Tender For Repair, Replacement Of Ht Poles, Acsr Conductors, Ht Oh Lines & Ug Cables, Transformers, God, Vcb, Acb And Other Allied E/M Works At Chh Sambhajinagar Mil Station Under Ge(S) Ahilyanagar
Tender Value
27.55 Lakhs
Estimated cost
Bid Submission
19 Oct 2026
15 days left
EMD
56000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Ahmednagar → Maharashtra
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair, Replacement Of Ht Poles, Acsr Conductors, Ht Oh Lines & Ug Cables, Transformers, God, Vcb, Acb And Other Allied E/M Works At Chh Sambhajinagar Mil Station Under Ge(S) Ahilyanagar
BOQ
| Sl. No. | Item Description |
| 1 | Earth work in excavation by mechanical means (Hydraulic excavator) in foundation trenches or drains or laying of pipe or for shafts, wells cesspits, man holes etc (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m all as specified and directed. |
| 2 | All as per item No 01 above but in hard soil or bituminous road / hard standing all as specified and directed. |
| 3 | All as per item No 01 above but more than 1.5 Mtr and upto 2 Mtr all as specified and directed. |
| 4 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed by the Engineer - in - Charge. |
| 5 | Supply and lay HDPE PIPE (PE 100,SDR-21,6 Kgf/Cm^2) IS 4984-2016) 110 mm dia for laying of HT cables etc complete with all accessories all as specified and directed. |
| 6 | Supply and laying in replacement HT XLPE Insulated, Screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables Heavy duty with aluminium conductor, 11000 Volts (Earthed) grade laid in trenches, ducts, along pole, along Transformer cross sectional area 185 Sqmm 3 Core complete all as specified and directed by Engr in charge. |
| 7 | All as per item no 06 above but here in before 120 Sqmm 3 core all as specified and directed. |
| 8 | Dismantling of ACSR or AAC conductors/Guard wire of any size and any description from any height/ poles or any location, complete all as specified and as directed. |
| 9 | Dismantling and taking down cross-arms of M.S. channel or angle sections with nuts, bolts, washers etc complete all as specified and directd by Engr in Charge. |
| 10 | Dismantling of Unserviceable HT insulators Pin/ shackle/ Disc & loop type from existing OH lines complete all as specified and directed by Engr in Charge. |
| 11 | M & L for HT Cable end termination box suitable for 11000 Volts grade 185 Sqmm 3 Core XLPE 11KV cable, outdoor, heat shrinkable type with all accessories complete all as specified and directed. |
| 12 | M & L for HT Cable end termination box suitable for 11000 Volts grade 120 Sqmm 3 Core XLPE 11KV cable, outdoor, heat shrinkable type with all accessories complete all as specified and directed. |
| 13 | M & L for HT Straight through heat shrink type joint for 11000 Volts grade 185 Sqmm 3 Core XLPE 11KV cable, heat shrinkable type with all accessories complete all as specified and directed. |
| 14 | M & L for HT Straight through heat shrink type joint for 11000 Volts grade 120 Sqmm 3 Core XLPE 11KV cable, heat shrinkable type with all accessories complete all as specified and directed. |
| 15 | Supply and fix in replacement 100 mm bore GI pipe light grade for cable protection, ISI marked with all fixing accessories such as clamps of suitable size/length, Nut bolts and washers and fixed complete to walls and ceilings or laid in floors complete including taking down old unserviceable pipe any type complete all as specifed and as directed. |
| 16 | Supply and fixing in replacement lightning arresters expulsion type suitable for 11 KV complete with all fittings, transmission class, discharge capacity 65 KA complete all as specified and directed by Engr in Charge. |
| 17 | Supply & Fixing in replacement GI strip of size 32 x 6 mm buried in ground or fixed to pole, wall including fixing clamp made out of 40x5 mm MSFI nut, bolt and washers complete including taking out old GI strip all as specified and directed by Engr -in -Charge. |
| 18 | S & F in replacement Air termination, single pointed copper rod 12mm dia and 300mm long in building top of any height with all scaffolding and ladder arrangements all as specified & directed by Engr-in-charge. |
| 19 | S & F in replacement Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos, 8mm dia 25mm long hex head screw all as specified & directed by Engr-in-charge. |
| 20 | S & F in replacement Aluminium strip 25 x 3 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground all as specified & directed by Engr-in-charge. |
| 21 | Supply and fix cross arms. Bracings, support channel, back plate hooks etc fabricated from structural steel sections (MS Channel) of required size and shape including nuts, bolts,washers, welding, bending , cutting cold or hot, drilling holes for inserting bolts as indicated and directed including painting with one coat of red oxide primer and two coats of silver aluminium paint complete all as specified and directed by Engr-in-Charge. |
| 22 | S&F in replacement of 33 KV grade pin type insulator of suitable size complete and including spindle, washers etc all as specified and directed by Engr in Charge. |
| 23 | M&L Disc type insulators, porcelain, vitreous 145 mm high and 255 mm dia ball and socket type, white, brown or green single disc assembly suitable for 11000 volt grade supply all as specified and directed. |
| 24 | Supply and fixing 11 KV grade pin type insulator of 150 mm height, 150 mm dia complete including spindle, washers and etc all as specified. |
| 25 | Supply and fix in replacement danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with screws, nut bolts with adequate size clamps on HT pole of 25x20 cm size all as directed by Engr-in-charge. |
| 26 | M & L for Preparing surfaces of HT pole by scrapping old paints and applying one coat red oxide primer and two coats of aluminium paint and writing \\"HT\\" and Pole No in black paint etc complete all as specified and directed by Engr- in -Charge. |
| 27 | M & L for Preparing surfaces of two pole structure including cross arms, channels, clamps etc by scrapping old paints and applying one coat red oxide primer and two coats of aluminium paint and writing \\"HT\\" and Pole No in black paint etc complete all as specified and directed by Engr- in -Charge. |
| 28 | M & L for Preparing surfaces of four pole structure including cross arms, channels, clamps etc by scrapping old paints and applying one coat red oxide primer and two coats of aluminium paint and writing \\"HT\\" and Pole No in black paint etc complete all as specified and directed by Engr- in -Charge. |
| 29 | M & L for replacement of jump connection of two/four pole structure by using ACSR conductor weasel, alkathine pipe, aluminium lugs, nuts, bolts etc. all as directed by Engineer-in-charge.Note : Rates includes Conductor, Pipes, Lugs, Nut bolts etc. |
| 30 | M & L for dismantling air break GOD set vertical/horizonatal mounted, including insulators and operating mechanism for repair/replacement of broken/worn out components and insulators etc by replacing stationary and moving contacts adjusting from ground level for smooth operation by replacing flexible copper strip, insulators, nuts, bolts, washer, GI pipe handle etc, all as directed by Engineer-in-charge. |
| 31 | Supply and fixing in replacement of GOD handle with locking strip and insulation sleeve complete all as specified and directed by Engr-in-Charge. |
| 32 | Supply and fixing in replacement of GI pipe 25 mm dia \\"medium grade\\" 6 metre in length complete all as specified and directed by Engr-in-Charge. |
| 33 | Lobour only for cleaning of bushes, small plants up to root level around and surrounding area E/M installations (i.e two pole / four pole structures, out door substation yards, pump house & misc E/M installations etc) including surface dressing n.exc 15 cm deep and removing debris to distance n.exc 50m complete all as specified and directed by Engr-in-charge.Note : The work shall be executed at an intervel of quarterly/as directed by Engr-in-charge as per site requirment. |
| 34 | Supply, fixing, testing and commissioning in replacement of air break gang operated device, triple pole mechanically operated outdoor type, mounted on and including 11 KV H.T. porcelain insulators and steel channel frame, GI operating rod, 25mm dia of suitable length with operating mechanism working from ground level, vertically operated including locking arrangement for operating handle, suitable for current rating upto 200 Amp, 11000 Volts working pressure all as specified and directed by Engr-in -Charge. |
| 35 | Supply and fix in replacement of dropout fuse unit explusion type for outdoor air break swirch (GOD) single pole, mounted on and including insulators for 11000 Volts working pressure fixed to and including MS channel with nuts, bolts, washers etc. synthetic bounded fuse carrying tube complete with line tabs and suitable for current carrying capacity upto 200 Amps only all as specified and directed. |
| 36 | Material and labour for stone aggregate 40mm graded spreading and leveling around 2 pole/ 4 pole structure where GOD installed and substation Area including well ramming with two layers of 50 mm thickness complete taking out old unserviceable aggregate stone of any size all as specified and directed by Engr-in-Charge. |
| 37 | M & L in replacement Earthing complete with galvanized steel earth plate electrode 60 cm X 60 cm X 6.0 mm thick buried directly in ground in any type of strata (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level connecting to the GI strip 32 x 6mm, by means nut bolt, nuts, check nuts and washer of the GI Earth wire protected by provision of GI light grade pipe 40 mm incl provision of concrete pit in PCC (1:2:4) type B-1 using 20 mm graded stone aggregated with 40 mm thick cover with RCC (1:2:4) reinforced with XPM (weight not less than 4 Kg / Sqm) and frame of angle iron 25mm X 25 mm X 3mm with lugs 2 Nos and with 6 mm dia MS bar handle made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, taste point made out of phosphorus bronze with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding than 50 mtr, all as per electric plate No 3 of SSR Part I 2020 and connection to earth test point all as specified incl testing on completion”.Note : The unit Rate includes earth strip and protection pipe up to (max 7.5 metre) from earth plate/earth point/test point. |
| 38 | Labour only for restringing/restretching of HT OH line by replacing pin binding with new aluminium conductor and maintaining sag within permissible limit for 3 runs of ACSR conductor all as specified and directed.Notes :(i) Span from one pole to next pole (30 to 50 RM) will be considered as a one Job(ii) Any damage cause due to contractormen will be rectified without any extra payment. |
| 39 | Lobour only for trimming of tree branches touching to the HT/LT over head line or near to the HT/LT over head line as per the direction of AGE E/M/ JE incharge complete including removing the tree branches all as specified and directed.Notes :(i) Span from one pole to next pole (30 to 50 RM) will be considered as a one Span.(ii) Any damage cause due to contractormen will be rectified without any extra payment(iii) T & P such as ladder, rope, cutter, Axes and other related material will be provided by the contractor. |
| 40 | Material and labour required for locating fault on high voltage power cables up to 11 kv complete by using fault detector machine including transportation, materials and all accessories,Tools and by carring out high pressure test all as directed by Engr-in-charge. (Note:Excavation ,earth work and materials (cable, joint kits) required for faults clearing shell be measured and paid separetely under relevant items) |
| 41 | Material and Labour for dehydration, filtration and cleaning of transformer oil, both indoor/outdoor/ pole mounted/plinth mounted HT switch gear etc at different locations by suitable dehgydration plant testing of oil sample before and after dehydration for each transformer/equipment and results of transformer oil dielectric strength minimum upto 42 KV , recorded jointly by contractor and Engineer-in-Charge complete including all necessary tools, plants, transportation etc all as specified/directed by Engineer-in-Charge.Note : Oil for topping up/fresh fill shall be measured and paid seperately under relevant item. |
| 42 | Supply & filling of transformer oil in transformer in situ/ at site for topping up the level of oil having dielectric strength 40-60 KV during filling after initial filtration conforming to IS-335 (Transformer oil shall be supplied in sealed container and empty barrel of transformer oil will be deposited by contractor in E/M store yard) |
| 43 | M&L for painting the panel Boards, Transformer fencing, Gates, Transformer Name plate boards by spray painting with applying two coats of synthetic enamel paint including prepartion of surface by scrapping old paint and writing SM No, MES No, and capacity of transformer on boards with white paint all as specified and directed by Engineer-in-Charge |
| 44 | M&L for repair to transformer pole mounted/plinth mounted of any capacity to stop the leakage of transformer by lifiting core assembley with the help of chain pully block/crane, removing transformer oil, replacing cork sheet gasket 5mm thick, reassembling the transformer completely, refilling transformer oil, connecting HT/LT connection and required for replacement of unserviceable nuts/bolts/washer all as directed by Engineer-in-charge (Note : Spares required shall be measured and paid separately ) |
| 45 | M&L for replacement of breather assembley with silica gel. |
| 46 | Supply only HT porcelain bushing complete with brass/ tinned copper rod with nuts and gasket set complete for following cap transformer :- (a) 63 KVA to 100 KVA capacity |
| 47 | Supply only HT porcelain bushing complete with brass/ tinned copper rod with nuts and gasket set complete for following cap transformer :- (b) 160 KVA to 250 KVA capacity |
| 48 | Supply only HT porcelain bushing complete with brass/ tinned copper rod with nuts and gasket set complete for following cap transformer :- (c) 315 KVA to 400 KVA capacity |
| 49 | Supply & fix in replacement of tap changer switch 11 KV complete with rod and gasket for following cap transformer :- (a) 160 KVA to 250 KVA capacity |
| 50 | Supply & fix in replacement of tap changer switch 11 KV complete with rod and gasket for following cap transformer :- (b) 315 KVA to 400 KVA capacity |
| 51 | S & F in replacement of HV rod brass, 12mm dia with brass nut 2 Nos and rubber bush 300mm long all as directed by Engineer-in-Charge. |
| 52 | S & F in replacement of LV rod brass 15mm/20mm dia, 300mm long with rubber bushing and brass nuts 2 Nos all as directed by Engineer-in-Charge. |
| 53 | M&L for disconnecting of defective transformer (indoor/outdoor type) of capacity 100 to 400 KVA, 11 KV/433 volts copper/ wound from power mains and dismantling the same from 2/4 pole structure/ platform mounted and transporting the same to authorised workshop and opening the transformer cover, draining out of tranformer oil and keep safely for reuse after filtration, assembling, removing of the burnt parts i.e tape, paper insulating strings etc gently and carefully, washing of the dust, rust and dirt from all parts including taking out HT/LT leg coil core tank and cooling tubes, painting the inner side tank by zinc chromate paint and preparing the same for re-assembling after carrying out required repair and installation on existing 2/4 pole structure/ platform with neccessary fixing arrangment including connecting up electrically, commissioning and testing all as directed by Engineer-in-Charge and specified in particular specification :-Notes : (i) Rate quoted shall be inclusive of taking out and reinstalling after repair of transformer with the help of crane, including transportation to workshop and back incluiding handling. (ii) U/S wornout items required replacement shall be measured and paid separately under respective item of BoQ. |
| 54 | Supply Only new HV/LV coil Copper for item No 56 above |
| 55 | S&F in replacement digital volt meter suitable for panel board mounting complete all as specified and directed. |
| 56 | S&F in replacement digital Ammeter suitable for panel board mounting complete all as specified and directed. |
| 57 | S & F in replacement MCCB 400 Amp 4 pole 36 KA complete all as specified and directed. |
| 58 | S & F in replacement MCCB 250 Amp 4 pole 36 KA complete all as specified and directed. |
| 59 | S & F in replacement MCCB 160 Amp 4 pole 36 KA complete all as specified and directed. |
| 60 | Supply only HT 11000 volts DO fuse element aluminium type of 20A to 80 A rating |
| 61 | Supply only HT insulation tape with high di-electric strength (33 KV) of size 0.6mm x25 mm x16.5 Mtrs for HT & LT cable of any size all as directed by the Engr in Charge. |
| 62 | Labour for Disconnecting, Repairing, servicing and overhauling of existing HT 11 KV VCBs of any make from housing and cleaning, rubbing and overhauling the mechanical parts and servicing of 11 KV indoor VCB, checking of quality of vaccum interrupter, insulation resistances, static contact resistance, testing (IR value, Ratio test, Polarity test) and connection verification of 11 KV current transformer (Set of three) by PRIMARY INJECTION KIT, and testing and calibration of relay (set of two over current and one earth fault) by SECONDARY INJECTION KIT including all other functional tests of VCB, C&R panel and CTs, PTs complete all as directed. NOTE: (i) contractor shall make his own arrangement of testing equipments and electric supply so required.(ii) All spares required for replacement shall be measured and paid separetely under respective items here-in-after as supply only in supply only rates |
| 63 | Supply only 11 KV ABB classic VCB breaker spring charging motor 230 V, AC, all as specified and directed by Engr-in-charge. |
| 64 | Supply only indicator lamp suitable for VCB all as specified and directed by Engr-in-charge. |
| 65 | Supply only limit switch all as specified and directed by Engr-in-charge. |
| 66 | Supply only selector Switch for Voltmeter/Ammeter all as specified and directed by Engr-in-charge. |
| 67 | Supply only Master Trip Relay 110 Volt DC all as specified and directed by Engr-in-charge. |
| 68 | Supply only Trip Circuit Supervising Relay all as specified and directed by Engr-in-charge. |
| 69 | M & L for rewiring of Protection & Metering CTs, relays, meters contactors etc complete as required at site and as directed by Engr-in-Charge. |
| 70 | Supply only PT fuse set 3.15 amp all as specified and directed by Engr-in-charge. |
| 71 | Supply only PT male femle contact all as specified and directed by Engr-in-charge. |
| 72 | Supply only Over Current/ Earth fault/ Short Circuit current relay all as specified and directed by Engr-in-charge. |
| 73 | Supply and provide rubber mat of size 2m x 1m x 8mm thick all as specified and directed by Engr-in-charge. |
| 74 | M&L for providing precast RCC 1:1.5:3, type-A1, using 20 mm graded stone aggregates as in cable route indicator of height 800mm x width 300mm x thickness 120mm duly reinforced all as per details shown in drawing and having top circular section, provided with and including PCC 1:4:8, TYPE D2, using 40mm graded stone aggregates foundation of suitable size as directed and including engraving letters\\"MES 1 KV HT\\" on route indicator duly painted in synthetic enamel paint complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 28, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 19, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 15 daysOct 26, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 22 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender