Tender For Sub-Station And Transmission Line (Composite Package-C13)
Tender Value
Ref. Documents
Estimated cost
Bid Submission
28 Oct 2026
9 days left
EMD
1.50 Crore
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
24 Paraganas North → West Bengal
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Sub-Station And Transmission Line (Composite Package-C13)
BOQ
| Sl. No. | Item Description |
| 1 | COMPOSITE PACKAGE-C13 |
| 2 | Sub-Station and Transmission Line (COMPOSITE PACKAGE-C13) |
| 3 | Golatore |
| 4 | Manbazar |
| 5 | Khatra |
| 6 | 132KV Manbazar -Khatra |
| 7 | 132 KV Khatra-Goaltr |
| 8 | Dal-Gajol at Raiganj |
| 9 | 2.0 ELECTRICAL PART : |
| 10 | CIRCUIT BREAKER : 132 KV, 1600 A, 31.5 KA for 3sec, SF6, 1 Pole/ ph , 3Ph , Gang Operated and as per Technical Specification with support structure complete |
| 11 | ISOLATORS |
| 12 | 132 KV, 1250 A,31.5 KA for 3sec, HCB, motor operated 3-phase Assembly WITH EARTHING SWITCH (excluding insulators) |
| 13 | Solid Core Insulator for each set of above Isolators |
| 14 | 132 KV, 1250 A,31.5 KA for 3sec, HCB, motor operated 3-phase Assembly WITHOUT EARTHING SWITCH (excluding insulators) |
| 15 | Solid Core Insulator for each set of above Isolators |
| 16 | 132 KV, 1250 A,31.5 KA for 3sec, HCB, motor operated 3-phase Assembly WITHOUT EARTHING SWITCH Staggered Type (excluding insulators) |
| 17 | Solid Core Insulator for each set of above Isolators |
| 18 | 132 KV, 1250 A,31.5 KA for 3sec, HCB, motor operated 3-phase Assembly WITHOUT EARTHING SWITCH Type (excluding insulators) |
| 19 | Solid Core Insulator for each set of above Isolators |
| 20 | SURGE ARRESTOR As per Technical Specification |
| 21 | SURGE ARRESTOR (1 - ɸ) - 120 KV, 10 KA, Heavy Duty, Metal Oxide , Gapless , Polymer Housed |
| 22 | CURRENT TRANSFORMER |
| 23 | 145 KV CURRENT TRANSFORMER (1 - ɸ) - Feeder (1000-800-400/1A, 5 cores) |
| 24 | CVT As per Technical specification |
| 25 | 145 KV line CVT |
| 26 | Control & Relay Panel |
| 27 | 132 KV Simplex type C&R Panel with BCU and Breaker Control Switch matching with the existing system inclusive of all relays, Annunciator (Minimum 24 windows or more as per scheme requirement, with RS485 port for Modbus Communication, Auxiliary AC and DC Supply as well as Dedicated AC Fail and DC Fall windows) and other accessories as per specification and requirement - for Feeder including 2nos. Distance protection relay of different manufacturer having different model, algorithm, hardware with group selection switch. |
| 28 | Integration of present 132 KV bays with existing 132 KV Bus Bar Differential Protection systems respectively inclusive of additional component as per actual requirement, so as to make the protection scheme work properly). |
| 29 | 132 KV Solid Core POST INSULATOR with hardware fittings and accessories as per Technical Specification and requirement |
| 30 | DISC INSULATORS as per Technical Specification and as per requirement |
| 31 | HARDWARE FITTINGS and ACCESSORIES for SUSPENSION & TENSION Insulator String as per Technical Specification for extension of Main Bus & transfer Bus and others as per requirements (without Disc) |
| 32 | 2.5 \\"IPS ALUMINIUM TUBULAR PIPE as per Technical Specification and as per requirement |
| 33 | ACSR Moose CONDUCTORS as per Technical Specification for Main Bus ,Transfer Bus and droppers, jumpers as per requirement |
| 34 | CLAMPS, CONNECTORS & BUNDLE SPACER including equipment connectors as per Technical Specification and as per requirement |
| 35 | CONTROL CABLE (1.1 KV GRADE) as per Tech spec |
| 36 | Control cable 1.1KV grade( Cupper ) as per TECH Spec and as per requirement as per approved drawing and cable schedule for entire work including cable laying from ACDB & DCDB ,panel and switchyard equipment and also any equipments supplied by WBSETCL if any including Supply and installation of all required cables Actual quantity will be finalised as per approved drawing and cable schedule and as per requirement |
| 37 | POWER CABLE - Multi Core, PVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification and as per requirement (All cables shall be of Copper only.) |
| 38 | 3.5 core 25 sqmm PVC, Armoured AL as per Technical Specification. |
| 39 | 3.5 core 35 sqmm PVC, Armoured AL as per Technical Specification. |
| 40 | 2 core 10 sqmm PVC, Armoured AL as per Technical Specification. |
| 41 | SUBSTATION EARTHING SYSTEM complete including GIS equipments and its accessories , Outdoor Switchyard and other installation of the Substation area. As per Tech specification. |
| 42 | 32mm dia or higher MS rod for main earthmat grid, corner mesh and periphry for outdoor switchyard . The actual quantity shall be finalised depending on the approved design (Only design quantity with lap length without any wastage for main mat, periphery & corner mesh will be considered for payment.) The Earthmat design is to be done as per Technical Specification & matching with existing system. |
| 43 | 32mm dia or higher MS rod for riser below and above ground auxiliary Mat fencing and gate earthing bending length and overlapping length |
| 44 | GS flat for riser above ground / cable trench & other areas. Rod/pipe electrode , test link and other materials etc. - as per requirement, technical specification and approved design/layout including earthpit. |
| 45 | MISCELLANEOUS ITEMS as per technical specification and as per requirement |
| 46 | Bay marshalling kiosk |
| 47 | junction box for CT/CVT |
| 48 | Distribution Boards |
| 49 | Angle channels ferrul etc |
| 50 | Danger plate, phase plate, bay nameplate, |
| 51 | Cable Tray |
| 52 | Fire protection system including hydrant & extinguisher for extended portion of existing switchyard area matching with existing system including diversion of fire hydrant system if any in case of obstructing new construction work. |
| 53 | Communication Equipment (As per technical specification, BOQ and mentioned Annexure) |
| 54 | E-1 Port Interfacing Cable |
| 55 | Digital Teleprotection Coupler suitable for integration with SDH terminal equipment to communicate on G 703 (E1, 2 Mbps) with minimum Eight commands as per Technical Specification requirement. |
| 56 | Integration (including data base creation) of newly constructed 132KV bays with existing SAS with supply of all hardware and software as per approved drawing, system requirement and technical specification. |
| 57 | Integration of newly constructed 132KV bays at SLDC & Back up SLDC (including data base creation) with supply of hardware and software as per system requirement and as per technical specification. |
| 58 | Civil Part: |
| 59 | Supply, fabrication, galvanisaton of various switchyard & equipment structures, LM / High Mast ( 35Mtr or 50 Mtr-based on DSLP Calculation), XLPE cable supporting structure complete as per approved electrical layout drawings and technical specification (Electrical & civil) and as per requirement complete. |
| 60 | Switchyard Structures including Nuts & Bolts |
| 61 | Foundation Bolts for switchyard structures including nuts, washers and anchor plates (Foundation Bolts shall be galvanisedupto threaded length from top) |
| 62 | 2.0 ELECTRICAL PART : |
| 63 | CIRCUIT BREAKER : 132 KV, 1600 A, 31.5 KA for 3sec, SF6, 1 Pole/ ph , 3Ph , Gang Operated and as per Technical Specification with support structure complete |
| 64 | ISOLATORS |
| 65 | 132 KV, 1250 A,31.5 KA for 3sec, HCB, motor operated 3-phase Assembly WITH EARTHING SWITCH (excluding insulators) |
| 66 | Solid Core Insulator for each set of above Isolators |
| 67 | 132 KV, 1250 A,31.5 KA for 3sec, HCB, motor operated 3-phase Assembly WITHOUT EARTHING SWITCH (excluding insulators) |
| 68 | Solid Core Insulator for each set of above Isolators |
| 69 | 132 KV, 1250 A,31.5 KA for 3sec, HCB, motor operated 3-phase Assembly WITHOUT EARTHING SWITCH Staggered Type (excluding insulators) |
| 70 | Solid Core Insulator for each set of above Isolators |
| 71 | 132 KV, 1250 A,31.5 KA for 3sec, HCB, motor operated 3-phase Assembly WITHOUT EARTHING SWITCH Type (excluding insulators) |
| 72 | Solid Core Insulator for each set of above Isolators |
| 73 | SURGE ARRESTOR As per Technical Specification |
| 74 | SURGE ARRESTOR (1 - ɸ) - 120 KV, 10 KA, Heavy Duty, Metal Oxide , Gapless , Polymer Housed |
| 75 | CURRENT TRANSFORMER |
| 76 | 145 KV CURRENT TRANSFORMER (1 - ɸ) - Feeder (1000-800-400/1A, 5 cores) |
| 77 | CVT As per Technical specification |
| 78 | 145 KV line CVT |
| 79 | Control & Relay Panel |
| 80 | 132 KV Simplex type C&R Panel with BCU and Breaker Control Switch matching with the existing system inclusive of all relays, Annunciator (Minimum 24 windows or more as per scheme requirement, with RS485 port for Modbus Communication, Auxiliary AC and DC Supply as well as Dedicated AC Fail and DC Fall windows) and other accessories as per specification and requirement - for Feeder including 2nos. Distance protection relay of different manufacturer having different model, algorithm, hardware with group selection switch. |
| 81 | Integration of present 132 KV bays with existing 132 KV Bus Bar Differential Protection systems respectively inclusive of additional component as per actual requirement, so as to make the protection scheme work properly). |
| 82 | 132 KV Solid Core POST INSULATOR with hardware fittings and accessories as per Technical Specification and requirement |
| 83 | DISC INSULATORS as per Technical Specification and as per requirement |
| 84 | HARDWARE FITTINGS and ACCESSORIES for SUSPENSION & TENSION Insulator String as per Technical Specification for extension of Main Bus & transfer Bus and others as per requirements (without Disc) |
| 85 | 2.5 \\"IPS ALUMINIUM TUBULAR PIPE as per Technical Specification and as per requirement |
| 86 | ACSR Moose CONDUCTORS as per Technical Specification for Main Bus ,Transfer Bus and droppers, jumpers as per requirement |
| 87 | CLAMPS, CONNECTORS & BUNDLE SPACER including equipment connectors as per Technical Specification and as per requirement |
| 88 | CONTROL CABLE (1.1 KV GRADE) as per Tech spec |
| 89 | Control cable 1.1KV grade( Cupper ) as per TECH Spec and as per requirement as per approved drawing and cable schedule for entire work including cable laying from ACDB & DCDB ,panel and any other equipment and also any equipments supplied by WBSETCL if any including Supply and installation of all required cables Actual quantity will be finalised as per approved drawing and cable schedule and as per requirement |
| 90 | POWER CABLE - Multi Core, PVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification and as per requirement (All cables shall be of Copper only.) |
| 91 | 3.5 core 25 sqmm PVC, Armoured AL as per Technical Specification. |
| 92 | 3.5 core 35 sqmm PVC, Armoured AL as per Technical Specification. |
| 93 | 2 core 10 sqmm PVC, Armoured AL as per Technical Specification. |
| 94 | SUBSTATION EARTHING SYSTEM complete including GIS equipments and its accessories , Outdoor Switchyard and other installation of the Substation area. As per Tech specification. |
| 95 | 32mm dia or higher MS rod for main earthmat grid, corner mesh and periphry for outdoor switchyard . The actual quantity shall be finalised depending on the approved design (Only design quantity with lap length without any wastage for main mat, periphery & corner mesh will be considered for payment.) The Earthmat design is to be done as per Technical Specification & matching with existing system. |
| 96 | 32mm dia or higher MS rod for riser below and above ground auxiliary Mat fencing and gate earthing bending length and overlapping length |
| 97 | GS flat for riser above ground / cable trench & other areas. Rod/pipe electrode , test link and other materials etc. - as per requirement, technical specification and approved design/layout including earthpit. |
| 98 | MISCELLANEOUS ITEMS as per technical specification and as per requirement |
| 99 | Bay marshalling kiosk |
| 100 | junction box for CT/CVT |
| 101 | Distribution Boards |
| 102 | Angle channels ferrul etc |
| 103 | Danger plate, phase plate, bay nameplate, |
| 104 | Cable Tray |
| 105 | Fire protection system including hydrant & extinguisher for extended portion of existing switchyard area matching with existing system including diversion of fire hydrant system if any in case of obstructing new construction work. |
| 106 | Communication Equipment (As per technical specification, BOQ and mentioned Annexure) |
| 107 | Erection of Digital Teleprotection Coupler as per requirement, technical specification and supply BOQ |
| 108 | Integration of newly constructed 132KV bays at local end, SLDC and back up SLDC (including data base creation) as per requirement of technical specification by directly communicating with concerned OEM at local end and agency engaged for AMC of SCADA at SLDC and Back up SLDC End respectively . |
| 109 | Civil (Structural) Part: |
| 110 | Erection of various switchyard & equipment structures, LM- Lattice type ( 35Mtr or 50 Mtr-based on DSLP Calculation), XLPE cable supporting structure complete as per approved electrical layout drawings and technical specification (Electrical & civil) and as per requirement complete. (including Nuts & Bolts and foundation bolts) CIVIL Part: 2NOS LINE BAY AT GOALTORE 132KV S/S |
| 111 | Survey work (topography & contour) & setting out of layout as per bid drawing so as to match the land ulitilisation plan drawing as per technical specification, requirement complete. |
| 112 | Chilchaling, dressing and levelling for proposed scope of work as per tender drawing, Technical Specification and requirement complete. |
| 113 | Dismantling of existing structures (RCC / Bituminous road, cable trench including cable pull pit, storm water drain, switchyard pedestals, foundations / RCC,Steel Structures, yard PCC complete) as per requirement including removal of spoils as per instruction of the Engineer in charge. Serviceable materials (if any) are to be handed over to WBSETCL / WBSEDCL as per direction of EIC. N.B.: Lead distance of dismantled debris/non serviceable materials shall be finalized in consultation with EIC and as suit to site. |
| 114 | Design & constructions of foundations for various switchyard Tower structures, LM Lattice type, equipment structures (if any), drain (if required) including other Electro-mechanical equipment as per requirement as indicated in Electrical Schedule of Works and as per approved foundation layout drawing, foundation drawings and specification complete. |
| 115 | Concreting in sub-structure with Reinforced Cement Concrete M-20 grade including supply of all materials, labour & tools and tackles as required Including shuttering & Supply & Laying of Reinforcement (for main, distribution bars, spacers, stirrups/links, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection) complete as per drawing and Technical Specification etc. requirement complete (thw work is to be executed in line with approved drawing and as per decision/direction of the EIC). as per Technical Specification and approved drawing complete. Dewatering & shoring shall be done as per site requirement in consultation with EIC.N.B:The above item is inclusive of setting out & holding down Anchor fastener (i/c supply as required) / foundation bolts with Nut including anchor plate, washer (at bottom fitted complete and packing the hole with cement concrete or cement grout (as per civil tech. spec.). |
| 116 | Design & construction of outdoor cable trench including trench cover ( excluding supply of cable tray with M.S angles and Flats etc.) as per requirement within switchyard complete as per approved drawing, specification and requirement. |
| 117 | Concreting in sub-structure with Reinforced Cement Concrete M-20 grade including supply of all materials, labour & tools and tackles as required Including shuttering & Supply of Reinforcement (for main, distribution bars, spacers, stirrups/links, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection) complete as per drawing and Technical Specification etc. requirement complete (thw work is to be executed in line with approved drawing and as per decision/direction of the EIC). as per Technical Specification and approved drawing complete. Dewatering & shoring is to be done as per site requirement in consultation with EIC. |
| 118 | Fitting and fixing of all M.S. structural steel, Insert plate, MS FLAT, MS Grating etc. in outdoor cable trench and drain with simple rolled structural members (e.g. joists, angle, channel sections conforming to IS: 226, IS: 808 & SP (6)- 1964 connected to one another with bracket, gussets, cleats as per design, direction of Engineer-incharge complete including cutting to requisite shape and length, fabrication with necessary bolting, metal arc welding conforming to IS: 816- 1969 & IS: 1995 using electrodes of approved make and brand conforming to IS:814- 2004, haulage, hoisting and erection including supply of all materials, tool tackles and labour complete as per Technical Specification & approved drawing. Steel work shall be painted with one coat of primer and two coats of paint in line with civil tech spec and requirement complete. |
| 119 | EARTHING SYSTEM COMPLETE |
| 120 | Supplying & Laying of 100 mm thick Crushed stone /gravel (if required after using the existing crushed stone/gravel) matching with the existing one within the earthmat area as per approved layout and Technical Specification. |
| 121 | Removal of existing gravels/crushed stone (including dismantling of PCC under the gravel as required) & stacking the same in covenient location for future use after necessary cleaning & washing . |
| 122 | Relaying of existing Crushed stone as available from stacking of crushed stone as per approved layout and Technical Specification & requirement complete. |
| 123 | Laying of 75 mm thick P.C.C (1:4:8) with Jhama bricks at switch yard earthmat area including supply of all materials & labour complete as per Technical Specification and approved drawing complete and as per direction of the EIC. |
| 124 | MISCLLANEOUS ITEMS (As will be required for successful commisioning of the work in all respect) |
| 125 | Earthwork in excavation of foundation up to 1.5M in all sorts of soil including removing, spreading or stacking the spoils within a lead of 75 M or as directed. The items includes necessary trimming the sides of trenches, levelling, dressing and ramming the bottom, bailing out water as per approved drawing, technical specification,including labour & requirement complete. |
| 126 | Earthwork in excavation of foundation from 1.5M to 3.0M in all sorts of soil including removing, spreading or stacking the spoils within a lead of 75 M or as directed. The items includes necessary trimming the sides of trenches, levelling, dressing and ramming the bottom, bailing out water as per approved drawing, technical specification,including labour & requirement complete. |
| 127 | Earthwork in excavation of foundation from 3.0M to 4.0M in all sorts of soil including removing, spreading or stacking the spoils within a lead of 75 M or as directed. The items includes necessary trimming the sides of trenches, levelling, dressing and ramming the bottom, bailing out water as per approved drawing, technical specification,including labour & requirement complete.Sl. No. 32 of Civil Tech Spec. annexure is included & will be done as per site requirement in consultation with EIC. N.B.: The above 3 items are to be read in conjunction with Sl. No. 32 of Civil Tech Spec. annexure. |
| 128 | Earthwork in filling of foundation trenches or plinth with good earth, in layers not exceeding 150mm including watering and ramming etc. layer by layer as per approved drawing, including labour & technical specification, requirement complete. |
| 129 | Concreting with Cement Concrete M-10 grade including supply of all materials and labour inclusive of shuttering as per Technical Specification and approved drawing complete. |
| 130 | Filling below foundation with medium coarse saturated sand (F.M of 2.6 to 2.9) including supply of all materials, labour & laying as per Technical Specification and approved drawing complete. |
| 131 | 1st Class Clay Brick Work in foundation including supply of all materials & labour complete as per Technical Specification and approved drawing complete and as per decision/direction of the EIC. |
| 132 | 125thk. Brick wall with cement mortar (1:6) |
| 133 | 2.0 ELECTRICAL PART : |
| 134 | 145KV 31.5KA for 3sec Gas Insulated Switchgear matching with existing system i) 2000 A rated Double Bus Bar /Matching with existing systemii) 3 phase / single phase encapsulated iii) Minimum 2000 A rated Circuit Breaker iv) CT with current ratio as per CT specificationv) Each feeder comprises of Circuit Breaker, Disconnectors, CTs, Bus bar, density monitors, gas partition etc.vi) suitable for XLPE cable Entry matching with existing system vii) Local Control Cubicle (LCC) with all required accessories and Gas monitoring system. matching with existing system.-The complete system shall be as per technical specification and requirement and matching with existing system comprising of - |
| 135 | Feeder Bay |
| 136 | Adapter unit |
| 137 | SURGE ARRESTOR As per Technical Specification |
| 138 | SURGE ARRESTOR (1 - ɸ) - 120 KV, 10 KA, Heavy Duty, Metal Oxide , Gapless , Polymer Housed |
| 139 | CVT As per Technical specification |
| 140 | 145 KV line CVT |
| 141 | CONTROL & PROTECTION PANEL matching with the existing system inclusive of all relays, Annunciator (Minimum 24 windows or more as per scheme requirement, with RS485 port for Modbus Communication, Auxiliary AC and DC Supply as well as Dedicated AC Fail and DC Fail windows) at each panel and other accessories as per specificaction and requirement. (Protection Panels will be installed in existing Panel Room.) |
| 142 | Protection panel with BCU and Breaker Control Switch for 132 KV Line Feeder. Panel will have 2 nos. Distance Protection Relays of different manufacturer having different model, algorithm, hardware with group selection switch and all other accessories complete as per Tech Spec. |
| 143 | Integration of present 132 KV bays with existing 132 KV Bus Bar Differential Protection systems respectively inclusive of additional component as per actual requirement, so as to make the protection scheme work properly). Conductor, Clamps & connector etc |
| 144 | ACSR Moose CONDUCTORS as per Technical Specification droppers, jumpers as per requirement |
| 145 | CLAMPS, CONNECTORS & BUNDLE SPACER including equipment connectors as per Technical Specification and as per requirement |
| 146 | CONTROL CABLE (1.1 KV GRADE) as per Tech spec |
| 147 | Control cable 1.1KV grade( Cupper ) as per TECH Spec and as per requirement as per approved drawing and cable schedule for entire work including cable laying from ACDB & DCDB ,panel and any other equipment and also any equipments supplied by WBSETCL if any including Supply and installation of all required cables Actual quantity will be finalised as per approved drawing and cable schedule and as per requirement |
| 148 | POWER CABLE - Multi Core, PVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification and as per requirement (All cables shall be of Copper only.) |
| 149 | 4C X 25 sq. mmPVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification |
| 150 | 4C X 16 sq. mmPVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification |
| 151 | 4C X 10 sq. mmPVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification |
| 152 | 4C X 35 sq. mmPVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification |
| 153 | 4C X 50 sq. mmPVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification |
| 154 | 2C X 4 sq. mmPVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification |
| 155 | SUBSTATION EARTHING SYSTEM complete including GIS equipments and its accessories , Outdoor Switchyard and other installation of the Substation area. As per Tech specification. |
| 156 | Earthing for GIS enclosure, GS flat /GSS Earthwire for indoor and outdoor switchyard equipments etc. - as per requirement, technical specification and approved design/layout. |
| 157 | 6.6 KV/3.8 KV Copper bonding cable with suitable diameter as per Technical Specification |
| 158 | 1 ph Earth Link Box with SVL as per technical requirement / as per approved drawings. |
| 159 | 1 ph Earth Link Box with out SVL as per technical requirement / as per approved drawings. |
| 160 | Earth Strip and other accessories including lugs for link box etcwherever required for Earthing of all XLPE Cable completei as per technical requirement / as per approved drawings. |
| 161 | 1.1 KV 240 sqmm Copper earth continuity cable as per approved drawing and Technical specification |
| 162 | MISCELLANEOUS ITEMS as per technical specification and as per requirement |
| 163 | Danger plate, phase plate, bay nameplate, |
| 164 | Trefoil clam suitable for approved XLPE cable, fabrication marker, tags, protection cover tiles, pvc warning tape, route marker, jointing marker, clamps connector etc |
| 165 | HDPE Pipe 150mm Dia |
| 166 | Communication Equipment (As per technical specification, BOQ and mentioned Annexure) |
| 167 | E-1 Port Interfacing Cable |
| 168 | Digital Teleprotection Coupler suitable for integration with SDH terminal equipment to communicate on G 703 (E1, 2 Mbps) with minimum Eight commands as per Technical Specification requirement. |
| 169 | Integration (including data base creation) of newly constructed 132KV bays with existing SAS with supply of all hardware and software as per approved drawing, system requirement and technical specification. |
| 170 | Integration of newly constructed 132KV bays at SLDC & Back up SLDC (including data base creation) with supply of hardware and software as per system requirement and as per technical specification. |
| 171 | XLPE Copper Cable as per technical Specification |
| 172 | 132 KV 1200 sq.m Single core Aluminium corrugated copper cable |
| 173 | Outdoor End Termination Kit |
| 174 | For 132 KV 1200 sq.mm XLPE Copper Cable |
| 175 | Indoor End Termination Kit: |
| 176 | For 132 KV 1200 sqmm Sq mm single core copper cable for Line |
| 177 | Illumination system for outdoor switchyard for extension portion of existing switchyard area. |
| 178 | CIVIL PART : |
| 179 | Supply, fabrication, galvanisaton of various switchyard & equipment structures, LM / High Mast ( 35Mtr or 50 Mtr-based on DSLP Calculation), XLPE cable supporting structure complete as per approved electrical layout drawings and technical specification (Electrical & civil) and as per requirement complete. |
| 180 | Switchyard Structures including Nuts & Bolts |
| 181 | Foundation Bolts for switchyard structures including nuts, washers and anchor plates (Foundation Bolts shall be galvanisedupto threaded length from top) |
| 182 | 2.0 ELECTRICAL PART : |
| 183 | 145KV 31.5KA for 3sec Gas Insulated Switchgear matching with existing system i) 2000 A rated Double Bus Bar /Matching with existing systemii) 3 phase / single phase encapsulated iii) Minimum 2000 A rated Circuit Breaker iv) CT with current ratio as per CT specificationv) Each feeder comprises of Circuit Breaker, Disconnectors, CTs, Bus bar, density monitors, gas partition etc.vi) suitable for XLPE cable Entry matching with existing system vii) Local Control Cubicle (LCC) with all required accessories and Gas monitoring system. matching with existing system.-The complete system shall be as per technical specification and requirement and matching with existing system comprising of - |
| 184 | Feeder Bay |
| 185 | Adapter unit |
| 186 | SURGE ARRESTOR As per Technical Specification |
| 187 | SURGE ARRESTOR (1 - ɸ) - 120 KV, 10 KA, Heavy Duty, Metal Oxide , Gapless , Polymer Housed |
| 188 | CVT As per Technical specification |
| 189 | 145 KV line CVT |
| 190 | CONTROL & PROTECTION PANEL matching with the existing system inclusive of all relays, Annunciator (Minimum 24 windows or more as per scheme requirement, with RS485 port for Modbus Communication, Auxiliary AC and DC Supply as well as Dedicated AC Fail and DC Fail windows) at each panel and other accessories as per specificaction and requirement. (Protection Panels will be installed in existing Panel Room.) |
| 191 | Protection panel with BCU and Breaker Control Switch for 132 KV Line Feeder. Panel will have 2 nos. Distance Protection Relays of different manufacturer having different model, algorithm, hardware with group selection switch and all other accessories complete as per Tech Spec. |
| 192 | Integration of present 132 KV bays with existing 132 KV Bus Bar Differential Protection systems respectively inclusive of additional component as per actual requirement, so as to make the protection scheme work properly). Conductor, Clamps & connector etc |
| 193 | ACSR Moose CONDUCTORS as per Technical Specification droppers, jumpers as per requirement |
| 194 | CLAMPS, CONNECTORS & BUNDLE SPACER including equipment connectors as per Technical Specification and as per requirement |
| 195 | CONTROL CABLE (1.1 KV GRADE) as per Tech spec |
| 196 | Control cable 1.1KV grade( Cupper ) as per TECH Spec and as per requirement as per approved drawing and cable schedule for entire work including cable laying from ACDB & DCDB ,panel and any other equipment and also any equipments supplied by WBSETCL including Supply and installation of all required cables Actual quantity will be finalised as per approved drawing and cable schedule and as per requirement |
| 197 | POWER CABLE - Multi Core, PVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification and as per requirement (All cables shall be of Copper only.) |
| 198 | 4C X 25 sq. mmPVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification |
| 199 | 4C X 16 sq. mmPVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification |
| 200 | 4C X 10 sq. mmPVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification |
| 201 | 4C X 35 sq. mmPVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification |
| 202 | 4C X 50 sq. mmPVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification |
| 203 | 2C X 4 sq. mmPVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification |
| 204 | SUBSTATION EARTHING SYSTEM complete including GIS equipments and its accessories , Outdoor Switchyard and other installation of the Substation area. As per Tech specification. |
| 205 | Earthing for GIS enclosure, GS flat /GSS Earthwire for indoor and outdoor switchyard equipments etc. - as per requirement, technical specification and approved design/layout. |
| 206 | 6.6 KV/3.8 KV Copper bonding cable with suitable diameter as per Technical Specification |
| 207 | 1 ph Earth Link Box with SVL as per technical requirement / as per approved drawings. |
| 208 | 1 ph Earth Link Box with out SVL as per technical requirement / as per approved drawings. |
| 209 | Earth Strip and other accessories including lugs for link box etcwherever required for Earthing of all XLPE Cable completei as per technical requirement / as per approved drawings. |
| 210 | 1.1 KV 240 sqmm Copper earth continuity cable as per approved drawing and Technical specification |
| 211 | MISCELLANEOUS ITEMS as per technical specification and as per requirement |
| 212 | Danger plate, phase plate, bay nameplate, |
| 213 | Trefoil clam suitable for approved XLPE cable, fabrication marker, tags, protection cover tiles, pvc warning tape, route marker, jointing marker, clamps connector etc |
| 214 | HDPE Pipe 150mm Dia |
| 215 | Communication Equipment (As per technical specification, BOQ and mentioned Annexure) |
| 216 | Erection of Digital Teleprotection Coupler as per requirement, technical specification and supply BOQ |
| 217 | Integration of newly constructed 132KV bays at local end, SLDC and back up SLDC (including data base creation) as per requirement of technical specification by directly communicating with concerned OEM at local end and agency engaged for AMC of SCADA at SLDC and Back up SLDC End respectively . |
| 218 | XLPE Copper Cable as per technical Specification |
| 219 | 132 KV 1200 sq.m Single core Aluminium corrugated copper cable |
| 220 | Outdoor End Termination Kit |
| 221 | For 132 KV 1200 sq.mm XLPE Copper Cable |
| 222 | Indoor End Termination Kit: |
| 223 | For 132 KV 1200 sqmm Sq mm single core copper cable for Line |
| 224 | Illumination system for outdoor switchyard for extension portion of existing switchyard area. |
| 225 | CIVIL PART : |
| 226 | Supply, fabrication, galvanisaton of various switchyard & equipment structures , Additional LM Structure (to achieve necessay DSLP which is in the vendor scope) etc. (including foundation bolts and other nuts & bolts) complete as per approved electrical layout drawings and specification and as per requirement. CIVIL Part: 2NOS LINE BAY AT MANBAZAR 132KV S/S |
| 227 | Survey work (topography & contour) & setting out of layout as per bid drawing so as to match the land ulitilisation plan drawing as per technical specification, requirement complete. |
| 228 | Chilchaling, dressing and levelling for proposed scope of work as per tender drawing, Technical Specification and requirement complete. |
| 229 | Dismantling of existing structures (RCC / Bituminous road, cable trench including cable pull pit, storm water drain, switchyard pedestals, foundations / RCC,Steel Structures, yard PCC complete) as per requirement including removal of spoils as per instruction of the Engineer in charge. Serviceable materials (if any) are to be handed over to WBSETCL / WBSEDCL as per direction of EIC. N.B.: Lead distance of dismantled debris/non serviceable materials shall be finalized in consultation with EIC and as suit to site. |
| 230 | Planning, design & construction of GIS foundation and necessary arrangement for fixing of GIS equipment matching with existing flooring (over newly constructed foundation) inside the GIS building alongwith modification and construction of indoor cable trench (if required) as per civil technical specification, approved drawing & requirement complete. |
| 231 | Planning & construction of cut-outs on GIS Floor inside GIS building with necessary sealing arrangement (including mending good damages of RCC floor) as per approved drawing, civil technical specification & requirement complete. Necessary structural modification of RCC building as may be required are to be done at site in line with approved drawing and requirement complete. |
| 232 | 50MM thk IPS with Metallic hardener flooring and skirting with necessary underlay complete including supply of all materials and labour complete as per Technical Specification,approved drawing and as per direction of the EIC. |
| 233 | Laying of epoxy paint (in line with the manufacturer specification) of approved colour over the metallic hardener flooring as per direction of the EIC including supply of all materials and labour complete. However application of the paint shall be done at site by the authorized applicator of the paint manufacturer. |
| 234 | Design & constructions of foundations for various switchyard Tower structures, LM Lattice type, equipment structures (if any), drain (if required) including other Electro-mechanical equipment as per requirement as indicated in Electrical Schedule of Works and as per approved foundation layout drawing, foundation drawings and specification complete. |
| 235 | Concreting in sub-structure with Reinforced Cement Concrete M-20 grade including supply of all materials, labour & tools and tackles as required Including shuttering & Supply & Laying of Reinforcement (for main, distribution bars, spacers, stirrups/links, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection) complete as per drawing and Technical Specification etc. requirement complete (thw work is to be executed in line with approved drawing and as per decision/direction of the EIC). as per Technical Specification and approved drawing complete. Dewatering & shoring shall be done as per site requirement in consultation with EIC.N.B:The above item is inclusive of setting out & holding down Anchor fastener (i/c supply as required) / foundation bolts with Nut including anchor plate, washer (at bottom fitted complete and packing the hole with cement concrete or cement grout (as per civil tech. spec.). |
| 236 | Design & construction of outdoor cable trench including trench cover ( excluding supply of cable tray with M.S angles and Flats etc.) as per requirement within switchyard complete as per approved drawing, specification and requirement. |
| 237 | Concreting in sub-structure with Reinforced Cement Concrete M-20 grade including supply of all materials, labour & tools and tackles as required Including shuttering & Supply of Reinforcement (for main, distribution bars, spacers, stirrups/links, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection) complete as per drawing and Technical Specification etc. requirement complete (thw work is to be executed in line with approved drawing and as per decision/direction of the EIC). as per Technical Specification and approved drawing complete. Dewatering & shoring is to be done as per site requirement in consultation with EIC. |
| 238 | Fitting and fixing of all M.S. structural steel, Insert plate, MS FLAT, MS Grating etc. in outdoor cable trench and drain with simple rolled structural members (e.g. joists, angle, channel sections conforming to IS: 226, IS: 808 & SP (6)- 1964 connected to one another with bracket, gussets, cleats as per design, direction of Engineer-incharge complete including cutting to requisite shape and length, fabrication with necessary bolting, metal arc welding conforming to IS: 816- 1969 & IS: 1995 using electrodes of approved make and brand conforming to IS:814- 2004, haulage, hoisting and erection including supply of all materials, tool tackles and labour complete as per Technical Specification & approved drawing. Steel work shall be painted with one coat of primer and two coats of paint in line with civil tech spec and requirement complete. |
| 239 | EARTHING SYSTEM COMPLETE |
| 240 | Supplying & Laying of 100 mm thick Crushed stone /gravel (if required after using the existing crushed stone/gravel) matching with the existing one within the earthmat area as per approved layout and Technical Specification. |
| 241 | Removal of existing gravels/crushed stone (including dismantling of PCC under the gravel as required) & stacking the same in covenient location for future use after necessary cleaning & washing . |
| 242 | Relaying of existing Crushed stone as available from stacking of crushed stone as per approved layout and Technical Specification & requirement complete. |
| 243 | Laying of 75 mm thick P.C.C (1:4:8) with Jhama bricks at switch yard earthmat area including supply of all materials & labour complete as per Technical Specification and approved drawing complete and as per direction of the EIC. |
| 244 | MISCLLANEOUS ITEMS (As will be required for successful commisioning of the work in all respect) |
| 245 | Earthwork in excavation of foundation up to 1.5M in all sorts of soil including removing, spreading or stacking the spoils within a lead of 75 M or as directed. The items includes necessary trimming the sides of trenches, levelling, dressing and ramming the bottom, bailing out water as per approved drawing, technical specification,including labour & requirement complete. |
| 246 | Earthwork in excavation of foundation from 1.5M to 3.0M in all sorts of soil including removing, spreading or stacking the spoils within a lead of 75 M or as directed. The items includes necessary trimming the sides of trenches, levelling, dressing and ramming the bottom, bailing out water as per approved drawing, technical specification,including labour & requirement complete. |
| 247 | Earthwork in excavation of foundation from 3.0M to 4.0M in all sorts of soil including removing, spreading or stacking the spoils within a lead of 75 M or as directed. The items includes necessary trimming the sides of trenches, levelling, dressing and ramming the bottom, bailing out water as per approved drawing, technical specification,including labour & requirement complete.Sl. No. 32 of Civil Tech Spec. annexure is included & will be done as per site requirement in consultation with EIC. N.B.: The above 3 items are to be read in conjunction with Sl. No. 32 of Civil Tech Spec. annexure. |
| 248 | Earthwork in filling of foundation trenches or plinth with good earth, in layers not exceeding 150mm including watering and ramming etc. layer by layer as per approved drawing, including labour & technical specification, requirement complete. |
| 249 | Concreting with Cement Concrete M-10 grade including supply of all materials and labour inclusive of shuttering as per Technical Specification and approved drawing complete. |
| 250 | Filling below foundation with medium coarse saturated sand (F.M of 2.6 to 2.9) including supply of all materials, labour & laying as per Technical Specification and approved drawing complete. |
| 251 | 1st Class Clay Brick Work in foundation including supply of all materials & labour complete as per Technical Specification and approved drawing complete and as per decision/direction of the EIC. |
| 252 | 125thk. Brick wall with cement mortar (1:6) |
| 253 | 2.0 ELECTRICAL PART : |
| 254 | CIRCUIT BREAKER : 132 KV, 1600 A, 31.5 KA for 3sec, SF6, 1 Pole/ ph , 3Ph , Gang Operated and as per Technical Specification with support structure complete |
| 255 | ISOLATORS |
| 256 | 132 KV, 1250 A,31.5 KA for 3sec, HCB, motor operated 3-phase Assembly WITH EARTHING SWITCH (excluding insulators) |
| 257 | Solid Core Insulator for each set of above Isolators |
| 258 | 132 KV, 1250 A,31.5 KA for 3sec, HCB, motor operated 3-phase Assembly WITHOUT EARTHING SWITCH (excluding insulators) |
| 259 | Solid Core Insulator for each set of above Isolators |
| 260 | SURGE ARRESTOR As per Technical Specification |
| 261 | SURGE ARRESTOR (1 - ɸ) - 120 KV, 10 KA, Heavy Duty, Metal Oxide , Gapless , Polymer Housed |
| 262 | CURRENT TRANSFORMER |
| 263 | 145 KV CURRENT TRANSFORMER (1 - ɸ) - Feeder (1000-800-400/1A, 5 cores) |
| 264 | CVT As per Technical specification |
| 265 | 145 KV line CVT |
| 266 | Control & Relay Panel |
| 267 | 132 KV Duplex type C&R Panel - for Feeder including 2 nos distance protection relay of different manufacturer having different model, algorithm, hardware with group selection switch Annunciator and other relays as per Technical Specification and matching with existing panels. |
| 268 | 132 KV Solid Core POST INSULATOR with hardware fittings and accessories as per Technical Specification and requirement |
| 269 | DISC INSULATORS as per Technical Specification and as per requirement |
| 270 | HARDWARE FITTINGS and ACCESSORIES for SUSPENSION & TENSION Insulator String as per Technical Specification for extension of Main Bus & transfer Bus and others as per requirements (without Disc) |
| 271 | 2.5 \\"IPS ALUMINIUM TUBULAR PIPE as per Technical Specification and as per requirement |
| 272 | ACSR Moose CONDUCTORS as per Technical Specification for extension of Main Bus ,Transfer Bus and droppers, jumpers as per requirement |
| 273 | CLAMPS, CONNECTORS & BUNDLE SPACER including equipment connectors as per Technical Specification and as per requirement |
| 274 | CONTROL CABLE (1.1 KV GRADE) as per Tech spec |
| 275 | Control cable 1.1KV grade( Cupper ) as per TECH Spec and as per requirement as per approved drawing and cable schedule for entire work including cable laying from ACDB & DCDB ,panel and switchyard equipment and also any equipments supplied by WBSETCL if any including Supply and installation of all required cables Actual quantity will be finalised as per approved drawing and cable schedule and as per requirement |
| 276 | POWER CABLE - Multi Core, PVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification and as per requirement (All cables shall be of Copper only.) |
| 277 | 3.5 core 25 sqmm PVC, Armoured AL as per Technical Specification. |
| 278 | 3.5 core 35 sqmm PVC, Armoured AL as per Technical Specification. |
| 279 | 2 core 10 sqmm PVC, Armoured AL as per Technical Specification. |
| 280 | SUBSTATION EARTHING SYSTEM complete including GIS equipments and its accessories , Outdoor Switchyard and other installation of the Substation area. As per Tech specification. |
| 281 | 32mm dia or higher MS rod for main earthmat grid, corner mesh and periphry for outdoor switchyard . The actual quantity shall be finalised depending on the approved design (Only design quantity with lap length without any wastage for main mat, periphery & corner mesh will be considered for payment.) The Earthmat design is to be done as per Technical Specification & matching with existing system. |
| 282 | 32mm dia or higher MS rod for riser below and above ground auxiliary Mat fencing and gate earthing bending length and overlapping length |
| 283 | GS flat for riser above ground / cable trench & other areas. Rod/pipe electrode , test link and other materials etc. - as per requirement, technical specification and approved design/layout including earthpit. |
| 284 | MISCELLANEOUS ITEMS as per technical specification and as per requirement |
| 285 | Bay marshalling kiosk |
| 286 | junction box for CT/CVT |
| 287 | Distribution Boards |
| 288 | Angle channels ferrul etc |
| 289 | Danger plate, phase plate, bay nameplate, |
| 290 | Cable Tray |
| 291 | Illumination system for outdoor switchyard for extension portion of existing switchyard area. |
| 292 | Fire protection system including hydrant & extinguisher for extended portion of existing switchyard area matching with existing system including diversion of fire hydrant system if any in case of obstructing new construction work. |
| 293 | Communication Equipment (As per technical specification, BOQ and mentioned Annexure) |
| 294 | E-1 Port Interfacing Cable |
| 295 | Digital Teleprotection Coupler suitable for integration with SDH terminal equipment to communicate on G 703 (E1, 2 Mbps) with minimum Eight commands as per Technical Specification requirement. |
| 296 | Integration (including data base creation) of newly constructed 132KV bays with existing RTU with supply of all hardware and software as per approved drawing, system requirement and technical specification. |
| 297 | Integration of newly constructed 132KV bays at SLDC & Back up SLDC (including data base creation) with supply of hardware and software as per system requirement and as per technical specification. CIVIL PART : |
| 298 | Supply, fabrication, galvanisaton of various switchyard & equipment structures, LM / High Mast ( 35Mtr or 50 Mtr-based on DSLP Calculation), XLPE cable supporting structure complete as per approved electrical layout drawings and technical specification (Electrical & civil) and as per requirement complete. |
| 299 | Switchyard Structures including Nuts & Bolts |
| 300 | Foundation Bolts for switchyard structures including nuts, washers and anchor plates (Foundation Bolts shall be galvanisedupto threaded length from top) |
| 301 | 2.0 ELECTRICAL PART : |
| 302 | CIRCUIT BREAKER : 132 KV, 1600 A, 31.5 KA for 3sec, SF6, 1 Pole/ ph , 3Ph , Gang Operated and as per Technical Specification with support structure complete |
| 303 | ISOLATORS |
| 304 | 132 KV, 1250 A,31.5 KA for 3sec, HCB, motor operated 3-phase Assembly WITH EARTHING SWITCH (excluding insulators) |
| 305 | Solid Core Insulator for each set of above Isolators |
| 306 | 132 KV, 1250 A,31.5 KA for 3sec, HCB, motor operated 3-phase Assembly WITHOUT EARTHING SWITCH (excluding insulators) |
| 307 | Solid Core Insulator for each set of above Isolators |
| 308 | SURGE ARRESTOR As per Technical Specification |
| 309 | SURGE ARRESTOR (1 - ɸ) - 120 KV, 10 KA, Heavy Duty, Metal Oxide , Gapless , Polymer Housed |
| 310 | CURRENT TRANSFORMER |
| 311 | 145 KV CURRENT TRANSFORMER (1 - ɸ) - Feeder (1000-800-400/1A, 5 cores) |
| 312 | CVT As per Technical specification |
| 313 | 145 KV line CVT |
| 314 | Control & Relay Panel |
| 315 | 132 KV Duplex type C&R Panel - for Feeder including 2 nos distance protection relay of different manufacturer having different model, algorithm, hardware with group selection switch,Annunciator and other relays as per Technical Specification and matching with existing panels. |
| 316 | 132 KV Solid Core POST INSULATOR with hardware fittings and accessories as per Technical Specification and requirement |
| 317 | DISC INSULATORS as per Technical Specification and as per requirement |
| 318 | HARDWARE FITTINGS and ACCESSORIES for SUSPENSION & TENSION Insulator String as per Technical Specification for extension of Main Bus & transfer Bus and others as per requirements (without Disc) |
| 319 | 2.5 \\"IPS ALUMINIUM TUBULAR PIPE as per Technical Specification and as per requirement |
| 320 | ACSR Moose CONDUCTORS as per Technical Specification for extension of Main Bus ,Transfer Bus and droppers, jumpers as per requirement |
| 321 | CLAMPS, CONNECTORS & BUNDLE SPACER including equipment connectors as per Technical Specification and as per requirement |
| 322 | CONTROL CABLE (1.1 KV GRADE) as per Tech spec |
| 323 | Control cable 1.1KV grade( Cupper ) as per TECH Spec and as per requirement as per approved drawing and cable schedule for entire work including cable laying from ACDB & DCDB ,panel and all switchyard equipment and also any equipments supplied by WBSETCL if any including Supply and installation of all required cables Actual quantity will be finalised as per approved drawing and cable schedule and as per requirement |
| 324 | POWER CABLE - Multi Core, PVC, Armoured, 1.1 KV POWER CABLE (AL) as per Technical Specification and as per requirement (All cables shall be of Copper only.) |
| 325 | 3.5 core 25 sqmm PVC, Armoured AL as per Technical Specification. |
| 326 | 3.5 core 35 sqmm PVC, Armoured AL as per Technical Specification. |
| 327 | 2 core 10 sqmm PVC, Armoured AL as per Technical Specification. |
| 328 | SUBSTATION EARTHING SYSTEM complete including GIS equipments and its accessories , Outdoor Switchyard and other installation of the Substation area. As per Tech specification. |
| 329 | 32mm dia or higher MS rod for main earthmat grid, corner mesh and periphry for outdoor switchyard . The actual quantity shall be finalised depending on the approved design (Only design quantity with lap length without any wastage for main mat, periphery & corner mesh will be considered for payment.) The Earthmat design is to be done as per Technical Specification & matching with existing system. |
| 330 | 32mm dia or higher MS rod for riser below and above ground auxiliary Mat fencing and gate earthing bending length and overlapping length |
| 331 | GS flat for riser above ground / cable trench & other areas. Rod/pipe electrode , test link and other materials etc. - as per requirement, technical specification and approved design/layout including earthpit. |
| 332 | MISCELLANEOUS ITEMS as per technical specification and as per requirement |
| 333 | Bay marshalling kiosk |
| 334 | junction box for CT/CVT |
| 335 | Distribution Boards |
| 336 | Angle channels ferrul etc |
| 337 | Danger plate, phase plate, bay nameplate, |
| 338 | Cable Tray |
| 339 | Illumination system for outdoor switchyard for extension portion of existing switchyard area. |
| 340 | Fire protection system including hydrant & extinguisher for extended portion of existing switchyard area matching with existing system including diversion of fire hydrant system if any in case of obstructing new construction work. |
| 341 | Communication Equipment (As per technical specification, BOQ and mentioned Annexure) |
| 342 | Erection of Digital Teleprotection Coupler as per requirement, technical specification and supply BOQ |
| 343 | Integration of newly constructed 132KV bays at local end, SLDC and back up SLDC (including data base creation) as per requirement of technical specification by directly communicating with concerned OEM at local end and agency engaged for AMC of SCADA at SLDC and Back up SLDC End respectively . CIVIL PART : |
| 344 | Supply, fabrication, galvanisaton of various switchyard & equipment structures , Additional LM Structure (to achieve necessay DSLP which is in the vendor scope) etc. (including foundation bolts and other nuts & bolts) complete as per approved electrical layout drawings and specification and as per requirement. CIVIL Part: 4NOS LINE BAY AT KHATRA 132KV S/S |
| 345 | Survey work (topography & contour) & setting out of layout as per bid drawing so as to match the land ulitilisation plan drawing as per technical specification, requirement complete. |
| 346 | Chilchaling, dressing and levelling for proposed scope of work as per tender drawing, Technical Specification and requirement complete. |
| 347 | Dismantling of existing structures (RCC / Bituminous road, cable trench including cable pull pit, storm water drain, switchyard pedestals, foundations / RCC,Steel Structures, yard PCC complete) as per requirement including removal of spoils as per instruction of the Engineer in charge. Serviceable materials (if any) are to be handed over to WBSETCL / WBSEDCL as per direction of EIC. N.B.: Lead distance of dismantled debris/non serviceable materials shall be finalized in consultation with EIC and as suit to site. |
| 348 | Design & constructions of foundations for various switchyard Tower structures, LM Lattice type, equipment structures (if any), drain (if required) including other Electro-mechanical equipment as per requirement as indicated in Electrical Schedule of Works and as per approved foundation layout drawing, foundation drawings and specification complete. |
| 349 | Concreting in sub-structure with Reinforced Cement Concrete M-20 grade including supply of all materials, labour & tools and tackles as required Including shuttering & Supply & Laying of Reinforcement (for main, distribution bars, spacers, stirrups/links, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection) complete as per drawing and Technical Specification etc. requirement complete (thw work is to be executed in line with approved drawing and as per decision/direction of the EIC). as per Technical Specification and approved drawing complete. Dewatering & shoring shall be done as per site requirement in consultation with EIC.N.B:The above item is inclusive of setting out & holding down Anchor fastener (i/c supply as required) / foundation bolts with Nut including anchor plate, washer (at bottom fitted complete and packing the hole with cement concrete or cement grout (as per civil tech. spec.). |
| 350 | Design & construction of outdoor cable trench including trench cover ( excluding supply of cable tray with M.S angles and Flats etc.) as per requirement within switchyard complete as per approved drawing, specification and requirement. |
| 351 | Concreting in sub-structure with Reinforced Cement Concrete M-20 grade including supply of all materials, labour & tools and tackles as required Including shuttering & Supply of Reinforcement (for main, distribution bars, spacers, stirrups/links, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection) complete as per drawing and Technical Specification etc. requirement complete (thw work is to be executed in line with approved drawing and as per decision/direction of the EIC). as per Technical Specification and approved drawing complete. Dewatering & shoring is to be done as per site requirement in consultation with EIC. |
| 352 | Fitting and fixing of all M.S. structural steel, Insert plate, MS FLAT, MS Grating etc. in outdoor cable trench and drain with simple rolled structural members (e.g. joists, angle, channel sections conforming to IS: 226, IS: 808 & SP (6)- 1964 connected to one another with bracket, gussets, cleats as per design, direction of Engineer-incharge complete including cutting to requisite shape and length, fabrication with necessary bolting, metal arc welding conforming to IS: 816- 1969 & IS: 1995 using electrodes of approved make and brand conforming to IS:814- 2004, haulage, hoisting and erection including supply of all materials, tool tackles and labour complete as per Technical Specification & approved drawing. Steel work shall be painted with one coat of primer and two coats of paint in line with civil tech spec and requirement complete. |
| 353 | EARTHING SYSTEM COMPLETE |
| 354 | Supplying & Laying of 100 mm thick Crushed stone /gravel (if required after using the existing crushed stone/gravel) matching with the existing one within the earthmat area as per approved layout and Technical Specification. |
| 355 | Removal of existing gravels/crushed stone (including dismantling of PCC under the gravel as required) & stacking the same in covenient location for future use after necessary cleaning & washing . |
| 356 | Relaying of existing Crushed stone as available from stacking of crushed stone as per approved layout and Technical Specification & requirement complete. |
| 357 | Laying of 75 mm thick P.C.C (1:4:8) with Jhama bricks at switch yard earthmat area including supply of all materials & labour complete as per Technical Specification and approved drawing complete and as per direction of the EIC. |
| 358 | MISCLLANEOUS ITEMS (As will be required for successful commisioning of the work in all respect) |
| 359 | Earthwork in excavation of foundation up to 1.5M in all sorts of soil including removing, spreading or stacking the spoils within a lead of 75 M or as directed. The items includes necessary trimming the sides of trenches, levelling, dressing and ramming the bottom, bailing out water as per approved drawing, technical specification,including labour & requirement complete. |
| 360 | Earthwork in excavation of foundation from 1.5M to 3.0M in all sorts of soil including removing, spreading or stacking the spoils within a lead of 75 M or as directed. The items includes necessary trimming the sides of trenches, levelling, dressing and ramming the bottom, bailing out water as per approved drawing, technical specification,including labour & requirement complete. |
| 361 | Earthwork in excavation of foundation from 3.0M to 4.0M in all sorts of soil including removing, spreading or stacking the spoils within a lead of 75 M or as directed. The items includes necessary trimming the sides of trenches, levelling, dressing and ramming the bottom, bailing out water as per approved drawing, technical specification,including labour & requirement complete.Sl. No. 32 of Civil Tech Spec. annexure is included & will be done as per site requirement in consultation with EIC. N.B.: The above 3 items are to be read in conjunction with Sl. No. 32 of Civil Tech Spec. annexure. |
| 362 | Earthwork in filling of foundation trenches or plinth with good earth, in layers not exceeding 150mm including watering and ramming etc. layer by layer as per approved drawing, including labour & technical specification, requirement complete. |
| 363 | Concreting with Cement Concrete M-10 grade including supply of all materials and labour inclusive of shuttering as per Technical Specification and approved drawing complete. |
| 364 | Filling below foundation with medium coarse saturated sand (F.M of 2.6 to 2.9) including supply of all materials, labour & laying as per Technical Specification and approved drawing complete. |
| 365 | 1st Class Clay Brick Work in foundation including supply of all materials & labour complete as per Technical Specification and approved drawing complete and as per decision/direction of the EIC. |
| 366 | 125thk. Brick wall with cement mortar (1:6) |
| 367 | 2.0 PART - I |
| 368 | Standard suspension 132 KV D/C 'DA' type towers (0o to 2o) Superstructure Stub - set of 4 upto 6 metre body extension |
| 369 | Standard small angle 132 KV D/C 'DB' type towers (0o to 15o) Superstructure Stub - set of 4 upto 6 metre body extension |
| 370 | Standard medium angle 132 KV D/C 'DC' type towers (15o to 30o) Superstructure Stub - set of 4 upto 6 metre body extension |
| 371 | Standard large angle 132 KV D/C 'DD' type towers (30o to 60o) & Dead end Superstructure Stub - set of 4 upto 6 metre body extension Stub - set of 4 upto for 9/15 metre body extension |
| 372 | Standard large angle 220 KV D/C 'LT2' type Anchor towers (30o to 60o) & Dead end Superstructure Stub - set of 4 upto 6 metre extension |
| 373 | River Crossing (RC) Tower (+35 Mtr. Extn.) Superstructure Stub - set of 4 |
| 374 | Extensions only : +3 Metre Body Extension for 132 KV 'DA' type tower +6 Metre Body Extension for 132 KV 'DA' type tower +3 Metre Body Extension for 132 KV 'DB' type tower +6 Metre Body Extension for 132 KV 'DB' type tower +3 Metre Body Extension for 132 KV 'DC' type tower +6 Metre Body Extension for 132 KV 'DC' type tower +3 Metre Body Extension for 132 KV 'DD' type tower +6 Metre Body Extension for 132 KV 'DD' type tower +15 Metre Body Extension for 132 KV 'DD' type tower +6 Metre Body Extension for 220KV 'LT2' type tower |
| 375 | Number Plate |
| 376 | Danger Plate |
| 377 | Phase Plate (in sets of three Red, Yellow, Blue) |
| 378 | Complete pipe type grounding material for tower |
| 379 | Barbed wire type anti-climbing device |
| 380 | Special Tower / Tower structure (For power line x-ing, river x-ing, rail x-ing, N.H. x-ing, auxiliary x-arm, extended stub etc.for all non-scheduled tower/tower structure) Superstructure (per tonne rate to be quoted) Fabricated members (MS) Bolts & nuts Stub (per tonne rate to be quoted) Fabricated members (MS) Bolts & nuts PART - II |
| 381 | ACSR Panther CONDUCTOR (As Per Tech Spec) : STANDARD LENGTH (KM) |
| 382 | COMPOSITE FIBER OPTIC OVERHEAD EARTHWIRE (48F OPGW) STANDARD LENGTH (KM) AS PER TECHNICAL SPECIFICATION |
| 383 | 24 FIBER OPTIC APPROACH CABLE (ARMOURED) INCLUDING ALL HARDWARES, TIES, CLIPS, CLEATS, CONDUITS, DUCTS, SUPPORTING FITTINGS ETC. AND OTHER MATERIALS WHICHEVER REQUIRED FOR COMPLETE INSTALLATION AS PER TECHNICAL SPECIFICATION AND REQUIREMENT. |
| 384 | SUPPLY OF 96F FIBER OPTIC DISTRIBUTION PANEL (FODP) (Dimension: 1400mm x 600mm x 600mm)SUITABLE FOR APPROACH CABLE INDOOR TYPE WITH FC-PC COUPLING AND PIGTAILS (DWSM FIBER) AS PER TECHNICAL SPECIFICATION (At Beledurganagar end) |
| 385 | 132 KV SUSPENSION INSULATOR STRING (70KN - Antifog Type) - 1x9Nos. PORCELENE DISC INSULATOR OR PORCELENE LONG ROD INSULATOR OR POLYMER LONG ROD INSULATOR |
| 386 | 132 KV TENSION INSULATOR STRING (120KN - Antifog Type) - 1x10Nos. PORCELENE DISC INSULATOR OR PORCELENE LONG ROD INSULATOR OR POLYMER LONG ROD INSULATOR |
| 387 | CONDUCTOR ACCESSORIES : MID SPAN COMPRESSION JOINT (suitable for ACSR Panther conductor - IN LINE WITH APPROVED DRUM SCHEDULE, in case of extreme excceptional situation) REPAIR SLEEVE (suitable for ACSR Panther conductor) VIBRATION DAMPER (suitable for ACSR Panther conductor - One set includes average quantity of Vibration Dampers required for one span as per approved drawing, design & specification) |
| 388 | 48F OPGW EARTHWIRE ACCESSORIES : VIBRATION DAMPER (One set includes average quantity of Vibration Dampers required for one span as per approved drawing, design & specification) SINGLE SUSPENSION CLAMP ASSEMBLY WITH EARTH BOND DOUBLE TENSION CLAMP ASSEMBLY (PASS THROUGH) WITH EARTH BOND SINGLE TENSION CLAMP ASSEMBLY WITH EARTH BOND DOWN LEAD CLAMP for OPGW (to be fixed at an interval of 1.5 mtr) OPGW HOLDER BRACKET JOINT BOX |
| 389 | INSULATOR HARDWARES : SINGLE SUSPENSION INSULATOR HARDWARE FITTINGS COMPLETE (A. G. Type) compatible to ACSR Panther conductor as per specification DOUBLE SUSPENSION INSULATOR HARDWARE FITTINGS COMPLETE (A. G. Type) compatible to ACSR ACSR Panther conductor as per specification SINGLE TENSION INSULATOR HARDWARE FITTINGS COMPLETE compatible to ACSR Panther conductor as per specification DOUBLE TENSION INSULATOR HARDWARE FITTINGS COMPLETE compatible to ACSR Panther conductor as per specification PILOT INSULATOR HARDWARE FITTINGS COMPLETE compatible to ACSR ACSR Panther conductor as per specification |
| 390 | (ERECTION) Detail Survey including route alignment preparation of profiles & Schedules of towers Check survey and final peg marking |
| 391 | Setting of stubs : 'DA' type 132 KV D/C towers (0° to 2°) up to +6 MBE 'DB' type 132 KV D/C towers(0° to 15°) up to +6 MBE DC' type 132 KV D/C towers(15° to 30°) up to +6 MBE 'DD' type 132 KV D/C towers(30° to 60°) & dead end up to +6 MBE 'DD' type 132 KV D/C towers (30° to 60°) & dead end for +9/15 MBE LT2' type 220 KV D/C 'towers (30o to 60o) & Dead end 220 KV D/C River Crossing (RC) Tower (+35 Mtr. Extn.) |
| 392 | Soil resistivity test as per specification and direction of EIC |
| 393 | Design and Construction of tower foundations in all types of soil and conditions as per foundation drawings approved by the purchaser including excavation, concreting (M-20 grade), over lean concrete (M-10 grade of 50 mm minimum thickness), steel reinforcement, shoring, shuttering, dewatering, backfilling with carried earth (where necessary) and/or excavated good soil, disposal of surplus soil, forms, mixing, placing, finishing, protection and curing of concrete with all cost of supply of materials such as cement, sand, coarse aggregate, water, reinforcement, mild steel angle etc. with all cost of labour, materials, tools, plants, incidentals etc. complete in all respect as per specification and/or as directed by the employer. Rates shall be quoted in respective price schedule on per tower basis 'DA' type 132 KV D/C tower foundation upto +6 M extension Dry Type Wet Type Partially sub-merged type Fully sub-merged type 'DB' type 132 KV D/C tower foundation upto +6 M extension Dry Type Wet Type Partially sub-merged type Fully sub-merged type 'DC' type 132 KV D/C tower foundation upto +6 M extension Dry Type Wet Type Partially sub-merged type Fully sub-merged type 'DD' type 132 KV D/C tower foundation upto +6 M extension Dry Type Wet Type Partially sub-merged type Fully sub-merged type 'DD' type 132 KV D/C tower foundation upto for +9/15 M extension Fully sub-merged type LT2' type 220 KV D/C 'towers (30o to 60o) & Dead end upto +6 M extension Partially sub-merged type Fully sub-merged type 220 KV D/C River Crossing (RC) Tower (+35 Mtr. Extn.) Fully sub-merged type |
| 394 | Superstructure erection of standard normal tower including all work above ground level including tack welding excluding hoisting of insulator, fitting of danger, number & phase plates and anticlimbing devices etc. 132 KV D/C 'DA' type towers 132 KV D/C 'DB' type towers 132 KV D/C 'DC' type towers 132 KV D/C 'DD' type & Dead end towers 220 KV D/C 'LT2' type & Dead end towers 220 KV D/C River Crossing (RC) Tower (+35 Mtr. Extn.) |
| 395 | Extensions only : +3 Metre Body Extension for 132 KV 'DA' type tower +6 Metre Body Extension for 132 KV 'DA' type tower +3 Metre Body Extension for 132 KV 'DB' type tower +6 Metre Body Extension for 132 KV 'DB' type tower +3 Metre Body Extension for 132 KV 'DC' type tower +6 Metre Body Extension for 132 KV 'DC' type tower +3 Metre Body Extension for 132 KV 'DD' type tower +6 Metre Body Extension for 132 KV 'DD' type tower +15 Metre Body Extension for 132 KV 'DD' type tower +6 Metre Body Extension for 220KV 'LT2' type tower |
| 396 | Laying, stringing, tensioning, clamping, jointing etc. complete of 6 nos. of ACSR PANTHER conductor including hoisting of insulators, armour rods, dampers and other accessories for complete route KM for double circuit line |
| 397 | Laying, stringing, tensioning, clamping, jointing etc. of one earthwire (48F-OPGW) including earth bonding with tower, fitting, fixing of all necessary accessories for complete route KM |
| 398 | Installation of approach cable (armoured) complete including ties, clips, cleats, conduits, ducts, supporting fittings etc. and other materials whichever and wherever required as per technical specificaiton |
| 399 | Installation of 96F FODP indoor type complete with all connections as per technical specificaiton and requirement (At Beledurganagar end) |
| 400 | Fittings of tower accessories : Number plate Danger plate Phase plate (in set of three) Barbed wire type anticlimbing devices |
| 401 | Grounding work for pipe earth including cost of coke, salt etc. including necessary excavation and backfilling complete |
| 402 | Erection of Special Tower / Tower structure (For power line x-ing, river x-ing, rail x-ing, N.H. x-ing, auxiliary x-arm, extended stub etc.all for non-scheduled tower/tower structure) Stub setting and footing work excluding the cost of excavation, concreting & back filling of Special Tower other than bored pile locations. Superstructure erection of Special Tower including tack welding |
| 403 | UNIT RATES : Concrete M-10 per cubic metre (CUM) including supply of cost of all materials complete, including dewatering Concrete M-20 per cubic metre (CUM) including dewatering, supply of all materials & shuttering but excluding reinforcement Supply, bending & binding of reinforcement rod including cost of binding material & labour complete |
| 404 | Earth Work : (Excavation including compacted back filling & required dewatering) Normal dry soil - Do - wet soil - Do - P.S. soil - Do - F.S. soil |
| 405 | Shoring of pits with shuttering, supply of materials & labour |
| 406 | Dewatering of Pits : Manual per man hour Mechanical pump (Rate to be quoted in H.P-Hr.) |
| 407 | Cost of Building revetments with bricks, with 1 : 6 cement morter including 12 mm thick cement plaster (1:4) and neat cement punning on all exposed surfaces, excavation per cubic metre of brickwork including supply of materials and transport |
| 408 | Back filling and levelling of the volume of earth enclosed by revetment walls. (Good earth arranged & supplied by the contractor) including supply of materials, transport etc. complete |
| 409 | Back filling with medium coarse sand in foundation trench/pit as per specification and/or as per direction (per cum.) |
| 410 | Cost of compaction of brick bats in foundation trench as per specification and/or as per direction (per cum.) of EIC including supply of all materials and transport complete |
| 411 | Soil testing as per relevant IS codes and direction of EIC Upto 10 M depth |
| 412 | Rivetment work by providing Sal-bullah / Eucalyptus bullah piles of diameter not less than 150mm, driving upto desired depth but not less than 4 m and spacing as per approved design and joining each bullah piles with the staging props by proper arrangement capable to transmit the loads from superstructure, including supply of pile, double coat coal tarring on wooden surface and all complete. Drum Sheet Walling to be provided of 1.40m (av.) high on Sal-bullah /Eucalyptus bullah piling 15 cm dia. and 3.25m long driven 1.75m (av.) below G.L. and 75cm centre to centre including fitting fixing 3 nos. of half bullah pieces (from 10 cm dia) and drum(empty bitumen) sheet (approved condition) of height 1.5m , cutting and straightening drum sheet (each joint must have lap length of min.50mm) including cost of necessary nails, bolts, nuts etc Note : 1. Diameter of bullah to be measured at 1.5 m from thicker end. Note : 2. Projected area of the deck on river bed should be considered for arriving at the cost. Rate to be quoted based on per meter length of pile |
| 413 | 2.0 PART - I |
| 414 | Standard suspension 132 KV D/C 'DA' type towers (0o to 2o) Superstructure Stub - set of 4 upto 6 metre body extension |
| 415 | Standard small angle 132 KV D/C 'DB' type towers (0o to 15o) Superstructure Stub - set of 4 upto 6 metre body extension |
| 416 | Standard medium angle 132 KV D/C 'DC' type towers (15o to 30o) Superstructure Stub - set of 4 upto 6 metre body extension |
| 417 | Standard large angle 132 KV D/C 'DD' type towers (30o to 60o) & Dead end Superstructure Stub - set of 4 upto 6 metre body extension |
| 418 | Standard large angle 'DWF' type dwarf towers (30o to 60o) & Dead end for power line crossing Superstructure Stub - set of 4 upto +6 metre extension |
| 419 | Extensions only : +3 Metre Body Extension for 132 KV 'DA' type tower +6 Metre Body Extension for 132 KV 'DA' type tower +3 Metre Body Extension for 132 KV 'DB' type tower +6 Metre Body Extension for 132 KV 'DB' type tower +3 Metre Body Extension for 132 KV 'DC' type tower +6 Metre Body Extension for 132 KV 'DC' type tower +3 Metre Body Extension for 132 KV 'DD' type tower +6 Metre Body Extension for 132 KV 'DD' type tower +3 Metre Body Extension for 132 KV 'DWF' type tower |
| 420 | Number Plate |
| 421 | Danger Plate |
| 422 | Phase Plate (in sets of three Red, Yellow, Blue) |
| 423 | Complete pipe type grounding material for tower |
| 424 | Barbed wire type anti-climbing device |
| 425 | Special Tower / Tower structure (For power line x-ing, river x-ing, rail x-ing, N.H. x-ing, auxiliary x-arm, extended stub etc.for all non-scheduled tower/tower structure). Superstructure (per tonne rate to be quoted) Fabricated members (MS) Bolts & nuts Stub (per tonne rate to be quoted) Fabricated members (MS) Bolts & nuts PART - II |
| 426 | ACSR Panther CONDUCTOR (As Per Tech Spec) : STANDARD LENGTH (KM) |
| 427 | COMPOSITE FIBER OPTIC OVERHEAD EARTHWIRE (48F OPGW) STANDARD LENGTH (KM) AS PER TECHNICAL SPECIFICATION |
| 428 | 24 FIBER OPTIC APPROACH CABLE (ARMOURED) INCLUDING ALL HARDWARES, TIES, CLIPS, CLEATS, CONDUITS, DUCTS, SUPPORTING FITTINGS ETC. AND OTHER MATERIALS WHICHEVER REQUIRED FOR COMPLETE INSTALLATION AS PER TECHNICAL SPECIFICATION AND REQUIREMENT. |
| 429 | SUPPLY OF 96F FIBER OPTIC DISTRIBUTION PANEL (FODP) (Dimension: 1400mm x 600mm x 600mm)SUITABLE FOR APPROACH CABLE INDOOR TYPE WITH FC-PC COUPLING AND PIGTAILS (DWSM FIBER) AS PER TECHNICAL SPECIFICATION (At Gazole end) |
| 430 | 132 KV SUSPENSION INSULATOR STRING (70KN - Antifog Type) - 1x9Nos. PORCELENE DISC INSULATOR OR PORCELENE LONG ROD INSULATOR OR POLYMER LONG ROD INSULATOR |
| 431 | 132 KV TENSION INSULATOR STRING (120KN - Antifog Type) -1x10Nos. PORCELENE DISC INSULATOR OR PORCELENE LONG ROD INSULATOR OR POLYMER LONG ROD INSULATOR |
| 432 | CONDUCTOR ACCESSORIES : MID SPAN COMPRESSION JOINT (suitable for ACSR Panther conductor - IN LINE WITH APPROVED DRUM SCHEDULE, in case of extreme excceptional situation) REPAIR SLEEVE (suitable for ACSR Panther conductor) VIBRATION DAMPER (suitable for ACSR Panther conductor - One set includes average quantity of Vibration Dampers required for one span as per approved drawing, design & specification) |
| 433 | 48F OPGW EARTHWIRE ACCESSORIES : VIBRATION DAMPER (One set includes average quantity of Vibration Dampers required for one span as per approved drawing, design & specification) SINGLE SUSPENSION CLAMP ASSEMBLY WITH EARTH BOND DOUBLE TENSION CLAMP ASSEMBLY (PASS THROUGH) WITH EARTH BOND SINGLE TENSION CLAMP ASSEMBLY WITH EARTH BOND DOWN LEAD CLAMP for OPGW (to be fixed at an interval of 1.5 mtr) OPGW HOLDER BRACKET JOINT BOX |
| 434 | INSULATOR HARDWARES : SINGLE SUSPENSION INSULATOR HARDWARE FITTINGS COMPLETE (A. G. Type) compatible to ACSR Panther conductor as per specification DOUBLE SUSPENSION INSULATOR HARDWARE FITTINGS COMPLETE (A. G. Type) compatible to ACSR ACSR Panther conductor as per specification SINGLE TENSION INSULATOR HARDWARE FITTINGS COMPLETE compatible to ACSR Panther conductor as per specification DOUBLE TENSION INSULATOR HARDWARE FITTINGS COMPLETE compatible to ACSR Panther conductor as per specification PILOT INSULATOR HARDWARE FITTINGS COMPLETE compatible to ACSR ACSR Panther conductor as per specification |
| 435 | ERECTION Detail Survey including route alignment preparation of profiles & Schedules of towers Check survey and final peg marking |
| 436 | Setting of stubs : 'DA' type 132 KV D/C towers up to +6 MBE 'DB' type 132 KV D/C towers up to +6 MBE 'DC' type 132 KV D/C towers up to +6 MBE 'DD' type 132 KV D/C towers & dead end up to +6 MBE 'DWF' type 132 KV D/C Dwarf towers up to +6 MBE |
| 437 | Soil resistivity test as per specification and direction of EIC |
| 438 | Design and Construction of tower foundations in all types of soil and conditions as per foundation drawings approved by the purchaser including excavation, concreting (M-20 grade), over lean concrete (M-10 grade of 50 mm minimum thickness), steel reinforcement, shoring, shuttering, dewatering, backfilling with carried earth (where necessary) and/or excavated good soil, disposal of surplus soil, forms, mixing, placing, finishing, protection and curing of concrete with all cost of supply of materials such as cement, sand, coarse aggregate, water, reinforcement, mild steel angle etc. with all cost of labour, materials, tools, plants, incidentals etc. complete in all respect as per specification and/or as directed by the employer. Rates shall be quoted in respective price schedule on per tower basis 'DA' type 132 KV D/C tower foundation upto +6 M extension Dry Type Wet Type Partially sub-merged type Fully sub-merged type 'DB' type 132 KV D/C tower foundation upto +6 M extension Dry Type Wet Type Partially sub-merged type Fully sub-merged type 'DC' type 132 KV D/C tower foundation upto +6 M extension Dry Type Wet Type Partially sub-merged type Fully sub-merged type 'DD' type 132 KV D/C tower foundation upto +6 M extension Dry Type Wet Type Partially sub-merged type Fully sub-merged type DWF' type 132 KV D/C Dwarf tower foundation upto +6 M extension Fully sub-merged type |
| 439 | Superstructure erection of standard normal tower including all work above ground level including tack welding excluding hoisting of insulator, fitting of danger, number & phase plates and anticlimbing devices etc. 132 KV D/C 'DA' type towers 132 KV D/C 'DB' type towers 132 KV D/C 'DC' type towers 132 KV D/C 'DD' type & dead end towers 132KV ' 'DWF' type Dwarf towers |
| 440 | Extensions only : +3 Metre Body Extension for 132 KV 'DA' type tower +6 Metre Body Extension for 132 KV 'DA' type tower +3 Metre Body Extension for 132 KV 'DB' type tower +6 Metre Body Extension for 132 KV 'DB' type tower +3 Metre Body Extension for 132 KV 'DC' type tower +6 Metre Body Extension for 132 KV 'DC' type tower +3 Metre Body Extension for 132 KV 'DD' type tower +6 Metre Body Extension for 132 KV 'DD' type tower +3 Metre Body Extension for 132 KV 'DWF' type tower |
| 441 | Laying, stringing, tensioning, clamping, jointing etc. complete of 6 nos. of ACSR PANTHER conductor including hoisting of insulators, armour rods, dampers and other accessories for complete route KM for double circuit line |
| 442 | Laying, stringing, tensioning, clamping, jointing etc. of one earthwire (48F-OPGW) including earth bonding with tower, fitting, fixing of all necessary accessories for complete route KM |
| 443 | Installation of approach cable (armoured) complete including ties, clips, cleats, conduits, ducts, supporting fittings etc. and other materials whichever and wherever required as per technical specificaiton |
| 444 | Installation of 96F FODP indoor type complete with all connections as per technical specificaiton and requirement |
| 445 | Fittings of tower accessories : Number plate Danger plate Phase plate (in set of three) Barbed wire type anticlimbing devices Grounding work for pipe earth including cost of coke, salt etc. including necessary excavation and backfilling complete |
| 446 | Erection of Special Tower / Tower structure (For power line x-ing, river x-ing, rail x-ing, N.H. x-ing, auxiliary x-arm, extended stub etc.all for non-scheduled tower/tower structure) Stub setting and footing work excluding the cost of excavation, concreting & back filling of Special Tower other than bored pile locations. Superstructure erection of Special Tower including tack welding |
| 447 | UNIT RATES : Concrete M-10 per cubic metre (CUM) including supply of cost of all materials complete, including dewatering Concrete M-20 per cubic metre (CUM) including dewatering, supply of all materials & shuttering but excluding reinforcement Supply, bending & binding of reinforcement rod including cost of binding material & labour complete |
| 448 | Earth Work : (Excavation including compacted back filling & required dewatering) Normal dry soil - Do - wet soil - Do - P.S. soil - Do - F.S. soil |
| 449 | Shoring of pits with shuttering, supply of materials & labour |
| 450 | Dewatering of Pits : Manual per man hour Mechanical pump (Rate to be quoted in H.P-Hr.) Cost of Building revetments with bricks, with 1 : 6 cement morter including 12 mm thick cement plaster (1:4) and neat cement punning on all exposed surfaces, excavation per cubic metre of brickwork including supply of materials and transport Back filling and levelling of the volume of earth enclosed by revetment walls. (Good earth arranged & supplied by the contractor) including supply of materials, transport etc. complete Back filling with medium coarse sand in foundation trench/pit as per specification and/or as per direction (per cum.) Cost of compaction of brick bats in foundation trench as per specification and/or as per direction (per cum.) of EIC including supply of all materials and transport complete |
| 451 | Soil testing as per relevant IS codes and direction of EIC Upto 10 M depth |
| 452 | Rivetment work by providing Sal-bullah / Eucalyptus bullah piles of diameter not less than 150mm, driving upto desired depth but not less than 4 m and spacing as per approved design and joining each bullah piles with the staging props by proper arrangement capable to transmit the loads from superstructure, including supply of pile, double coat coal tarring on wooden surface and all complete. Drum Sheet Walling to be provided of 1.40m (av.) high on Sal-bullah /Eucalyptus bullah piling 15 cm dia. and 3.25m long driven 1.75m (av.) below G.L. and 75cm centre to centre including fitting fixing 3 nos. of half bullah pieces (from 10 cm dia) and drum(empty bitumen) sheet (approved condition) of height 1.5m , cutting and straightening drum sheet (each joint must have lap length of min.50mm) including cost of necessary nails, bolts, nuts etc Note : 1. Diameter of bullah to be measured at 1.5 m from thicker end. Note : 2. Projected area of the deck on river bed should be considered for arriving at the cost. Rate to be quoted based on per meter length of pile |
| 453 | 2.0 PART - I |
| 454 | Standard Suspension 220 KV M/C 'T4' type towers (0o to 2o) Superstructure Stub - set of 4 upto 6 metre extension |
| 455 | Standard small angle 220 KV M/C 'ST4' type towers(0o to 15o) Superstructure Stub - set of 4 upto 6 metre extension |
| 456 | Standard medium angle 220 KV M/C 'MT4' type towers (15o to 30o) Superstructure Stub - set of 4 upto 6 metre extension |
| 457 | Standard large angle 220 KV M/C 'LT4' type towers (30o to 60o) & Dead end Superstructure (including modified tower for auxiliary cross arm, if any) Stub - set of 4 upto 6 metre extension Stub - set of 4 upto +12/+15/+18/+25 metre extension |
| 458 | Standard large angle 220 KV D/C 'DD' type towers (30o to 60o) & Dead end Superstructure Stub - set of 4 upto 6 metre extension |
| 459 | Extensions only +3 Metre Body Extension for 'DD' type tower. +6 Metre Body Extension for 'DD' type tower. +3 Metre Body Extension for 'T4' type tower. +6 Metre Body Extension for 'T4' type tower. +3 Metre Body Extension for 'ST4' type tower. +6 Metre Body Extension for 'ST4' type tower. +3 Metre Body Extension for 'MT4' type tower. +6 Metre Body Extension for 'MT4' type tower. +3 Metre Body Extension for 'LT4' type tower. +6 Metre Body Extension for 'LT4' type tower. +12 Metre Body Extension for 'LT4' type tower. +15 Metre Body Extension for 'LT4' type tower. +18 Metre Body Extension for 'LT4' type tower. |
| 460 | Number Plate |
| 461 | Danger Plate |
| 462 | Phase Plate (in sets of three Red, Yellow, Blue) |
| 463 | Complete pipe type grounding material for tower |
| 464 | Circuit plate |
| 465 | Barbed wire type anti-climbing device |
| 466 | Special Tower / Tower structure (For power line x-ing, river x-ing, rail x-ing, N.H. x-ing, auxiliary x-arm, extended stub, Composite towers etc.for all non-scheduled tower/tower structure). Stub ( per tonne rate to be quoted) Fabricated members (MS) Bolts & nuts Superstructure ( per tonne rate to be quoted) Fabricated members (MS) Bolts & nuts PART - II |
| 467 | SOLID CARBON COMPOSITE CORE HTLS CONDUCTOR EQUIVALENT TO ACSR ZEBRA, WITH MINIMUM CURRENT CARRYING CAPACITY OF 1200 AMP, AS PER TECHNICAL SPECIFICATION. |
| 468 | COMPOSITE FIBER OPTIC OVERHEAD EARTHWIRE (48F OPGW) STANDARD LENGTH (KM) AS PER TECHNICAL SPECIFICATION. |
| 469 | 24 FIBER OPTIC APPROACH CABLE (ARMOURED) INCLUDING ALL HARDWARES, TIES, CLIPS, CLEATS, CONDUITS, DUCTS, SUPPORTING FITTINGS ETC. AND OTHER MATERIALS WHICHEVER REQUIRED FOR COMPLETE INSTALLATION AS PER TECHNICAL SPECIFICATION AND REQUIREMENT. |
| 470 | SUPPLY OF 96F FIBER OPTIC DISTRIBUTION PANEL (FODP) (Dimension: 1400mm x 600mm x 600mm)SUITABLE FOR APPROACH CABLE INDOOR TYPE WITH FC-PC COUPLING AND PIGTAILS (DWSM FIBER) AS PER TECHNICAL SPECIFICATION (At both end) |
| 471 | 220 KV SUSPENSION INSULATOR STRING (70KN) -1x14Nos. PORCELENE DISC INSULATOR OR PORCELENE LONG ROD INSULATOR OR POLYMER LONG ROD INSULATOR |
| 472 | 220 KV TENSION INSULATOR STRING (120KN) - 1x15Nos. PORCELENE DISC INSULATOR OR PORCELENE LONG ROD INSULATOR OR POLYMER LONG ROD INSULATOR |
| 473 | CONDUCTOR ACCESSORIES :(Suitable for HTLS CONDUCTOR to be supplied) REPAIR SLEEVE (suitable for HTLS CONDUCTOR to be supplied) VIBRATION DAMPER (suitable for HTLS CONDUCTOR to be supplied - One set includes average quantity of Vibration Dampers required for one span OF MULTI CIRCUIT TOWER as per approved drawing, design & specification) VIBRATION DAMPER (suitable for HTLS CONDUCTOR to be supplied - One set includes average quantity of Vibration Dampers required for one span OF DOUBLE CIRCUIT TOWER as per approved drawing, design & specification) |
| 474 | 48F OPGW EARTHWIRE ACCESSORIES : VIBRATION DAMPER (One set includes average quantity of Vibration Dampers required for one span as per approved drawing, design & specification) SINGLE SUSPENSION CLAMP ASSEMBLY WITH EARTH BOND DOUBLE TENSION CLAMP ASSEMBLY (PASS THROUGH) WITH EARTH BOND SINGLE TENSION CLAMP ASSEMBLY WITH EARTH BOND DOWN LEAD CLAMP for OPGW (to be fixed at an interval of 1.5 mtr) OPGW HOLDER BRACKET JOINT BOX |
| 475 | INSULATOR HARDWARES FOR HTLS CONDUCTOR TO BE SUPPLIED SINGLE SUSPENSION INSULATOR HARDWARE FITTINGS COMPLETE (A. G. Type) DOUBLE SUSPENSION INSULATOR HARDWARE FITTINGS COMPLETE (A. G. Type) SINGLE TENSION INSULATOR HARDWARE FITTINGS COMPLETE DOUBLE TENSION INSULATOR HARDWARE FITTINGS COMPLETE PILOT INSULATOR HARDWARE FITTINGS COMPLETE |
| 476 | SOLID CARBON COMPOSITE CORE HTLS CONDUCTOR SUITABLE TO CARRY MINIMUM 1200 AMP CURRENT EQUIVALENT TO ACSR ZEBRA AS PER TECHNICAL SPECIFICATION (SPARE QUANTITY) |
| 477 | SPARE INSULATOR HARDWARES FOR HTLS CONDUCTOR TO BE SUPPLIED SINGLE SUSPENSION INSULATOR HARDWARE FITTINGS COMPLETE (A. G. Type) DOUBLE SUSPENSION INSULATOR HARDWARE FITTINGS COMPLETE (A. G. Type) SINGLE TENSION INSULATOR HARDWARE FITTINGS COMPLETE DOUBLE TENSION INSULATOR HARDWARE FITTINGS COMPLETE PILOT INSULATOR HARDWARE FITTINGS COMPLETE |
| 478 | 2.0 Detail Survey including route alignment preparation of profiles & Schedules of towers. Check survey and final peg marking. |
| 479 | Setting of stubs : 'T4' type towers up to +6 MBE 'ST4' type towers up to +6 MBE 'MT4' type towers up to +6 MBE 'LT4' type towers & dead end up to +6 MBE 'LT4' type towers & dead end up to +12/+15/+18/+25 MBE 'DD' type towers & dead end up to +6 MBE |
| 480 | Soil resistivity test as per specification and direction of EIC. |
| 481 | Design and Construction of tower foundation in all types of soil and conditions as per foundation drawing approved by the purchaser including excavation, concreting (M-20 grade) over lean concrete (M-10 grade, of 50 mm minimum thickness), steel reinforcement, shoring, shuttering, dewatering, backfilling with carried earth (where necessary) and/or excavated good soil, disposal of surplus soil, forms, mixing, placing, finishing, protection and curing of concrete with all cost of supply of materials such as cement, sand, coarse aggregate, water, reinforcement, mild steel angle etc., with all cost of labour, materials, tools, plants, incidentals etc. complete in all respect as per specification and/or as directed by the employer. Rates shall be quoted in respective price schedule on per tower basis. T4' type tower foundation upto +6 MBE Wet type Partially sub-merged type Fully sub-merged type ST4' type tower foundation upto +6 MBE Wet type Partially sub-merged type Fully sub-merged type MT4' type tower foundation upto +6 MBE Wet type Partially sub-merged type Fully sub-merged type LT4' type tower foundation upto +6 MBE Wet type Partially sub-merged type Fully sub-merged type LT4' type tower foundation upto +12/+15/+18/+25 MBE Fully sub-merged type DD' type tower foundation upto +6 MBE Fully sub-merged type |
| 482 | Superstructure erection of standard normal tower including all work above ground level including tack welding excluding hoisting of insulator, fitting of danger, number & phase plates and anticlimbing devices etc. 'T4' type towers 'ST4 type towers 'MT4' type towers 'LT4' type & dead end towers 'DD' type & dead end towers |
| 483 | Extensions only : +3 Metre Body Extension for 'DD' type tower. +6 Metre Body Extension for 'DD' type tower. +3 Metre Body Extension for 'T4' type tower. +6 Metre Body Extension for 'T4' type tower. +3 Metre Body Extension for 'ST4' type tower. +6 Metre Body Extension for 'ST4' type tower. +3 Metre Body Extension for 'MT4' type tower. +6 Metre Body Extension for 'MT4' type tower. +3 Metre Body Extension for 'LT4' type tower. +6 Metre Body Extension for 'LT4.' type tower. +12 Metre Body Extension for 'LT4' type tower. +15 Metre Body Extension for 'LT4 type tower. +18 Metre Body Extension for 'LT4' type tower. |
| 484 | Laying, stringing, tensioning, clamping, jointing etc. complete of 12nos. of HTLS CONDUCTOR to be supplied including hoisting of insulators, armour rods, dampers and other accessories for complete route Km for multi circuit. |
| 485 | Laying, stringing, tensioning, clamping, jointing etc. complete of 6nos. of HTLS CONDUCTOR to be supplied including hoisting of insulators, armour rods, dampers and other accessories for complete route Km for double circuit. |
| 486 | Laying, stringing, tensioning, clamping, jointing etc. of one earthwire (48F-OPGW) including earth bonding with tower, fitting, fixing of all necessary accessories for complete route Km. |
| 487 | Installation of approach cable (armoured) within substation premises complete including ties, clips, cleats, conduits, ducts, supporting fittings etc. and other materials whichever and wherever required as per technical specificaiton. |
| 488 | Installation of 96F FODP indoor type complete with all connections as per technical specificaiton and requirement. |
| 489 | Fittings of tower accessories Number plate Danger plate Phase Plate (in sets of three Red, Yellow, Blue) Grounding work for pipe earth including cost of coke, salt etc. including necessary excavation and backfilling complete. Circuit plate Barbed wire type anticlimbing devices |
| 490 | Erection of Special Tower / Tower structure (For power line x-ing, river x-ing, rail x-ing, N.H. x-ing, auxiliary x-arm, extended stub, Composite tower etc.for all non-scheduled tower/tower structure). Stub setting and footing work excluding the cost of excavation,concreting & back filling of Special Tower other than bored pile locations. Superstructure erection of Special Tower including tack welding. |
| 491 | UNIT RATES : Concrete M-10 per cubic metre (CUM) including supply of cost of all materials complete, including dewatering. Concrete M-20 per cubic metre (CUM) including dewatering, supply of all materials & shuttering but excluding reinforcement. Supply, bending & binding of reinforcement rod including cost of binding material & labour complete. |
| 492 | Earth Work : (Excavation including compacted back filling & required dewatering) Normal dry soil - Do - wet soil - Do - P.S. soil - Do - F.S. soil |
| 493 | Shoring of pits with shuttering, supply of materials & labour |
| 494 | Dewatering of pits Manual per man hour Mechanical pump (Rate to be quoted in H.P-Hr.) |
| 495 | Cost of Building revetments with bricks, with 1 : 6 cement morter including 12 mm thick cement plaster (1:4) and neat cement punning on all exposed surfaces, excavation per cubic metre of brickwork including supply of materials and transport. Back filling and levelling of the volume of earth enclosed by revetment walls. (Good earth arranged & supplied by the contractor) including supply of materials, transport etc. complete. Back filling with medium coarse sand in foundation trench/pit as per specification and/or as per direction (per cum.). Cost of compaction of brick bats in foundation trench as per specification and/or as per direction (per cum.) of EIC including supply of all materials and transport complete. |
| 496 | Soil testing as per relevant IS codes and direction of EIC Upto 10 M depth |
| 497 | Dismantle of 220KV D/C towers along with all accessories etc. including auxiliary X-arm and hand over the same to the WBSETCL'S store as per direction of EIC. (Rate to be quoted as per tower basis) |
| 498 | Dismantling and subsequent stringing of only 6 Nos. ACSR Panther conductor per route KM of existing D/C line as per direction of EIC. (Rate to be quoted as per route Km basis) |
| 499 | Revetment walling by providing Sal-bullah / Eucalyptus bullah piles of diameter not less than 150mm, driving upto desired depth but not less than 4 m and spacing as per approved design and joining each bullah piles with the staging props by proper arrangement capable to transmit the loads from superstructure, including supply of pile, double coat coal tarring on wooden surface and all complete. Drum Sheet Walling to be provided of 1.40m (av.) high on Sal-bullah /Eucalyptus bullah piling 15 cm dia. and 3.25m long driven 1.75m (av.) below G.L. and 75cm centre to centre including fitting fixing 3 nos. of half bullah pieces (from 10 cm dia) and drum(empty bitumen) sheet (approved condition) of height 1.5m , cutting and straightening drum sheet (each joint must have lap length of min.50mm) including cost of necessary nails, bolts, nuts etc Note : 1. Diameter of bullah to be measured at 1.5 m from thicker end. Note : 2. Projected area of the deck on river bed should be considered for arriving at the cost. Rate to be quoted based on per meter length of pile Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 30, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 28, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysOct 30, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender