Tender For Construction of Of Phc Building At Manju Tehsil Arki Distt. Solan Hp.(Sh: Providing electrical installation Therein )
Tender Value
10.13 Lakhs
Estimated cost
Bid Submission
05 Oct 2026
5 days left
EMD
20500
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Shimla → Himachal Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Construction of Of Phc Building At Manju Tehsil Arki Distt. Solan Hp.(Sh: Providing electrical installation Therein )
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group-B |
| 3 | Group-C |
| 4 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 6 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 7 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 8 | 4 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 9 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 10 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 11 | 3x1.5 Sq. mm. |
| 12 | 3x 4 Sq. mm. |
| 13 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 14 | 25 mm |
| 15 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 16 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 17 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 18 | S/E of LED Downlighter surface square with CRCA/PDC body and diffuser The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings. |
| 19 | Wattage of LED fittings-As per following parameter. |
| 20 | Total lumens of the fittings.-as below |
| 21 | Diffuser - Polycarbonate diffuser/PMMA |
| 22 | Operating voltage =140 V to 270 V, AC supply or better. |
| 23 | Input frequency =50 Hz + 1 Hz |
| 24 | Power factor =Minimum 0.90 |
| 25 | Luminaire efficacy =>85 lm/w |
| 26 | Color rendering index=CRI shall be greater than 80 |
| 27 | Working/ operating temperature =0 o to + 45 oc or better |
| 28 | Color temperature =60000K + 10% |
| 29 | Electronic Driver |
| 30 | Drive current (LED)=As per OEM. |
| 31 | Operating voltage =140 V to 270 V, AC supply or better. |
| 32 | Type of driver =Constant current output driver |
| 33 | THD =Less than 10% |
| 34 | Surge Protection =2.5 KV minimum |
| 35 | Efficiency Driver=>85% |
| 36 | Protection=Shall have under voltage and over voltage protection. |
| 37 | Guarantee of LED fittings including LED driver =2 years against manufacturing defect. |
| 38 | Fixture =Should comply with LM 79 test from UL/NABL lab. |
| 39 | LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 40 | Life of LED=50000 burning hours at 70% lumen maintenance |
| 41 | Lumen output of the fitting=>1200 Lumens |
| 42 | Lumen output of the fitting=>1500 Lumens |
| 43 | Lumen output of the fitting=>2000 Lumens |
| 44 | Lumen output of the fitting=>2400 Lumens |
| 45 | S/E of LED Batten with polycarboante body and diffuser The fitting should be installed on existing surface/recess The job includes carriage, erection, making connections testing and commissioning of the fittings.Specification of LED fittings: |
| 46 | Wattage of LED fittings-As per following parameter. |
| 47 | Total lumens of the fittings.-as below |
| 48 | Diffuser - Polycarbonate diffuser/PMMA |
| 49 | Operating voltage =140 V to 270 V, AC supply or better. |
| 50 | Input frequency =50 Hz + 1 Hz |
| 51 | Power factor =Minimum 0.90 |
| 52 | Luminaire efficacy =>100 lm/w |
| 53 | Color rendering index=CRI shall be greater than 80 |
| 54 | Working/ operating temperature =00 to + 450c or better |
| 55 | Color temperature =60000K + 10% |
| 56 | Electronic Driver |
| 57 | Drive current (LED)=As per OEM. |
| 58 | Operating voltage =140 V to 270 V, AC supply or better. |
| 59 | Type of driver =Constant current output driver |
| 60 | THD =Less than 10% |
| 61 | Surge Protection =2.5 KV minimum |
| 62 | Efficiency Driver=>85% |
| 63 | Protection=Shall have under voltage and over voltage protection. |
| 64 | Guarantee of LED fittings including LED driver =2 years against manufacturing defect. |
| 65 | Fixture =Should comply with LM 79 test from UL/NABL lab. |
| 66 | LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 25,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 67 | Life of LED=25000 burning hours at 70% lumen maintenance |
| 68 | Lumen output of the fitting=>1000 Lumens |
| 69 | Lumen output of the fitting=>2000 Lumens |
| 70 | S/E of LED bulk head IP 66 rated with aluminium body/PDC housing The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings. |
| 71 | Wattage of LED fittings-As per following parameter. |
| 72 | Total lumens of the fittings.-as below |
| 73 | Diffuser - Polycarbonate diffuser/PMMA |
| 74 | Operating voltage =140 V to 270 V, AC supply or better. |
| 75 | Input frequency =50 Hz + 1 Hz |
| 76 | Power factor =Minimum 0.90 |
| 77 | Luminaire efficacy =>80 lm/w |
| 78 | Color rendering index=CRI shall be greater than 80 |
| 79 | Working/ operating temperature =0o to + 45oc or better |
| 80 | Color temperature =60000K + 10% |
| 81 | Electronic Driver |
| 82 | Drive current (LED)=As per OEM. |
| 83 | Operating voltage =140 V to 270 V, AC supply or better. |
| 84 | Type of driver =Constant current output driver |
| 85 | THD =Less than 10% |
| 86 | Surge Protection =2 KV minimum |
| 87 | Efficiency Driver=>85% |
| 88 | Protection=Shall have under voltage and over voltage protection. |
| 89 | Guarantee of LED fittings including LED driver =2 years against manufacturing defect. |
| 90 | Fixture =Should comply with LM 79 test from UL/NABL lab. |
| 91 | LED Type/ Make/ Model-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer. |
| 92 | Life of LED=50000 burning hours at 70% lumen maintenance |
| 93 | Lumen output of the fitting=>800 Lumens |
| 94 | Supplying and fixing PVC batten/ angle holder including connections etc. as required. |
| 95 | Supplying and fixing of LED street light versatile pressure die-cast alluminium housing with UV stablized PC IP diffuser for better light distribution alongwith electronic driver,complete with all accessories including making connections, testing etc. as required. Make:- C&S, Wipro, Bajaj,Havells, Panasonic, or any other approved by Engineer-in-Charge. |
| 96 | LED street light 45 W |
| 97 | Supplying and erection of street light bracket made of G.I. pipe 'A' class of suitable length and dia, the pipe bended to give an angle of 100 to 110 degree fitted with bolt & nuts at the top of existing pole or wall including painting the pipe with two coats of approved paint over priming coat complete in all respects as required:- 32 mm dia. G.I. pipe, heavy class |
| 98 | Supply, Installation, Testing and Commissioning of following sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.85, Air delivery minimum 215 CMM, 300 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote/ BLDC electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 99 | Ceiling Fan 1200 mm sweep |
| 100 | Ceiling Fan 1400 mm sweep |
| 101 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 102 | Installation of ventilatinmg /exhaust fan in the existing opening, including making good BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor the damage, connection, testing, commissioning etc. as required.Supply & Erection of Ventilating Fan ) following size complete with motor,, with minimum power consumption, rigid frame with rubber mounting for silent operation, in the existing opening including cost of making the hole to suit the size of above fan making good the damage, Carriage Charges connection, testing, commissioning etc. as required to complete the job to the entire satisfaction of EIC. |
| 103 | Exhaust Fan, 250 mm sweep |
| 104 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 105 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 106 | 12 way, Double Door |
| 107 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 108 | Single pole |
| 109 | Supplying and fixing following rating, followings poles 10ka 240/415v 'C' curves miniature circuit braker suitable for inductive load of following poles in the exsisting MCB DB complete with connections, testing and commissioning etc. as required. |
| 110 | 63 A DP |
| 111 | Supplying and fixing following rating, follwing pole, (single phase and neutral), 240/415 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 112 | 63 A DP |
| 113 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 114 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. |
| 115 | Providing and installation of stationary storage type Electric water heater (Geyser) of various sizes with 8 bar pressure rating Five star BEE rating and safety valve installation by means of expansion-bolts with nuts and washers, including embedding of expansion-bolts in the wall, making good the damages, electrical connections, testing etc. complete as required:- |
| 116 | 25 Liter capacity water heater (Cat-A) |
| 117 | Supplying and erection of sub- panel 63 Amp. cubical panel enclosure DMC/SMC Insulator supports control wiring with thimble power wiring with thimble terminal block & short links door locks & hings rubber gasket heat shrinkable sleeves colour coded engraved name plate indoor type wall mounted complete with locking arrangement to house 63 Amp. MCCB with 100 Amp Copper busbar Phase indication lamps RYB. The cubical panel shall have cable entry at two sides complete in all respects including the cost of switchgears. |
| 118 | Providing, laying and fixing of one No. aluminium conductor, PVC insulated and PVC sheatthed, armoured/XLPE power cable, working voltage 1100 volts grade on surface etc.of the required size. |
| 119 | Armoured cable 25 sq. mm ( 3.5 core) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 28, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 05, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 5 daysOct 06, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender