Defence Statutory Bodies & Commissions/Committees Closing in 14 days TDR #57739266

Tender For Comprehensive Repairs/ Other Maints Works To Lt Oh Lines, Poles, Lt Cables And Other Connected Works Under Ge Babina

Issued by Statutory Bodies & Commissions/Committees · Jhansi, Uttar Pradesh
Tender Value
48 Lakhs
Estimated cost
Bid Submission
17 Oct 2026
14 days left
EMD
96000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Jhansi → Uttar Pradesh
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Comprehensive Repairs/ Other Maints Works To Lt Oh Lines, Poles, Lt Cables And Other Connected Works Under Ge Babina

BOQ

Name of Work:- COMPREHENSIVE REPAIRS/ OTHER MAINTS WORKS TO LT OH LINES, POLES, LT CABLES AND OTHER CONNECTED WORKS UNDER GE BABINA
Sl. No. Item Description
1Excavation in trenches in soft/loose soil not exc 1.5 mtrs wide and not exc 1.5 mtr in depth for laying of pipe/ cables/ poles etc and getting out complete all as specified and as directed.
2Excavation in trenches in any type of soil exc 1.5 mtr but not exce 3.0 mtr in depth for laying of pipe/ cables/ poles etc and getting out complete all as specified and as directed.
3Returning filling in any type of soil including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and as directed.
4Removing excavated soils to a distance n.exc. 50 mtr and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and as directed.
5Material and labour for Double wall corrugated HDPE pipe,PN-10 ISI marked of outer dia 63mm, inner dia 50 mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts including taking down of u/s existing HDPE pipes etc complete all as specified and directed by Engineer-in-Charge.
6Material and labour for Double wall corrugated HDPE pipe,PN-10 ISI marked of outer dia 90 mm, inner dia 75 mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts including taking down of u/s existing HDPE pipes complete all as specified and directed by Engineer-in-Charge.
7Supply and laying dry river sand for cable cushioning in trenches to required width at bottom and top of cable incl spreading, levelling, watering and consiolidation complete all as specified and directed. Note: Punned thickness of sand shall be measured for payment purpose
8Supply and laying PCC cable cover of size 250 x150 x 40 mm, laid in trench flat for protection of cable complete all as specified and directed by Engr in charge.
9M&L for PCC 1:2:4 type B-1 (using 20mm graded stone aggregates) as in coping etc including form work for poles all as specified and directed by Engr-in-Charge.
10M&L for PCC 1:4:8 type D-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete for poles all as specified and directed by Engr-in-Charge.
11M&L for PCC 1:3:6 type C-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete including form work for poles all as specified and directed by Engr-in-Charge.
12Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 300Sqmm 3.5 core as per IS 7092 Pt -I and conneciont with suitable size aluminium lugs/thimble including taiking out old u/s existing LT cable complete all as specified and directed.
13Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 185Sqmm 3.5 core as per IS 7092 Pt -I and conneciont with suitable size aluminium lugs/thimble including taiking out old u/s existing LT cable complete all as specified and directed.
14Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 150Sqmm 3.5 core as per IS 7092 Pt -I and conneciont with suitable size aluminium lugs/thimble including taiking out old u/s existing LT cable complete all as specified and directed.
15Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 95Sqmm 3.5 core as per IS 7092 Pt -I and conneciont with suitable size aluminium lugs/thimble including taiking out old u/s existing LT cable complete all as specified and directed.
16Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 70Sqmm 3.5 core as per IS 7092 Pt -I and conneciont with suitable size aluminium lugs/thimble including taiking out old u/s existing LT cable complete all as specified and directed.
17Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 50Sqmm 3.5 core as per IS 7092 Pt -I and conneciont with suitable size aluminium lugs/thimble including taiking out old u/s existing LT cable complete all as specified and directed.
18Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 25Sqmm 4 core as per IS 7092 Pt -I and conneciont with suitable size aluminium lugs/thimble including taiking out old u/s existing LT cable complete all as specified and directed.
19Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 16Sqmm 4 core as per IS 7092 Pt -I and conneciont with suitable size aluminium lugs/thimble including taiking out old u/s existing LT cable complete all as specified and directed.
20Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 16Sqmm 2 core as per IS 7092 Pt -I and conneciont with suitable size aluminium lugs/thimble including taiking out old u/s existing LT cable complete all as specified and directed.
21Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 10Sqmm 2 core as per IS 7092 Pt -I and conneciont with suitable size aluminium lugs/thimble including taiking out old u/s existing LT cable complete all as specified and directed.
22S&F for replacement & testing commissioning of outdoor type bus bar panel, CPRI Approved weather proof MS cubical panel board made of 3.15 mm CRCA MS sheet outdoor type of size 110 cm x 80 cm x 40 cm, 4 Nos of aluminium bus bar of 500 Amp capacity with MCCB 4 pole of Capacity 315 Amp 25 KA (Ics =Icu=100%) including one coat of redoxide and two coat of enamel paint powder coated, mounted on angular frame work of 50x50x5mm thick angle iron base frame, minimum 60 cm hight and fixed with PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels, aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator all as specified & directed. Make:- M/s Mclayers Bhopal/M/s shalabh(india) Ltd/ M/s universal switchgear Ltd.
23Note:- (i) Panel drawing and make of MCCB and connected accessories will be submitted by the contractor for approval of Accepting officer before ordering the panel. (ii) The holes / aprons of cable exit and incoming should be close with suitable size of gland.( iii) The contractor should submit all Certificates before executing the job. (iv) CA No.,Contractor name, item of CA No. to be mentioned on the panel.(v) Suitable Cable glands for incoming cables and outgoing cable to be provided in the panel by the contractors. Cost of provisioning of cable glands deemed to be included in qouted rate.
24S&F for replacement & testing commissioning of outdoor type bus bar panel, CPRI Approved weather proof MS cubical panel board made of 3.15 mm CRCA MS sheet outdoor type of size 110 cm x 80 cm x 40 cm, 4 Nos of aluminium bus bar of 300 Amp capacity with MCCB 4 pole of Capacity 200 Amp 25 KA (Ics =Icu=100%) including one coat of redoxide and two coat of enamel paint powder coated, mounted on angular frame work of 50x50x5mm thick angle iron base frame, minimum 60 cm hight and fixed with PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels, aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator all as specified & directed. Make:- M/s Mclayers Bhopal/M/s shalabh(india) Ltd/ M/s universal switchgear Ltd.
25Note:- (i) Panel drawing and make of MCCB and connected accessories will be submitted by the contractor for approval of Accepting officer before ordering the panel. (ii) The holes / aprons of cable exit and incoming should be close with suitable size of gland.( iii) The contractor should submit all Certificates before executing the job. (iv) CA No.,Contractor name, item of CA No. to be mentioned on the panel.(v) Suitable Cable glands for incoming cables and outgoing cable to be provided in the panel by the contractors. Cost of provisioning of cable glands deemed to be included in qouted rate.
26S&F for replacement & testing commissioning of outdoor type bus bar panel, CPRI Approved weather proof MS cubical panel board made of 3.15 mm CRCA MS sheet outdoor type of size 110 cm x 80 cm x 40 cm, 4 Nos of aluminium bus bar of 300 Amp capacity with MCCB 4 pole of Capacity 160 Amp 25 KA (Ics =Icu=100%) including one coat of red oxide and two coat of enamel paint powder coated, mounted on angular frame work of 50x50x5mm thick angle iron base frame, minimum 60 cm hight and fixed with PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels, aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator all as specified & directed. Make:- M/s Mclayers Bhopal/M/s shalabh(india) Ltd/ M/s universal switchgear Ltd.
27Note:- (i) Panel drawing and make of MCCB and connected accessories will be submitted by the contractor for approval of Accepting officer before ordering the panel. (ii) The holes / aprons of cable exit and incoming should be close with suitable size of gland.( iii) The contractor should submit all Certificates before executing the job. (iv) CA No.,Contractor name, item of CA No. to be mentioned on the panel.(v) Suitable Cable glands for incoming cables and outgoing cable to be provided in the panel by the contractors. Cost of provisioning of cable glands deemed to be included in qouted rate.
28S&F in repair aluminium lugs/thimble of size 16 Sqmm LT XLPE cable complete all as specified and as directed.
29S&F in repair aluminium lugs/thimble of size 25 Sqmm LT XLPE cable complete all as specified and as directed.
30S&F in repair aluminium lugs/thimble of size 50 Sqmm LT XLPE cable complete all as specified and as directed.
31S&F in repair aluminium lugs/thimble of size 70 Sqmm LT XLPE cable complete all as specified and as directed.
32S&F in repair aluminium lugs/thimble of size 95 Sqmm LT XLPE cable complete all as specified and as directed.
33S&F in repair aluminium lugs/thimble of size 120 Sqmm LT XLPE cable complete all as specified and as directed.
34S&F in repair aluminium lugs/thimble of size 185 Sqmm LT XLPE cable complete all as specified and as directed.
35S&F in repair aluminium lugs/thimble of size 240 Sqmm LT XLPE cable complete all as specified and as directed.
36S&F in repair aluminium lugs/thimble of size 300 Sqmm LT XLPE cable complete all as specified and as directed.
37S&F in repair aluminium lugs/thimble of size 400 Sqmm LT XLPE cable complete all as specified and as directed.
38S&F in repair aluminium lugs/thimble of size 630 Sqmm LT XLPE cable complete all as specified and as directed.
39M&L for attending complaint of repair/ replacement of jumper on pole including taking out defective portion and making connection by providing suitable size conductor complete all as specified and as directed.
40M&L for attending complaint by disconnecting over head conductor, cutting worn out portion of LT under ground cables of any size and capacity includes taking out cable from under ground loop and rejoin the same to restore electric supply complete all as specified and as directed.
41M&L for attending complaint by disconnecting cable from LT switch gear/main switch of any type and capacity including providing suitable size of aluminium lugs complete all as specified and as directed.
42Labour only for attending complaint by replacement of worn out insulators of any type and size for 1100 Volts grade complete all as specified and as directed.Note:- Insulator will be measured and paid seperatly under respective items.
43S&F in repairs pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut of size 100 mm height, 65 mm dia for 1100 volts grade complete all as specified and directed.
44S&F in repair Shackle type 75mm height and 90mm dia insulator, porcelain, vitreous, white, brown or green including galvanised mild steel strap 31mm X 3mm, insulator bolts 12mm dia with suitable washers and nut, suitable for working pressure upto & including 1100 volts fixed on LT poles complete all as specified and directed.
45S & F in replacement of Air circuit breaker 04 Pole, 630 Amp 50KA for one second as per IS/IEC 60947-2 ICS=ICU =100% fixed type with thermal magentic release ,manual operated incl dismantling and taking out old U/S ACB from panel & fabrication work to bus bars for proper fitting etc complete etc complete all specified and directed.
46Supply and fixing in repair three phase automatic street light timer switch of capacity 12 KW using integrated sensor based NATURE SWITCH for automatic switching of street light based on LUX level of natural light required illuminance for switching on is less than 30Lux and for switching off greater than 10 Lux level. The sensor (nature switch) along with suitable power contactors input (supply) MCB and output (load MCB (s), support terminals should be enclosed in pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR graded SMC junction box conforming to IP 66 degree of ingress three phase 8KW lighting load capacity including mounting bracket, cable glands, openable doors with locking arrangement complete all as specified and as directed. The contactor MCB and circuit wiring should enough to take load of 12 KW equally distributed over three phase and street light timer should be comprising of following:-
47(a) Input MCB rating 40 Amps 230 volst-03 Nos(b) Contactor rating 40 Amps 230 volts- 03 Nos(c) Out put MCB rating 40 Amps vots-03 Nos(d) three phase circuit wiring minimum 10 Sqmm multistranded copper wire.Make: Cat Part No SWADEEP-02EC 12 KW1P, Note :- 01 Year Guarantees+01 year warranty on remaining other item from date of purchase.
48Supply and fixing in repairf single phase automatic street light timer switch of capacity 8KW using integrated sensor based NATURE SWITCH for automatic switching of street light based on LUX level of natural light required illuminance for switching on is less than 30Lux and for switching off greater than 10 Lux level. The sensor (nature switch) along with suitable power contactors input (supply) MCB and output (load MCB (s), support terminals should be enclosed in pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR graded SMC junction box conforming to IP 66 degree of ingress three phase 8KW lighting load capacity including mounting bracket, cable glands, openable doors with locking arrangement complete all as specified and as directed. The contactor MCB and circuit wiring should enough to take load of 8KW equally distributed over single phase and street light timer should be comprising of following:-
49(a) Input MCB rating 63 Amps 230 volst-01 Nos(b) Contactor rating 63 Amps 230 volts- 01 Nos(c) Out put MCB rating 63 Amps 230 vots-01 Nos(d) three phase circuit wiring minimum 16 Sqmm multistranded copper wire.Make: Cat Part No SWADEEP-02EC 8 KW1P, Note :- 01 Year Guarantees+01 year warranty on remaining other item from date of purchase.
50M & L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to galvanised earth lead 32X6mm by means of bolts, nuts, check nuts and washers of galvd iron or steel surronded by charcoal of coke and salt and protected by galvanized iron or steel pipe light grade 40 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 5 of MES schedule Pt I of 2009 and also including making test point for testing of earthing made out of gun metal or phosphorous bronge size 75x75x25 mm complete all as specified and directed by Engineer in Charge.
51Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover.2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values less than 2 ohms.3. The cost of GI earth lead and GI pipe of 7.50m lenth for protection of GI wire and excavationwork fpr pit shall deemed to be included in this item. Please Enable Macros to View BoQ information
52Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover.2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values less than 2 ohms.3. The cost of GI earth lead and GI pipe of 7.50m lenth for protection of GI wire and excavationwork fpr pit shall deemed to be included in this item. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57739266
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 48 Lakhs
LAST DATE 17-10-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Comprehensive Repairs/ Other Maints Works To Lt Oh Lines, Poles, Lt Cables And Other Connected Works Under Ge Babina
Basic Detail
Tender No 8558/E8
Bidding Type Tender
Location
City Jhansi
State Uttar Pradesh
Key Dates
Publish Date 26 Sep 2026
Submission Date 17 Oct 2026
Open Date 22 Oct 2026
Finance
Tender Value 48 Lakhs
Tender Fee 500
EMD 96000
Exemption Available
Document List
4f0871a3-a10a-45fb-862b-cde47521d6df.html
8558E8_CreditSchedule_1.pdf
8558_tenderDoc_1.pdf
BOQ_887146.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 26, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 17, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 14 days
Oct 22, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 19 days

Tender Documents

Download All (ZIP) ↓
html

4f0871a3-a10a-45fb-862b-cde47521d6df.html

pdf

8558E8_CreditSchedule_1.pdf

pdf

8558_tenderDoc_1.pdf

xls

BOQ_887146.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders