Tender For Construction of Block Office Quarter Building At Dhar Ur Of Baddi Forest Range Of Nalagarh Forest Division Tehsil Baddi,Distt.Solan Hp .(Sh:Providing electrical installation Therein)

Issued by Government Departments · Shimla, Himachal Pradesh
Tender Value
2.15 Lakhs
Estimated cost
Bid Submission
05 Oct 2026
3 days left
EMD
4350
Bank guarantee accepted
Document Fee
350
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Shimla → Himachal Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Construction of Block Office Quarter Building At Dhar Ur Of Baddi Forest Range Of Nalagarh Forest Division Tehsil Baddi,Distt.Solan Hp .(Sh:Providing electrical installation Therein)

BOQ

Name of Work:- C/O Block office quarter building at Dhar ur of Baddi forest range of Nalagarh forest Division Tehsil Baddi,Distt.Solan HP .(SH:Providing E.I therein)
Sl. No. Item Description
1Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
2Group-B
3Group-C
4Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed PVC conduit as required.
52 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
62 X 4 sq. mm + 1 X 4 sq. mm earth wire
74 X 4 sq. mm + 2 X 4 sq. mm earth wire
82 X 10 sq. mm + 1 X 6 sq. mm earth wire
9Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
103x1.5 Sq. mm.
113x4.0 Sq. mm.
12Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.:-25 mm. dia
13Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
14Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
15Supply, Installation, Testing and Commissioning of following sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.85, Air delivery minimum 215 CMM, 300 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote/ BLDC electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
16Ceiling Fan 1200 mm sweep
17Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
18Installation of ventilatinmg /exhaust fan in the existing opening, including making good BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor the damage, connection, testing, commissioning etc. as required.Supply & Erection of Ventilating Fan ) following size complete with motor,, with minimum power consumption, rigid frame with rubber mounting for silent operation, in the existing opening including cost of making the hole to suit the size of above fan making good the damage, Carriage Charges connection, testing, commissioning etc. as required to complete the job to the entire satisfaction of EIC.
19S/E of LED Batten with polycarboante body and diffuser The fitting should be installed on existing surface/recess The job includes carriage, erection, making connections testing and commissioning of the fittings.Specification of LED fittings:
20Wattage of LED fittings-As per following parameter.
21Total lumens of the fittings.-as below
22Diffuser - Polycarbonate diffuser/PMMA
23Operating voltage =140 V to 270 V, AC supply or better.
24Input frequency =50 Hz + 1 Hz
25Power factor =Minimum 0.90
26Luminaire efficacy =>100 lm/w
27Color rendering index=CRI shall be greater than 80
28Working/ operating temperature =00 to + 450c or better
29Color temperature =60000K + 10%
30Electronic Driver
31Drive current (LED)=As per OEM.
32Operating voltage =140 V to 270 V, AC supply or better.
33Type of driver =Constant current output driver
34THD =Less than 10%
35Surge Protection =2.5 KV minimum
36Efficiency Driver=>85%
37Protection=Shall have under voltage and over voltage protection.
38Guarantee of LED fittings including LED driver =2 years against manufacturing defect.
39Fixture =Should comply with LM 79 test from UL/NABL lab.
40LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 25,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
41Life of LED=25000 burning hours at 70% lumen maintenance
42Lumen output of the fitting=>2000 Lumens
43S/E of LED bulk head IP 66 rated with aluminium body/PDC housing The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings.
44Wattage of LED fittings-As per following parameter.
45Total lumens of the fittings.-as below
46Diffuser - Polycarbonate diffuser/PMMA
47Operating voltage =140 V to 270 V, AC supply or better.
48Input frequency =50 Hz + 1 Hz
49Power factor =Minimum 0.90
50Luminaire efficacy =>80 lm/w
51Color rendering index=CRI shall be greater than 80
52Working/ operating temperature =0o to + 45oc or better
53Color temperature =60000K + 10%
54Electronic Driver
55Drive current (LED)=As per OEM.
56Operating voltage =140 V to 270 V, AC supply or better.
57Type of driver =Constant current output driver
58THD =Less than 10%
59Surge Protection =2 KV minimum
60Efficiency Driver=>85%
61Protection=Shall have under voltage and over voltage protection.
62Guarantee of LED fittings including LED driver =2 years against manufacturing defect.
63Fixture =Should comply with LM 79 test from UL/NABL lab.
64LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
65Life of LED=50000 burning hours at 70% lumen maintenance
66Lumen output of the fitting=>800 Lumens
67S/E of LED Downlighter surface square with CRCA/PDC body and diffuser The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings.
68Wattage of LED fittings-As per following parameter.
69Total lumens of the fittings.-as below
70Diffuser - Polycarbonate diffuser/PMMA
71Operating voltage =140 V to 270 V, AC supply or better.
72Input frequency =50 Hz + 1 Hz
73Power factor =Minimum 0.90
74Luminaire efficacy =>85 lm/w
75Color rendering index=CRI shall be greater than 80
76Working/ operating temperature =0 o to + 45 oc or better
77Color temperature =60000K + 10%
78Electronic Driver
79Drive current (LED)=As per OEM.
80Operating voltage =140 V to 270 V, AC supply or better.
81Type of driver =Constant current output driver
82THD =Less than 10%
83Surge Protection =2.5 KV minimum
84Efficiency Driver=>85%
85Protection=Shall have under voltage and over voltage protection.
86Guarantee of LED fittings including LED driver =2 years against manufacturing defect.
87Fixture =Should comply with LM 79 test from UL/NABL lab.
88LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
89Life of LED=50000 burning hours at 70% lumen maintenance
90Lumen output of the fitting=>1500 Lumens
91Lumen output of the fitting=>2000 Lumens
92Supplying and fixing call bell/ buzzer suitable for 230 v 50 hz complete as required
93Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
9412 way , Double door
95Supplying and fixing following rating, followings poles 10ka 240/415v 'C' curves miniature circuit braker suitable for inductive load of following poles in the exsisting MCB DB complete with connections, testing and commissioning etc. as required.
9663 A DP
97Supplying and fixing following rating, follwing pole, (single phase and neutral), 240/415 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
9863 A DP
99Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
100Single pole
101Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. (but without charcoal/ coke and salt ) as required.
102Supplying and laying 6 SWG G.I. wire at 0.50 Meter below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.
103Providing and installation of stationary storage type Electric water heater (Geyser) of various sizes with 8 bar pressure rating Five star BEE rating and safety valve installation by means of expansion-bolts with nuts and washers, including embedding of expansion-bolts in the wall, making good the damages, electrical connections, testing etc. complete as required:-
104Geyser 10 Ltr
105Geyser 25 Ltr Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57762424
AUTHORITY Government Departments
TENDER VALUE 2.15 Lakhs
LAST DATE 05-10-2026
Authority
Authority Name Public Works Department
Work Description Tender for Construction of Block Office Quarter Building At Dhar Ur Of Baddi Forest Range Of Nalagarh Forest Division Tehsil Baddi,Distt.Solan Hp .(Sh:Providing electrical installation Therein)
Basic Detail
Tender No Electrical Division-I dated 28.09.2026
Bidding Type Tender
Location
City Shimla
State Himachal Pradesh
Key Dates
Publish Date 28 Sep 2026
Submission Date 05 Oct 2026
Open Date 06 Oct 2026
Finance
Tender Value 2.15 Lakhs
Tender Fee 350
EMD 4350
Exemption Not Available
Document List
208d8d8c-d566-4720-9548-85f40d4d0088.html
BOQ_215074.xls
DeclarationNEW.pdf
SBD_13_Dharampur.pdf
Tendernotice_1 (22).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 28, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 05, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 3 days
Oct 06, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 4 days

Tender Documents