Tender for Supply Installation Testing and Commissioning of electrical installation And Civil Works In Command Centre In Conference Room At Bharat Mandapam, New Delhi.
BOQ
| Sl. No. | Item Description |
| 1 | Part A- CIVIL WORK |
| 2 | Masonary Works |
| 3 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V levelCement mortar 1:4 (1 cement :4 coarse sand) |
| 4 | Extra for providing and placing in position 2 Nos 6 mm dia. M.S. bars atevery third course of half brick masonry |
| 5 | CEMENT PLASTER (IN COARSE SAND) |
| 6 | 12 mm cement plaster of mix : 1:6 (1 cement: 6 coarse sand) |
| 7 | 15 mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1 cement: 6 coarse sand) |
| 8 | VITRIFIED TILES: Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily.the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete.Glazed Vitrified tiles Matt/Antiskid finish of sizeSize of Tile 600x600mm. |
| 9 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing of edges to give high gloss finish etc. complete at all levels.Granite stone slab of colour black, Cherry/Ruby redArea of slab over 0.50 sqm |
| 10 | False Ceiling Works |
| 11 | GYPSUM BOARD CEILING: Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed fromM.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediateG.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with12.5mm thick tapered edge gypsum plain board conforming to IS: 2095- (Part I) :2011 (Board with BIS certification marks) |
| 12 | Wall Finshes Work |
| 13 | Providing and fixing plywood 4 mm thick, one side decorative veneer conforming to IS: 1328 (type-1), for plain lining / cladding with necessary screws,including priming coat on unexposed surface with : Decorative veneer facings of approved manufacture |
| 14 | Wooden Door Frames: Providing and fixing plywood 4 mm thick, one side decorative veneer conforming to IS: 1328 (type-1), for plain lining / cladding with necessary screws,including priming coat on unexposed surface with : Decorative veneer facings of approved manufactureSecond Class Teak Wood |
| 15 | Wooden battens for extra support in partition and panelling where ever required.Kiln seasoned and chemically treated hollock wood |
| 16 | LAMINATE PANELLING: Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt/ suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approvedquality.1.0 mm thick1. The surface to be polished is rubbed with sand paper 80/120 no. and then with sand paper of 160/180 nos.2. Applying two coats of sealer with spray gun and allowing sufficient drying time for 1st coat and 2nd coat is allowed to dry for 8 to 12 hrs.3. On drying of sealer coat, wet rubbing with emery cloth of finer grading with ample water to remove excess sealer layer and make the surface further smooth after this wet rubbing, then surface is applied with special grade melamine fillers to fill all the small and big holes/grooves etc. Filler coat to be allowed to dry for 4 to 6 hrs on which again a light wet rubbing is done this surface is further allowed to dry for 12 hrs.4. On this, final finish with Duco paint of approved brand. |
| 17 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete |
| 18 | Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content. With water thinnablecement primer on wall surface having VOC content less than 50 grams/litre |
| 19 | Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre ofapproved brand and manufacture, including applying additional coats wherever required to achieve even shade and colourTwo Coats |
| 20 | STEEL STRUCTURE |
| 21 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 22 | With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/ steel works |
| 23 | With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/ steel works Two or more coats on new work |
| 24 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shadeTwo or more coats on new work |
| 25 | Disposal of building rubbish / malba / similar unserviceable, dismantledor waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved byEngineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved. |
| 26 | Providing and fixing removable raised/false access flooring with system and its components of approved make for different plenum height with possible height adjustment upto 50 mm, comprising of modular load bearing floor panels supported on G.I. rectangular stinger frame work and G.I. Pedestal etc. all complete, as per the architectural drawings, as specified and as directed by Engineer-in-charge consisting of: (a) Providing at required spacing to form modular framework, pedestals made out of GI tube of thickness minimum 2 mm and 25 mm outer diameter, fully welded on to the G.I. Base plate of size 100 mm x 100 mm x 3 mm at the bottom of the pedestal tube, G.I. pedestal head of size 75mmx75mmx3.5 mm welded with GI fully threaded stud 16 mm outer diameter with two GI Check nuts screwed on the stud for level adjustment upto 50mm, locking and stabilizing the pedestal head in position at the required level. The pedestals shall be fixed to the subfloor (base) through base plate using epoxy based adhesive of approved make or the machine screw with rawl plug. (b) Stringers system in all steel construction hot dipped galvanized of rectangular size 570x20x30x0.80 mm thick having holes at both ends for securing the stringers on to the pedestal head using fully threaded screws ensuring maximum lateral stability in all directions, the grid formed by the pedestal and stringer assembly shall receive the floor panel, this system shall provide adequate solid, rigid support for access floor panel, the system shall provide a minimum clear uninterrupted clearance between the bottom of the floor for electrical conduits and wiring etc. all complete as per the architectural drawings, as specified and as directed by the Engineer-in-charge (c) Providing and fixing Access Floor panel of 600x600x32 mm medium grade Filled Steel anti static high pressure Lamination of 800H grade (FS800H). Access Floor panel shall be steel welded construction with an enclosed bottom pan with uniform pattern of 64 hemispherical cones. The top and bottom plates of Steel Gauges: top 0.6 mm and bottom 0.7 mm fused spot welded together (minimum 64 welds in each dome and 20 welds along each flange). The panel should be Corroresist epoxy coated for lifetime rust protection and cavity formed by the top and bottom plate is filled with Pyrogrip noncombustible Portland cementitious core mixed with light weight foaming compound. The access floor shall be factory finished with Anti-static High Pressure laminate with Non Warp technology upto 1 mm thickness for superior adhesion and Surface flatness within 0.75mm. The panel is to withstand a Concentrated Load of 363 kgs applied on area 25 mm x 25 mm without collapse in the centre of the panel which is placed on four steel blocks. The panel will withstand and UniformlyDistributed Load (UDL) minimum 1250 kg/sqm and an impact load of 50kg all complete as per the approved manufacturers specification and as per the direction of Engineer-in-charge. All specification must be printed on the side of the panel to ensure the quality of the product. 300 mm Finished Floor Height (FFH) |
| 27 | Providing and fixing false ceiling at all heights with integral densified calcium silicate reinforced with fibre and natural filler false ceiling tiles of Size 595x595 mm of approved texture, design and patterns as per CPWD Specification 2019, to be laid in true horizontal level suspended on interlocking metal T-Grid of hot dipped galvanised iron section of 0.33 mm thick (galvanized @ 120 grams per sqm including both sides)comprising of main-T runners of size 24x38 mm of length 3000 mm,cross - T of size 24x32 mm of length 1200 mm and secondary intermediate cross-T of size 24x32 mm of length 600 mm to formgrid module of size 600 x 600 mm, suspended from ceiling using galvanised mild steel items (galvanizing @ 80 grams per sqm) i.e. 12x50 mm long dash fasteners, 6 mm dia fully threaded hanger rod upto 1000 mm length and L-shape level adjuster of size 76x25x25x1.6 mm fixed with grid and Z cleat of size 25x37x25x1.6 mm thick with precut hole on both 25 mm flange to pierce into 12x50 mm or even bigger size dash fastener if require, fixed with Glavanised iron perimeter wall angle or size 24x24x0.40 mm of length 3000 mm to be fixed on periphey wall / partition with the help of plastic rawl plugs at 450 mm center to center and 40 mm long dry wall S.S screws. The work shall be carried out as per specifications, drawing and as per directionsof theEngineer-in-Charge. With 15 mm thick tegular/butt edged without perforation plain/designer light weight calcium silicate Anti-Microbial Bio-Safe coated false ceiling tiles Confirming to JIS-Z2801 and ASTM G-21 |
| 28 | Floor Finishes Work |
| 29 | Providing and fixing SPC vinyl plank flooring, size approx. 1220 × 180 mm, 3 mm thick with 0.3 mm wear layer, click lock system, anti-skid, termite resistant and waterproof, over properly prepared surface including underlayer, cutting, matching pattern, edge trimming and finishing complete as per manufacturer specifications and direction of Engineer-in-Charge.Approved Makes: Responsive / Square Foot / Polyflor / Gerflor / Armstrong / Tarkett or equivalent |
| 30 | WPC louvers panelling 12mm thick over existing wooden panelling complete with corner profile and other fixing accessories. |
| 31 | FLUSH DOOR SHUTTERS: Providing and fixing on all height prefabricated factory made 40mm thick flush door shutter in existing door frame bounded with BWP type synthetic resin adhesive & wooden fillers as per IS 848 -1974 shutter should be confirm IS:2202 (part-1) non decorative type flush door of area up to 1.80 to 2.50 sqm and nothing shall be paid on account of size variation upto 5% plus mimus of make Greenlam, Duro, Century or Equivalent with both side 4mm thick decorative teak veneering of make sapele/white american oak/vintage teak including fixing on all edges 8mm thick second class teak wood margin/lipping with 8 mm thick clear vision/frosted glass fitted vertically in flush door shutter of make Saint Gobin, Modi Guard & Hindustan National Glass fixed all-round by 4mm thick second class teak wood margin/molding and size of cut in flush door shutter will be approx. 200x1800mm or as per approved drawing and one no. of door rubbershutter finished complete with PU polish all-round i/c SS butt hinges and SS screws all complete as per the direction of engineer-in-charge. (Note: this item is inclusive of all material, T&P and labour involved and the work shall be executed as per the approved drawing). |
| 32 | Providing and Fixing 450x15x15 mm ss 304 Tower bolt -Square Type with screw for Wooden Doors of approved make and model all complete as per the direction of Engineer-in-charge. |
| 33 | Providing and Fixing lock for double door in SS finish for wooden doors of approved make and model all complete as per the direction of Engineer-in-charge. |
| 34 | Providing and Fixing Concealed Door closer T660 -60 kg (CE certified) for wooden doors of approved make and model all complete as per the direction of Engineer-in-charge. |
| 35 | Providing and Fixing SS 304 Hinges Four Ball Bearing 100x75x3 mm (with screws) for wooden doors of approved make and model all complete as per the directionof Engineer-in-charge. |
| 36 | LACQUERED GLASS: Providing and fixing of 6mm thick annealed SGG Planilaque Evolution (premium GRIHA rated lacquered glass from Saint- Gobain) of approved color by Architect/ Client / Customer, fixed with SGG ULTRAFIX (compatible neutral core silicon/ double sided tape) on a perfectly leveled 12mm thick water proof marine plywood / MDF / Mineral fibre board which is mounted on the RCC wall/any other structure. Lacquered glass must be made industrially (via curtain coating process); opaque (if viewed against a support wall), coated with PU lacquer (50 micron thick); color consistency (measured by Minolta spectrophotometer CM5081); highly durable (passes PERSOZ hardness test for minimum 220 oscillatios); humid resistant (conforms to BS EN 1036 1999); environmentally friendly (no lead, no arsenic, no copper, noformaldehyde); appropriate recycled content (12% post industrial/ 6% post consumer); compressive strength (1000 MPa) & tensile strength (40 MPa), same as float glass; |
| 37 | Furniture Items |
| 38 | Supplying and placing custom made Control room consolesTable-top: - The material of the working surface shall be minimum 25 mm thick MDF with High Pressure laminate. The proposed console's material for tabletop core should be fire retardant, Insulated. The Laminate finish must be Water Proof, Scratch resistant, and high hardness.Slat Wall: - The floating slat wall shall be made up of powder coated perforated MS sheet.Slatwall design should have integrated space option of light integrationSide Legs: - The material of the side leg shall be minimum 25 mm thick MDF with High Pressure laminate.Cable Trays and Wiring: - The desks shall be designed with vertical and horizontal cable trays to allow for continuous cable management between the cabinets. Wire shall be routed into the cabinet through side leg. Proposed console shall be RoHS Certified/tested from UL/Intertek and the valid certificate/ test report shall be submitted along with technical bid.Under Structure: Made of heavy duty extruded vertical and horizontal metal profiles. The part shall be duly powder coated with 40+ microns over all surfaces. All sheet metal parts shall be finished with a durable, black, electrostatic powder coating.3 Seater |
| 39 | Supplying and placing Conference table with laminate finish top. The Table top shall be made of MDF with 1mm laminate overall thickness of the table top shall be 50mm. The understructure shall be made of 18mm laminated MDF board. Table shall have metal cable tray to carry wires. 3 Nos. flap box. Size: 6500 x 1500x 750mm |
| 40 | Supplying & Placing medium back chair with mesh back. The chair shall have synchro tilt mechanism. PU arms and PU base.Gas lift height adjustment facility. |
| 41 | Providing and fixing of Acoustic wall panel in command Room. The panel must have 12.5 mm gypsum core, with a geometric array of 12 mm square perforations. The reverse of the board incorporates an acoustic fleece which provides sound absorption performance. MDF Board Dimensions: 1200* 2400mm , Board Thickness : 12.5 mm , Board Weight: 8 kg approx., Perforation Size : 12*12 mm, Perforation Spacing: 25 mm CTC, Perforation Area : 16 %, Perforation set size : 487*487mm, Pain border Size : 56.5mm , Centre Plain Board: 113mm, Edge Type: All 4 Trapped edges, Colour: Unpainted paper line ( Can be painted with an emulsion after installation). These wall panellingincludes the fabric wall panels with premium Vaneer panels as per approved designed |
| 42 | Credit for unused/deducted aluminium section of size 75x50x3.5 mm including deduction of supply, handling, wastage and associated accessories complete as directed by Engineer-in-Charge.” (-ve) |
| 43 | Part B- Electrical Works |
| 44 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 45 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulate opper conductor, single core cable in surface/ recessed steel conduit as required |
| 46 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 47 | 2 X 4 sq.mm + 1 X 4 sq.mm earth wire |
| 48 | 4 X 4 sq.mm + 2 X 4 sq.mm earth wire |
| 49 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 50 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS/ HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group C |
| 51 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 52 | 20 mm |
| 53 | 25 mm |
| 54 | 32 mm |
| 55 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 56 | 20 mm |
| 57 | 25 mm |
| 58 | 32 mm |
| 59 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 60 | 5/6 A switch |
| 61 | 15/16 A switch |
| 62 | 3 pin 5/6 A socket outlet |
| 63 | 6 pin 15/16 A socket outlet |
| 64 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 65 | 3 Module (100mmX75mm) |
| 66 | 6 Module (200mmX75mm) |
| 67 | 8 Module (125mmX125mm) |
| 68 | 12 Module (200mmX150mm) |
| 69 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 Amodular socket outlet and 15/16 A modular switch,connections etc. as required. |
| 70 | Supplying and fixing 5 amps to 32 amps rating, 240/415volts, 'C' curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 71 | Single Pole |
| 72 | Double Pole |
| 73 | Triple Pole |
| 74 | Triple Pole and Neutral |
| 75 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 76 | Supplying and fixing following rating, Four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc., as required |
| 77 | 100 A |
| 78 | Supply and fixing of following rating, four pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB), having a sensitive current 30 mA in the existing MCB DB Complete with connections, testing and commissioing etc as required. |
| 79 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, onsurface or in recess, with chained metal cover for the socket outlet and complete with connections, testing and commissioning etc. as required. |
| 80 | Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 20 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 81 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A \\"C\\" curve, TPMCB, in sheet steel enclosure, onsurface or in recess, with chained metal cover for the socket outlet and complete with connections, testing and commissioning etc. as required. |
| 82 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enamelled white on both sides, and with inscription in single red colour on front side as required. |
| 83 | Supplying Installation, Testing and Commissioning of following capacity TPN tap off box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing rising mains complete with TPN disconnector FSU and HRC fuses, connections, earthing etc. as required. |
| 84 | 400 A TPN |
| 85 | LED Down lighter (COB Type) (System lumen efficacy ≥120 lm/Watt )Supplying, Installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round / square/ Rectangular) COB Type of following bodymaterial and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with, 70%of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation ColourMatching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard.Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. \\"complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80Test report and all testing required for LED fixtures as per BIS shall be submitted Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body including trim with Aluminium Reflector |
| 86 | 18 watt |
| 87 | 22 watt |
| 88 | LED Panel light 2x2 ft., (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internalsurge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends ,CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminiumBody (Thickness > 1.20 mm) |
| 89 | 36 watt |
| 90 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray ( Galvanisation thikness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connections, suspennded from the ceiling ith G.I. suspenders including G.I. bolts and nuts etc, as required. |
| 91 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 92 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/submain wiring/ cable as required. |
| 93 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required |
| 94 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 95 | 3½ X 70 sq. mm (38mm) |
| 96 | 3½ X 95 sq. mm (45mm) |
| 97 | 3½ X 120 sq. mm (45mm) |
| 98 | Supplying one number 70 Sqmm, 3.5 Core PVC sheathed, XLPE insulated, Aluminium counductor armoured power cable of 1.1 kV, Grade, on surface/recess, existing cable trays, etc as required. |
| 99 | Supplying of one number 95 Sqmm, 3.5 Core PVC sheathed, XLPE insulated, Aluminium counductor armoured power cable of 1.1 kV, Grade, on surface/recess, existing cable trays, as required. |
| 100 | Supplying of one number 120 Sqmm, 3.5 Core PVC sheathed, XLPE insulated, Aluminium counductor armoured power cable of 1.1 kV, Grade, on surface/recess, existing cable trays, as required. |
| 101 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 102 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 103 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
| 104 | Online UPS- Input supply: Three Phase, Output supply: Three Phase. Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) at operating temperature 0 to 40 0C, Relative humidity 0 to 95%, Online double conversion true sine wave Uninterrupted hot swapable (allow for the replacement or addition of battery modules without shutting down the entire system) modular Power Supply (UPS) system with N+1 modules (N denotes total number of modules required for rated capacity). The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. UPS shall have inbuilt phase sequence correction. The UPS systems offered are to be of the latest technology with Digital Control Microprocessor based for reliable operation using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter (3 Level) with PWM (Pulse Width Modulation). The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >96% while operating on battery mode and delivering quality power to the 100% non-linear loads. Current total harmonic effect(ITHD) on the input grid shall be < 5% at 50 %load. (The required LC ( inductor (L) and a capacitor (C)) filters shall be included in UPS cost), extreme power factor kit to be included to limit the input power factor (PF) to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ), however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC : 3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage: 3Phase 415 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins, Sine wave output. Non condensing, noise level less than 60db at 1 meter distance, protections: Input Under voltage over voltage, abnormal out voltage, battery over charging, output over current, short circuit protection, battery deep discharge protection, 10KV surge. UPS must comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI)-type UPS. . Communication RS232/RS485/SNMP port open protocol for BMS integration, all hardware & software for iOT Communication as per approved by Engineering in charge. Required battery racks and interconnecting copper conductor cables of suitable size and connectors and all required accessories are inclusive of the cost). This system must provide a means for logging and alarming of all monitored points plus email notification. Forced air-cooling with integral inbuilt fans with redundancy (if one fan fail UPS should be able to handle at least 80% of the load, Noise Level 65 DB at 1 meter distance. The system shall be in compliance IEC 62040- 1,2 & 3, IS: 16242 and CPWD Specification. Display Panel (minimum) (In-build 5 inch or more LC Display / LED) to display : a) Input: Voltage, current, Frequency. b) Bypass: Voltage, Frequency. c) Output: Voltage, frequency, Current. d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage. f) Temperature: STS, Inverter, PFC. g) Event Logging & Statistical Data (On LCD/LED): UPS should capture and display up to 3000 events like: Over temperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-circuit / Device Fail / Inverter Fail / Rectifier Fail / Bypass Fail, etc. h) Statistical Data: No. of power failures / Transfers to Bypass / Total Running time, etc. i) Mains Mode of Operation /Battery Mode of Operation / Bypass feeding the load / UPS Fault /Battery charging and discharging, overload, battery voltage and battery capacity. j) Audible Alarms : Mains Failure, Battery Low Alarm, UPS Overload, Fault, Shutdown, Input Over, Under Voltage, Output Over, Under Voltage, Battery Over, Under Voltage, Over Load and short circuit, Over Temperature. The UPS should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc. |
| 105 | 30KVA (Each Power module shall be < 10 KVA) |
| 106 | UPS INPUT PANEL TTA PANELSupply, erection, testing and commissioning of 415V, 3 phase 4 wire 50 c/s UPS INPUT PANEL fully compartmentalized cubical type, as per the standards IEC61439-1&2 as tested assembly (PTTA) ,tested for impulse voltage 12 KV,IP 42 fabricated CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland plates i/c cleaning & finishing complete with 9 tank process for powder coating in approved shade, having required capacity extensible type FP bus bars of high conductivity, DMC / SMC bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 35KA for 1 Sec., bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, Form of separation shall be form 4b with metallic separation only entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of bus bars, interconnection etc. with indication lamps, push buttons necessary accessories, complete with following incoming and outgoing switchgears with protection and metering etc. as per specification and schematic diagram complete as required, with incoming & outgoing cable entry from bottom/top , wiring with 2.5sq. mm. FRLSH insulated copper conductor , cable alleys, PLC cable gland i/c providing following switch gears Supply, Installation, testing & commissioning of Inert type Novec-1230/FM200 or equivalent Fire Detection Tube based Gas suppression system for electrical panel. It includes all the require accessories/equipments to complete the panel protection, as per detail specification.All MCCBs shall be rating for 25kA (Ics=Icu). All MCCBs above 63A should be provided with Copper Spreader TerminalsMarshalling Bay To Be Provided for BMS OperationApproval shall be taken for each panel before fabrication. Incomer250A FP MCCB 25kA) with microprocessor based O/L, S/C,Instantaneous,E/F - 1 Nos. All incoming breaker should be communicable for status moniroting & Controlling through Modbus over TCP/IP RYB on, off trip indication lamp - 1 set.SPD type II, min. 25KA, FP - 2 nos. Multi Function Meter with CT RS 485 port.- 2 nos.C.T. 250A/5A, CLASS 1.0, 5VA- 6 nos. , Copper bus bar suitable for UPS Incomer Panel as per CPWD Publications.Outgoing:A. 100A MCCB (25kA) microprocessor based with O/L,S/C & inbuilt E/F Protection. - 4 nos.B. on, off trip indication lamp. - 4 set. With required accessaries as per CPWD Spefication. |
| 107 | UPS OUTPUT PANEL TTA PANELSupply, erection, testing and commissioning of 415V, 3 phase 4 wire 50 c/s UPS INPUT PANEL fully compartmentalized cubical type, as per the standards IEC61439-1&2 as tested assembly (PTTA) ,tested for impulse voltage 12 KV,IP 42 fabricated CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland plates i/c cleaning & finishing complete with 9 tank process for powder coating in approved shade, having required capacity extensible type FP bus bars of high conductivity, DMC / SMC bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 35 KA for 1 Sec., bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, Form of separation shall be form 4b with metallic separation only entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of bus bars, interconnection, interlocking between feeders etc.with indication lamps, push buttons necessary accessories, complete with following incoming and outgoing switchgears with protection and metering etc. as per specification and schematic diagram complete as required, with incoming & outgoing cable entry from bottom/top , wiring with 2.5sq. mm. FRLSH insulated copper conductor , cable alleys, PLC cable gland i/c providing following switch gears Supply, Installation, testing & commissioning of Inert type Novec-1230/FM200 or equivalent Fire Detection Tube based Gas suppression system for electrical panel. It includes all the require accessories/equipmentsto complete the panel protection, as per detail specification.All MCCBs shall be rating for 25kA (Ics=Icu). All MCCBs above 63A should be provided with Copper Spreader TerminalsMarshalling Bay To Be Provided for BMS OperationApproval shall be taken for each panel before fabrication. Incomer100A FP MCCB 25kA) with microprocessor based O/L, S/C, Instantaneous, E/F - 1 Nos.All incoming breaker should be communicable for status moniroting & Controlling through Modbus over TCP/IP RYB on, off trip indication lamp - 1 set. SPD type II, min. 25KA, FP - 2 nos. Multi Function Meter with CT RS 485 port.- 2 nos. C.T. 250A/5A, CLASS 1.0, 5VA- 6 nos., Copper bus bar suitable for UPS Incomer Panel as per CPWD Publications. Outgoing: A. 63A MCCB (25kA) microprocessor based with O/L,S/C & inbuilt E/F Protection. - 5 nos. B. on, off trip indication lamp. - 5 set. With required accessaries as per CPWD Spefication. |
| 108 | Part C- Fire Fighting and Fire Control System |
| 109 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 110 | 25 mm dia |
| 111 | 32mm dia |
| 112 | 150 mm dia |
| 113 | Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required. |
| 114 | Supplying, installation, testing & commsioning of response indicator on surface/recess MS box having two LEDs mettalic cover complete with all connections etc.as required. |
| 115 | Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required. |
| 116 | Supplying and fixing of metal flexible hose for sprinklers of size 1.8/2.0 mtrs length which provides a unique sprinklers drop assembly comprised of the following components: stainless steel flexible hose with two slip nuts, Branchline inlet , nipple, Straight sprinklers reducer bracket, bar fixing clamps and support bar etc as required. (Note: It should be UL listed and FM approved) |
| 117 | Supplying, installation, testing & commissioning of main control and indicating panel made out of 16 SWG MS sheet to accommodate the following items duly powder coated in approved colour with louvers for ventilation, locking arrangement, audio and visual indication for fire alarm and public address system, monitoring system including connections, interconnections etc complete as required. 6 zone panel for fire alarm system 100 watt amplifier racks suitable for operation on 230VAC/24V DC supply conforming to IEC-268-3 complete with all Talk back master station with LED PTT (press to talk) push button for operation on 230V AC/24 V DC supply conforming to IEC-268 for simplex mode of Operation/communication suitable for 20 Nos.talk back unit -1 set. Annoucement control desk suitable for selection of different zones selectively and ON ALL CALL switch with visual indication etc., complete as required- 1 set. Amplifier change over switch for inter changing amplifier- 1 No.Monitor panel for loudspeaker complete output selector ON/OFF switch, fuse visual indications etc. complete as required- 1 No. Gooseneck microphone with stand and ON/OFF switch -1 No.Mains ON/OFF switch, fuse indication lamps, DC and AC voltmeters & ammeters terminal blocks etc. complete as required -1 set. Battery charger trickle cum boost to take complete load of fire alarm & PA system complete with all accessories including providing & fixing of 2 nos. 12 volt,30 AH each sealed maintenance free batteries -1 set. |
| 118 | Supplying, installation, testing & commisoning fire alarm sounder with facility to make announcement, mounted in A.B.S. box with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required |
| 119 | SITC of Addressable Control relay module |
| 120 | Part- D (Air Conditioning System) |
| 121 | Supplying, Installation, Testing and commissioning of factory built floor mounted chilled water double skin type horizontal/vertical air handling units in confirmation to IS 18794 : 2024 made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 6 row deep, filter section with 50mm thick metal viscous/ washable synthetic type air prefilters, belt drive package with TEFC drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably designed for varialbe frequency drive applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.)and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities. (Total static pressure considered is max. 50 mm wg). (Note: AHU must have mixing chamber for fresh air, Supply air and return air; AHUs should also certified for mechanical and thermal performance as per EN 1886 standard & Eurovent Certified coils must be AHRI Certified). |
| 122 | 28900 CMH |
| 123 | Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping plumbing inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with fire retardant quality expanded polystrene moulded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date ) at joints repairing of damage to building etc. as per specifications and as required complete in all respect.Note:-The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy classas per IS: 3589, from minimum 6.35mm thick M.S.Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. |
| 124 | 80mm dia. (50mm thick insulation) |
| 125 | 65mm dia.(50mm thick insulation) |
| 126 | 32 mm dia (50mm thick insulation) |
| 127 | INSULATED VALVESSupplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. |
| 128 | Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation as specified |
| 129 | 80 mm dia. |
| 130 | 65 mm dia. |
| 131 | Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified. |
| 132 | 80 mm dia. |
| 133 | Providing and fixing in position industrial type pressure gauges with gun metal / brass valves complete etc. as required. |
| 134 | Providing & fixing in position industrial type mercury thermometers complete etc. as required. |
| 135 | Supplying, Installation, Testing and Commissioning of following sizes electronic, self-balancing, pressure independent type dynamic balancing valve with integrated 2 way modulating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar minimum. |
| 136 | 80 mm dia. |
| 137 | Supplying, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/ round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, bends, transitions, reducers, end caps, collars etc as required complete in all respect in confirmation with IS : 655 and approved drawings and specifications of following sheet thickness complete as required. |
| 138 | Thickness 0.80 mm sheet |
| 139 | Thickness 1.00 mm sheet |
| 140 | Supplying and fixing of 25mm thickness duly laminated aluminium foil of mat finish closed cell Nitrile rubber (Class \\"O\\") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. |
| 141 | Supplying, Fixing, installation, testing and commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core in confirmation to SMACNA/IS and as per specifications complete etc. as required. |
| 142 | Supplying, Fixing, installation, testing and commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core in confirmation to SMACNA/IS and as per specifications complete etc. as required. |
| 143 | Supplying, Fixing, installation, testing and commissioning of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers in confirmation to SMACNA/IS and as per specifications complete etc. as required. |
| 144 | Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete in confirmation to SMACNA/IS and as per specifications complete etc. as required. |
| 145 | Supplying, Fixing, testing and commissioning of fire dampers of minimum 90 minutes fire rated in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal and, in confirmation to IS and as per specifications complete etc. as required. |
| 146 | Fire damper |
| 147 | Actuator |
| 148 | Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with 50mm thick, density 32 kg/cu.m resin bonded glass fiber insulation friction fixed in 610mm x 610 mm frame work made of 25X50X50X50X25 mm made out of 0.6mm thick GI sheet U shaped channel and covered with reinforced fiber glass tissue and finished with 0.80 mm perforated aluminium sheet etc. complete as required and as per specifications. |
| 149 | SITC of 32 mm Gun Metal Gate Valve/ Pressure Release valve including flanges, nut-bolts, and other accesorries etc complete as required. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 28, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 08, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 7 daysOct 09, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender