip relay
359Hand reset trip relay
360Timer relay
361DC supervision relays
362Flag relays
363Auxiliary relays
364Multifunction Panel Meter
365Fiber Optic Cable with Connectors
366Transducers (Each Type used in the autoamtion system)
367Ethernet Switch (of offered type)
368(F) Station Transformer
36910% of total Transformer Oil quantity in non-returnable drums
370HV bushing
371LV bushing
372Pressure relief device
373Tap charger contact
374Set of valves
375Set of gasket
376Silica gel required for five replacements
377(G) Surge Arrester
378220kV class 198 kV rating LA complete as specified.
379132kV class 120 kV rating LA complete as specified.
38033 kV Class of 30kV rating LA Complete as specified
3812 Nos. Terminal connector of each type as spare
382(H) Battery & Battery Charger
383220 V & 48 V Type Battery
384Spare battery cell without electrolyte
385Terminal connectors with bolts & Nuts
386Float level indicators
387Vent Plugs
388220V/ 50V Battery Chargers
389Set of Control Cards
390Set of relays
391Set of contactor
392Micro-switches
393Filter Capacitors
394Thyristor/ Diode
395Set of switches
396Set of wound resistors
397Potentiometers
398Fuses of Thyristor with indicators
399(I) L.T. SWITCHGEAR :
400Relays
401CTs AND PTs
402Switches/Push buttons and Meters
403TPN Switches/MCB
404L.T. Breaker spares
405a) Spring charging motor
406b) Aux. Contact sets
407c) Busbar Seal off insulators
408d) Arc-chutes
409e) Moving contacts
410f) Arcing contacts (Fixed/Moving)
411g) Springs (Closing/Opening)
412h) Closing coil
413i) Tripping coil
414j) Aux. finger contact
415k) Limit switches
416l) Jaw contacts
417Busbar
418a) Busbar insulators
419b) Interphase barrier
420c) Busbar strip 1mm (Aluminium)
421(J) LIGHTING SYSTEM
422Single Pole MCB
423Triple pole MCB
424Fluorescent tube & Starter
425a) Choke
426b) Bottom Strips
427c) Top covers & reflector (if applicable)
428d) Holders
429e) Complete fittings
430Sodium vapour/Mercury vapour Lamps a) Lamp
431b) Ballast
432c) Condenser/ Igniter
433d) Lamp holder
434e) Lamp holder
435f) Complete fittings
436Incandescent lamp
437a) Bulbs
438b) Holders
439c) Complete fittings
440Switches and sockets
441Junction box
442Celing Fan
443(K) Clamps & Connectors Set
444(M) Isolators
445220 kV
446Solid core Insulator Stacks (Requirement of one Isolator)
447Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key interlock for electrical control circuit as per approved schematic --- Each set containing one number of each type and rating as offered.
448Limit switches & aux.switches--Each Set containing one no. of each type and rating as offered
449Motor with gear assembly and bevel gear assembly.
450Bearings (Requirement of one Isolator)
451Current carrying assembly total (Requirement of one Isolator)
452132 kV
453Solid core Insulator Stacks (Requirement of one Isolator)
454Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key interlock for electrical control circuit as per approved schematic --- Each set containing one number of each type and rating as offered.
455Limit switches & aux.switches--Each Set containing one no. of each type and rating as offered
456Motor with gear assembly and bevel gear assembly.
457Bearings (Requirement of one Isolator)
458Current carrying assembly total (Requirement of one Isolator)
45933 kV
460Solid core insulator Stacks ( Requirement of one Isolator)
461Limit switches and auxiliary switches ---Each Set containing one no. of each type and rating as offered
462Bearings (requirement of one isolator)
463Current carrying assembly 2000A total (requirement of one isolator)
464Motor with gear assembly and bevel gear assembly.
465Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key inter lock for electrical control circuit as per approved schematic-- Each Set containing one no. of each type and rating as offered
466Add: Any other supply item, if any, bidder may require completing the substation as per specification requirements.
467Auto Transformer:
468220/132 kV, 160 MVA Auto Transformer with all accessories (excluding transformer Oil) as per technical specification
469Insulating Oil for 160 MVA 220/132 kV Auto Transformer as per S-I , (1) above
470Digital RTCC Panel consisting of Digital RTCC relay as per technical Specification for transformers at S-I (1) above
471Power Transformer:
472132/33 kV, 31.5 MVA Power Transformer with all accessories (excluding transformer Oil) as per technical specification
473Insulating Oil for 31.5 MVA 132/33 kV Power Transformer S-II (4) above
474Digital RTCC Panel consisting of Digital RTCC relay as per technical Specification for transformers S-II, (4) above
475Circuit Breakers
476220 kV Circuit Breakers
477220kV circuit breakers (3 Ph.) Along with support Structure
4782500 A, 50 kA
479132 kV Circuit Breakers
480132 kV circuit breakers (3 Ph.) Along with support Structure
4811250 A, 40 kA
48233 kV Circuit Breakers
48333 kV circuit breakers (3 Ph.) Along with support Structure
4841600 A, 31.5 kA
485Instrument Transformers
486Capacitor Voltage Transformer
487Single-Phase, 220 kV, 4400 pf CVT
488Single Phase 132 kV , 4400 pf CVT
48933 kV Potential Transformer
49033/√3 kV /110-110√3
491Current Transformer (1-Phase)
492220 kV CT
4931000/1 A, 5C
494132 kV CT
4951000/1 A, 3C
496500/1 A, 3C
49733 kV CT
4981000/1 A, 4C
499500/1A, 2C
500C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II)
501New Substation
502Control Panel for 220 kV Transformer (220 kV Side) Type: SAS-THCB
503Relay Panel for 220 kV Transformer (for both HV & MV) Type: SAS-THRB
504Control Panel for 220 kV Feeder Type: SAS-FCB
505Relay Panel for 220 kV Feeder Type: SAS-FRB
506Control Panel for 220 kV Bus Coupler Type: SAS-BCCB
507Relay Panel for 220 kV Bus Coupler Type: SAS-BCRB
508220 kV Busbar Protection Relay Panel Type: SAS-BBRB
509Control Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLCB
510Relay Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLRB
511Control and Relay Panel for 1x 50/31.5/25 MVA, 132/33 kV Power Transformer Type SAS-TCRA
512Control Panel for 132 kV Feeder Type SAS-FCA
513Relay Panel for 132 kV Feeder Type SAS-FRA
514Control and Relay Panel for 132 kV Bus-Coupler Type SAS-BCRA
515Control and Protection Panel for 33 kV Feeder (I/C, O/G)/Bus-coupler/ Capacitor Bank [For TWIN FEEDER/BAY] Type-FCRD
516Station HMI [Industrial grade Computer with 21\\"TFT monitor as per specification requirements]
517Station HMI (Hot Standby)[Industrial grade Computer with 21\\"TFT monitor as per specification requirements]
518HMI View Node[Industrial grad Computer with 21\\"TFT monitor as per specification requirements]
519A3 Size B&W Laser Printer
520Substation Automation System Network Panel Type SAS-NW
521Modems (both sending and Receiving End) for communication to RCC & Sub SLDC for PLCC]
522Data Concentrator Unit (DCU) at Substation for RAS mounted in suitable enclosure & fully wired
523Software: Application as well as System Software as per specification requirements for various hardware elements for meeting of functional requirement of the specification.
524Substation Auxiliary Monitoring Panel Type SAS-SAMP
525Other Items:
526Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the Substation LAN as per specification requirements.
527Transducers, Sensors etc. (if not considered in the respective equipment/ items) for accumulating monitoring data as per the specification requirements for switchyards.
528Surge Arresters
529220 kV LA
530132 kV LA
53133 kV LA
532Substation LT Transformer
53333/ 0.433 kV, 250 kVA LT transformer complete with all accessories, fittings, terminal connectors etc as specified filled with transformer oil
534Batteries & Battery Charger
535Batteries (Sizing shall be as per requirement of technical specification)
536220 V [Min. 600 AH]
53748 V [Min. 600 AH]
538Battery Charger System
539220 V Float and Boost
54050 V Float and Boost
541Lighting System
542Outdoor Lighting & other Works
543Lighting Fixture Type FL-1
544Lighting Fixture Type FL-2
545Outdoor Receptacle
546Type-RP
547Type-RO
548Substation Premises Lighting
549Lighting poles
550Type-L1
551Type-D1
552Street Lighting Type-SL-L1 for mounting on poles
553Street Lighting Type-SL-D1 for mounting on Poles
554Sub-Lighting Boxes/Panels Type -SLP at Lighting Mast and Other Loaction as designated complete with all controgears and accessories, items etc.
555Lighting Panel Type ACP-2 as per technical specification
556Lighting Panel Type ACP-3 as per technical specification
557Indoor Lighting & Other Works
558Electrification
559Electric Fitting (if not covered under Civil Works) with G.I. Conduit, Junction Boxes, pull out boxes, copper wiring, Modular Switchboards, Modular Switches, GI Wire (16SWG) etc. for control room, Hall and administrative office building as per the requirements of the specifications
560Illumiation
561Lighting fixtures and Receptacles (including accessories/ materials etc. as per requirement alongwith complete accessories and mounting arrangements)
562Indoor Lignting Panels
563Lighting Panel (Indoor) Type ACP-1 as per technical specification
564Lighting Panel (Indoor) Type DCP as per technical specification
565Wall mounted fans Approx. 400 mm sweep
566Ceiling Fan - Approx. 1400mm sweep with electronic Step regulator
567Exhaust Fans
568Fire Fighting System
569DCP Type
570i) 5 Kg.
571ii) 10 Kg.
572Carbon di oxide type – 6 Liters.
573Foam Type- 9 Liters
574Sand type
575i) GI Buckets 9 liters capacity
576ii) Steel Stands for four buckets
577Air Conditioning System
578Air Conditioning for the Rooms specified in the specifications
5791.1kV Grade PVC insulated Al. conductor FRLS power cables and copper conductor armoured FRLS control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room and other building]
580Power Cables(XLPE)
5811Cx630 sq.mm
5823.5Cx300 sq.mm
583Power Cable(PVC)
5841Cx150 sq.mm
5853.5Cx70 sq.mm
5863.5Cx35 sq.mm
5874Cx16 sq.mm
5884C x 6 Sq. mm
5892C x 6 Sq. mm
590Control Cable (PVC)
5914 CX4 Sq. mm
5923Cx2.5 sq.mm
5935Cx2.5 sq.mm
5947Cx2.5 sq.mm
59510Cx2.5 sq.mm
59614Cx2.5 sq.mm
59719Cx2.5 sq.mm
598Substation Structures
599Standard Lattice Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for lattice steel structure as per specification requirements]:
600NON Standard Pipe support Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for Pipe support structure as per specification requirements]:
601Isolators (Moterized)
602220 kV (3-Phase) (Horizontal DOUBLE BREAK)
6031600A, 50KA, isolator with one E/S
604Post insulators for above Isolator
6051600A, 50KA, isolator with two E/S
606Post insulators for above Isolator
6071600A, 50KA, isolator without E/S
608Post insulators for above Isolator
6091600A, 50KA, isolator without E/S (TANDEM Type)
610Post insulators for above Isolator
611132 kV (3-Phase) (Horizontal DOUBLE BREAK)
6121250A, isolator with 2 E/S
613Post insulators for above Isolator
6141250A, isolator with one E/S
615Post insulators for above Isolator
6161250A isolator without E/S
617Post insulators for above Isolator
61833 kV (3-Phase) (Horizontal DOUBLE BREAK)
6191250A, isolator without E/S
620Post insulators for above Isolator
621800 A isolator without E/S
622Post insulators for above Isolator
623800A isolator with E/S
624Post insulators for above Isolator
625Switchyard Erection
626Busbar & Interconnections
627New Substation/ Switchyard
628220 kV Switchyard Works:
629Main-I Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/Porcelain Long Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
630Main-II Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Pocelain Long Rod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
631Aux Bus: 220 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string(DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers, corona shields etc. as per Layout arrangment of the subsation and specification requirements [for 3 bays]
632220 kV Overhead Jack Bus (for DMT Layout) on Twin ACSR Zebra(Bus-Coupler Bay)/ Single ACSR Zebra (Transformer/ Line on ACSR Zebra) with conductor, busbar material, insulator string (DT/SS), AF Type Disc Insulators/ Porcelain Longrod Insulators, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
633Twin ACSR Zebra
634Single ACSR Zebra
635Equipment Interconnections to Main Bus, Overhead Bus including Single ACSR Zebra (for Line), Twin ACSR Zebra (forTransformer bay & B/C Bay), bus-bar materials, clamps, connectors, spacers, corona shields, including equipment connectors, Junction box including of all accessories etc. for the following:
636220 kV DMT-type layout
637Line bay
638Transformer bay
639Bus-Coupler
640Bus CVT Interconnections to Main Buses including Single ACSR Zebra, clamps, connectors, junction box including of all accessories etc.
641132 kV Switchyard Works:
642Main Bus: 132 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulator, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays]
643Aux Bus: 132 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string (DT/DS), AF Disc Insulators/ Porcelain Longrod Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 4 bays]
644132 kV Overhead Jack Bus (for Main & Aux Layout) on Twin ACSR Zebra(220 kV Transformer/Bus-Coupler Bay), Single ACSR Zebra(132 kV Transformer/Bus-Coupler Bay) Single ACSR Panther (Line on ACSR Panther) on Single Panther ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
645Twin ACSR Zebra
646Single ACSR Zebra
647Single Panther
648Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Zebra (Bus Sectionalizer/ 220 kV Transformer /Bus-Coupler Bay)/ Single ACSR Zebra (132 kV Transformer Bay) Single ACSR Panther ( Line on ACSR Panther), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
649132 kV Main & Aux-type layout
650Line bay
651Transformer bay
652Bus-Coupler
653Sectionlizer
654Bus CVT Interconnections to Main Bus including Single ACSR Zebra, clamps, connectors, junction box including of all accessories etc.
65533 kV Switchyard Works:
656Main Bus: 33 kV Twin ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays+ Bus Coupler]
657Aux Bus: 33 kV Single ACSR Zebra Bus with conductor, busbar material, insulator string, Disc Insulators, hardware, Clamps, Connectors, spacers etc. as per Layout arrangment of the subsation and specification requirements [for 5 bays+ Bus Coupler]
65833 kV Overhead Jack Bus for Transformer Incomer (for Main & Aux Layout) on Twin Zebra ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
659Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Panther ( Transformer /Bus-Coupler Bay)/ Single ACSR Panther ( Line bays), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
66033 kV Main & Aux-type layout
661Line bay
662Transformer bay
663Bus-Coupler
664SEctionlizer
665LT Transformer connection with ACSR Panther conductor, 33 kV DO Fuse Set alongwith required Clamp/connectors
666Bus PT Interconnections to Main Bus including Single ACSR Panther , clamps, connectors, junction box including of all accessories etc.
667Bus Post Insulators (BPI)
668220 kV
669132 kV
67033 kV
671Earthing & Lightning Protection System
672Main, Auxilary Earthmats, Risers etc. for complete earthing in the Switchyard Area
67328 mm Dia MS Rod
67428mm Dia, 3.2 M Long MS Rod Earth Electrodes Directly Driven.
67528mm Dia, 8 M Long MS Rod Earth Electrodes Directly Driven.
67628mm Dia, 3.2M Long MS Rod Earth Electrode in untreated pit with test link
67728 mm dia, 3000 mm long GS pipe electrodes with test links and treated earth pits with C.I. cover hinged to C.I. frame alongwith all associated civil works
67850X12 mm GS Flat
67950X6 mm GS Flat
680Earth Enhancing Compound for treated pits as above and other requirement as per specification
681Cleat type clamps(8mm thick) for earthing down conductor (10.98 mm dia), 50x12 mm GS Flat and 50x6 mm GS flat
682Cu/Al Flexible braids Grounding Conductor connection to MS/GS Flats
683Earth Wire for Shielding Protection of Switchyard
6847/3.15 Galvenized Steel Wire
685Earthwire tension clamps with D Shackle assembly
686PG calmp to suit 7/3.15 mm GS earth wire
687Cleat clamp on structure to suit 7/3.15 mm GS earth wire/ 50 X 12 mm GS Flat
688Pad clamp on structure to suit 7/3.15 mm earth wire and 75 x 12 GS flat
689Lug to suit 7/3.15 mm earth wire
690Other Clamps, Copper Earth Bond etc. as per layout diagram for erection of Earth Wire
691Bay Marshalling KIOSK
692200 way (Stud Type Connectors)
693AC Distribution Boxes (Outdoor Type)
694Outdoor AC Distbibution Box (Double Front type)
695Outdoor AC Distbibution Box (Single Front type)
696Conduits, Cable Trays [Perforated and Ladder Type], Cable Tags, Cable Clamps, Cable Lugs,Cable sealing system, Gland Plates, Junction Boxes, PVC pipes, hume Pipes, Nylon type Trefoil Clamps etc.[Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room and other building]
697Other Steel Structures/ members [items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washers etc. considered for this component of price schedule] to be designed/ provided by the bidder for the completion of project [This shall not include the steel to be used in the civil works]
698LT Switchgear
699LT AC Main Panel
700LT AC Distribution Board
701Main Lighting Distribution Board
702Emergency Lighting Distribution Board
703220V DCDB
70448V DCDB
705PLCC EQUIPMENTS
706220 kV Wave trap (1250A, 0.5 mH, 40 kA)
707132 kV wave trap (1000A, 0.2 mH, 40 kA)
7084 kH to 16 kHz Channel Digitial PLCC Carrier terminal with digital protection coupler (DTPC) IEC/101/104 data and 4 W E&M speech applications .
7094 kH to 16 kHz Channel Digitial PLCC Carrier terminal with out digital protection coupler (DTPC) IEC/101/104 data and 4 W E&M speech applications .
710VFT equipment (Modem) suitable for transmission of Data through PLCC links based on frequency shift keying modulation techniques programmable for both baud rate from 50 Baud to 2400 Baud and center frequency through switches or jumpers (A.F. Shift Channel)
711Coupling Devices for Phase to Phase coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level.
712Coupling Devices for Phase to Ground coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level.
713HF Armoured Coaxial cable having 75 Ohms unbalanced impendance.
714Microprocessor based 24/8 line Electronic Private Automatic Exchange (EPAX) with PLCC interphasing facility
715Telephone Sets (Push Button Type)
71610 pair Jelly Filled and armoured telephone cable with copper conductor of 0.5 mm
7175 Pair jelly filled armoured telephone cable having copper conductor of Dia. 0.5 mm
7185 Pair jelly filled un armoured telephone cable having copper conductor of Dia. 0.5 mm
719Add: Any other item bidder may require to complete the Electrical Service works as per specification requirements
720CIVIL WORKS
721TOWER/ EQUIPMENT FOUNDATIONS :
722TOWER/ EQUIPMENT FOUNDATIONS :
723MAIN MATERIAL/ ITEMS
724Circuit Breakers
725132 kV Circuit Breakers
726132 kV circuit breakers (3 Ph.) Along with support Structure
7271250 A, 40 kA
728Instrument Transformers
729Capacitor Voltage Transformer
730Single Phase 132 kV , 4400 pf CVT
731Current Transformer (1-Phase)
732132 kV CT
733500/1 A, 3C
734C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II)
735132 kV Feeder C&R Panel as per Specification (Conventional Type without BCU)
736Upgrade/ New Hardware & Software as required for integration to Existing RTU/SCADA and RAS System
737Other Items:
738Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the Substation LAN as per specification requirements.
739Transducers, Sensors etc. (if not considered in the respective equipment/ items) for accumulating monitoring data as per the specification requirements for switchyards.
740Surge Arresters
741132 kV LA
7421.1kV Grade PVC insulated Al. conductor FRLS power cables and copper conductor armoured FRLS control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room and other building]
743Control Cable (PVC)
7444 CX4 Sq. mm
7454 CX2.5 Sq. mm
7466Cx2.5 sq.mm
74719Cx2.5 sq.mm
748Substation Structures
749Standard Lattice Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for lattice steel structure as per specification requirements]:
750Non-Standard type Pipe Support Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for Pipe Support structure as per specification requirements]
751Isolators (Moterized)
752132 kV (3-Phase) (Horizontal DOUBLE BREAK)
7531250A, isolator with one E/S
754Post insulators for above Isolator
7551250A isolator without E/S
756Post insulators for above Isolator
757Switchyard Erection
758Busbar & Interconnections
759Line bays on Existing terminal Substations
760132 kV Switchyard Works:
761132 kV Overhead Jack Bus (for Main & Aux Layout) on Twin ACSR Zebra(220 kV Transformer/Bus-Coupler Bay), Single ACSR Zebra(132 kV Transformer/Bus-Coupler Bay) Single ACSR Panther (Line on ACSR Panther) on Single Panther ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
762Single Panther
763Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Zebra (Bus Sectionalizer/ 220 kV Transformer /Bus-Coupler Bay)/ Single ACSR Zebra (132 kV Transformer Bay) Single ACSR Panther ( Line on ACSR Panther), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
764132 kV Main & Aux-type layout
765Line bay
766Bus Post Insulators (BPI)
767132 kV
768Earthing & Lightning Protection System
769Main, Auxilary Earthmats, Risers etc. for complete earthing in the Switchyard Area
77028 mm Dia MS Rod
77150X12 mm GS Flat
772Earth Enhancing Compound for treated pits as above and other requirement as per specification
773Cleat type clamps(8mm thick) for earthing down conductor (10.98 mm dia), 50x12 mm GS Flat and 50x6 mm GS flat
774Cu/Al Flexible braids Grounding Conductor connection to MS/GS Flats
775Earth Wire for Shielding Protection of Switchyard
776Earth wire GS 7/3.15
777Earthwire tension clamps with D Shackle assembly
778Other Clamps, Copper Earth Bond etc. as per layout diagram for erection of Earth Wire
779Bay Marshalling KIOSK
780200 way (Stud Type Connectors)
781Conduits, Cable Trays [Perforated and Ladder Type], Cable Tags, Cable Clamps, Cable Lugs,Cable sealing system, Gland Plates, Junction Boxes, PVC pipes, hume Pipes, Nylon type Trefoil Clamps etc.[Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room and other building]
782Other Steel Structures/ members [items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washers etc. considered for this component of price schedule] to be designed/ provided by the bidder for the completion of project [This shall not include the steel to be used in the civil works]
783PLCC EQUIPMENTS
784132 kV wave trap (100A, 0.2 mH, 40 kA)
7854 kH to 16 kHz Channel Digitial PLCC Carrier terminal with out digital protection coupler (DTPC) IEC/101/104 data and 4 W E&M speech applications .
786Coupling Devices for Phase to Ground coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level.
7875 Pair jelly filled un armoured telephone cable having copper conductor of Dia. 0.5 mm
788HF Armoured Coaxial cable having 75 Ohms unbalanced impendance.
789Add: Any other supply item, if any, bidder may require completing the substation as per specification requirements.
790SERVICE+ETC+Civil
791132 kV Circuit Breakers
792132 kV circuit breakers (3 Ph.) Along with support Structure
7931250 A, 40 kA
794Capacitor Voltage Transformer
795Single Phase 132 kV , 4400 pf CVT
796Current Transformer (1-Phase)
797132 kV CT
798500/1 A, 3C
799C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II)
800132 kV Feeder C&R Panel as per Specification (Conventional Type without BCU)
801Upgrade/ New Hardware & Software as required for integration to Existing RTU/SCADA and RAS System
802Other Items:
803Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the Substation LAN as per specification requirements.
804Transducers, Sensors etc. (if not considered in the respective equipment/ items) for accumulating monitoring data as per the specification requirements for switchyards.
805Surge Arresters
806132 kV LA
8071.1kV Grade PVC insulated Al. conductor FRLS power cables and copper conductor armoured FRLS control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room and other building]
808Control Cable (PVC)
8094 CX4 Sq. mm
8104 CX2.5 Sq. mm
8116Cx2.5 sq.mm
81219Cx2.5 sq.mm
813Substation Structures
814Standard Lattice Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for lattice steel structure as per specification requirements]:
815Non-Standard type Pipe Support Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for Pipe Support structure as per specification requirements]
816Isolators (Moterized)
817132 kV (3-Phase) (Horizontal DOUBLE BREAK)
8181250A, isolator with one E/S
819Post insulators for above Isolator
8201250A isolator without E/S
821Post insulators for above Isolator
822Switchyard Erection
823Busbar & Interconnections
824Line bays on Existing terminal Substations
825132 kV Switchyard Works:
826132 kV Overhead Jack Bus (for Main & Aux Layout) on Twin ACSR Zebra(220 kV Transformer/Bus-Coupler Bay), Single ACSR Zebra(132 kV Transformer/Bus-Coupler Bay) Single ACSR Panther (Line on ACSR Panther) on Single Panther ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
827Single Panther
828Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Zebra (Bus Sectionalizer/ 220 kV Transformer /Bus-Coupler Bay)/ Single ACSR Zebra (132 kV Transformer Bay) Single ACSR Panther ( Line on ACSR Panther), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
829132 kV Main & Aux-type layout
830Line bay
831Bus Post Insulators (BPI)
832132 kV
833Earthing & Lightning Protection System
834Main, Auxilary Earthmats, Risers etc. for complete earthing in the Switchyard Area
83528 mm Dia MS Rod
83650X12 mm GS Flat
837Earth Enhancing Compound for treated pits as above and other requirement as per specification
838Cleat type clamps(8mm thick) for earthing down conductor (10.98 mm dia), 50x12 mm GS Flat and 50x6 mm GS flat
839Cu/Al Flexible braids Grounding Conductor connection to MS/GS Flats
840Earth Wire for Shielding Protection of Switchyard
841Earth wire GS 7/3.15
842Earthwire tension clamps with D Shackle assembly
843Other Clamps, Copper Earth Bond etc. as per layout diagram for erection of Earth Wire
844Bay Marshalling KIOSK
845200 way (Stud Type Connectors)
846Conduits, Cable Trays [Perforated and Ladder Type], Cable Tags, Cable Clamps, Cable Lugs,Cable sealing system, Gland Plates, Junction Boxes, PVC pipes, hume Pipes, Nylon type Trefoil Clamps etc.[Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room and other building]
847Other Steel Structures/ members [items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washers etc. considered for this component of price schedule] to be designed/ provided by the bidder for the completion of project [This shall not include the steel to be used in the civil works]
848PLCC EQUIPMENTS
849132 kV wave trap (1000A, 0.2mH, 40 kA)
8504 kH to 16 kHz Channel Digitial PLCC Carrier terminal with out digital protection coupler (DTPC) IEC/101/104 data and 4 W E&M speech applications .
851Coupling Devices for Phase to Ground coupling having Band width programmable at site with protective Device & balancing transformer matching with line impedance of respective voltage level.
852HF Armoured Coaxial cable having 75 Ohms unbalanced impendance.
8535 Pair jelly filled un armoured telephone cable having copper conductor of Dia. 0.5 mm
854Add: Any other item bidder may require to complete the Electrical Service works as per specification requirements
855CIVIL WORKS
856TOWER/ EQUIPMENT FOUNDATIONS :
857TOWER/ EQUIPMENT FOUNDATIONS :
858MAIN MATERIAL/ ITEMS
859Circuit Breakers
86033 kV Circuit Breakers
86133 kV circuit breakers (3 Ph.) Along with support Structure
8621600 A, 31.5 kA
863Current Transformer (1-Phase)
86433 kV CT
865250/1 A, 2C
866C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II)
867Control and Protection Panel for 33 kV Feeder (I/C, O/G)/Bus-coupler/ Capacitor Bank [For TWIN FEEDER/BAY] Type-FCRD
868Other Items:
869Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the Substation LAN as per specification requirements.
870Transducers, Sensors etc. (if not considered in the respective equipment/ items) for accumulating monitoring data as per the specification requirements for switchyards.
8711.1kV Grade PVC insulated Al. conductor FRLS power cables and copper conductor armoured FRLS control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room and other building]
872Control Cable (PVC)
8734 CX4 Sq. mm
8743Cx2.5 sq.mm
8755Cx2.5 sq.mm
87614Cx2.5 sq.mm
87719Cx2.5 sq.mm
878Substation Structures
879Standard Lattice Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for lattice steel structure as per specification requirements]:
880Isolators (Moterized)
88133 kV (3-Phase) (Horizontal DOUBLE BREAK)
882800 A isolator without E/S
883Post insulators for above Isolator
884800A isolator withE/S
885Post insulators for above Isolator
886Switchyard Erection
887Busbar & Interconnections
888Line bays on Existing terminal Substations
88933 kV Switchyard Works:
89033 kV Overhead Jack Bus for Capacitor Bank (for Main & Aux Layout) on Twin Zebra ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
891Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Panther ( Transformer /Bus-Coupler Bay)/ Single ACSR Panther ( Line bays), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
89233 kV Main & Aux-type layout
893Capacitor Bank bay
894Bus Post Insulators (BPI)
89533 kV
896Earthing & Lightning Protection System
897Main, Auxilary Earthmats, Risers etc. for complete earthing in the Switchyard Area
898MS Channel 100x50x6 MM
89928 MM MS Rod
90050x12 mm GS Flat
901Earth Enhancing Compound for treated pits as above and other requirement as per specification
902Cleat type clamps(8mm thick) for earthing down conductor (10.98 mm dia), 50x12 mm GS Flat and 50x6 mm GS flat
903Cu/Al Flexible braids Grounding Conductor connection to MS/GS Flats
904Earth Wire for Shielding Protection of Switchyard
905Other Clamps, Copper Earth Bond etc. as per layout diagram for erection of Earth Wire
906Bay Marshalling KIOSK
907200 way (Stud Type Connectors)
908Conduits, Cable Trays [Perforated and Ladder Type], Cable Tags, Cable Clamps, Cable Lugs,Cable sealing system, Gland Plates, Junction Boxes, PVC pipes, hume Pipes, Nylon type Trefoil Clamps etc.[Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room and other building]
909Other Steel Structures/ members [items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washers etc. considered for this component of price schedule] to be designed/ provided by the bidder for the completion of project [This shall not include the steel to be used in the civil works]
910Capacitor Bank Equipments
91133 kV 5.43 MVAR Capacitor Bank with structure
912Neutral current Transformer(NCT)(1A/5A)
913Series reactors (1-phase) for parallel operation of two double star connected capacitor banks of 2.72 MVAR rating
914Add: Any other supply item, if any, bidder may require completing the substation as per specification requirements.
915Service+ETC+Civil
916Circuit Breakers
91733 kV Circuit Breakers
91833 kV circuit breakers (3 Ph.) Along with support Structure
9191600 A, 31.5 kA
920Current Transformer (1-Phase)
92133 kV CT
922250/1 A, 2C
923C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II)
924Control and Protection Panel for 33 kV Feeder (I/C, O/G)/Bus-coupler/ Capacitor Bank [For TWIN FEEDER/BAY] Type-FCRD
925Other Items:
926Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the Substation LAN as per specification requirements.
927Transducers, Sensors etc. (if not considered in the respective equipment/ items) for accumulating monitoring data as per the specification requirements for switchyards.
9281.1kV Grade PVC insulated Al. conductor FRLS power cables and copper conductor armoured FRLS control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room and other building]
929Control Cable (PVC)
9304 CX4 Sq. mm
9313Cx2.5 sq.mm
9325Cx2.5 sq.mm
93314Cx2.5 sq.mm
93419Cx2.5 sq.mm
935Substation Structures
936Standard Lattice Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for lattice steel structure as per specification requirements]:
937Isolators (Moterized)
93833 kV (3-Phase) (Horizontal DOUBLE BREAK)
939800 A isolator without E/S
940Post insulators for above Isolator
941800A isolator withE/S
942Post insulators for above Isolator
943Switchyard Erection
944Busbar & Interconnections
945Line bays on Existing terminal Substations
94633 kV Switchyard Works:
94733 kV Overhead Jack Bus for Capacitor Bank (for Main & Aux Layout) on Twin Zebra ( with conductor, busbar material, insulator string, Disc Insulators, hardware, clamps, connectors, spacers etc. as per Substation Layout arrangement and specification requirements [ for 1 Bay]
948Equipment Interconnections to Main Bus, Overhead Bus including Twin ACSR Panther ( Transformer /Bus-Coupler Bay)/ Single ACSR Panther ( Line bays), bus-bar materials, clamps, connectors, spacers including equipment connectors, Junction box including of all accessories etc. for the following:
94933 kV Main & Aux-type layout
950Capacitor Bank bay
951Bus Post Insulators (BPI)
95233 kV
953Earthing & Lightning Protection System
954Main, Auxilary Earthmats, Risers etc. for complete earthing in the Switchyard Area
955MS Channel 100x50x6 MM
95628 MM MS Rod
95750x12 mm GS Flat
958Earth Enhancing Compound for treated pits as above and other requirement as per specification
959Cleat type clamps(8mm thick) for earthing down conductor (10.98 mm dia), 50x12 mm GS Flat and 50x6 mm GS flat
960Cu/Al Flexible braids Grounding Conductor connection to MS/GS Flats
961Earth Wire for Shielding Protection of Switchyard
962Other Clamps, Copper Earth Bond etc. as per layout diagram for erection of Earth Wire
963Bay Marshalling KIOSK
964200 way (Stud Type Connectors)
965Conduits, Cable Trays [Perforated and Ladder Type], Cable Tags, Cable Clamps, Cable Lugs,Cable sealing system, Gland Plates, Junction Boxes, PVC pipes, hume Pipes, Nylon type Trefoil Clamps etc.[Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room and other building]
966Other Steel Structures/ members [items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washers etc. considered for this component of price schedule] to be designed/ provided by the bidder for the completion of project [This shall not include the steel to be used in the civil works]
967Capacitor Bank Equipments
96833 kV 5.43 MVAR Capacitor Bank
969Neutral current Transformer(NCT)(1A/5A)
970Series reactors (1-phase) for parallel operation of two double star connected capacitor banks of 2.72 MVAR rating
971CIVIL WORKS
972TOWER/ EQUIPMENT FOUNDATIONS : Please Enable Macros to View BoQ information
973TOWER/ EQUIPMENT FOUNDATIONS : Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57794603
AUTHORITY Government Departments
TENDER VALUE 43.98 Crore
LAST DATE 18-11-2026
Authority
Authority Name Rajasthan Rajya Vidhyut Prasaran Nigam Limited
Work Description Tender for Construction Of 220/132Kv, 160Mva And 132/33Kv, 31.5Mva Substation At Palana (Distt.-Bikaner) Including Survey Supply Of All Equipments/Materials, Erection (Including Civil Works), Testing And Commissioning On Turnkey Basis Against Specification No. Rvpn/Ehv/Bn-9019002602.
Basic Detail
Tender No RVPN/EHV/BN9019002602
Bidding Type Tender
Location
City Jaipur
State Rajasthan
Key Dates
Publish Date 03 Nov 2026
Submission Date 18 Nov 2026
Open Date 19 Nov 2026
Finance
Tender Value 43.98 Crore
Tender Fee 17700
EMD 87.95 Lakhs
Exemption Not Available
Document List
BOQ_1066880.xls
c81dd48e-da78-469f-8bdb-bf8c7bca6ce0.html
Commercial_doc_palana.pdf
ELP_Drawings.pdf
project_section.pdf
Technical_Palana_GSS_VOL-_1.pdf
Tendernotice_1 (79).pdf
Vol_III_Civil.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 03, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 18, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 6 days
Nov 18, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 6 days
Nov 19, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 7 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_1066880.xls

html

c81dd48e-da78-469f-8bdb-bf8c7bca6ce0.html

pdf

Commercial_doc_palana.pdf

pdf

ELP_Drawings.pdf

pdf

project_section.pdf

pdf

Technical_Palana_GSS_VOL-_1.pdf

pdf

Tendernotice_1 (79).pdf

pdf

Vol_III_Civil.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender