Tender For Construction Of Bn/Coy Mob Store With Allied Services At Barrackpore Military Station Under Ge Barrackpore.
Tender Overview
Project Description
Tender for Construction Of Bn/Coy Mob Store With Allied Services At Barrackpore Military Station Under Ge Barrackpore.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 29-Sep-2026 | Drawing | Other | 31-Oct-2026 |
| 2 | 23-Oct-2026 | Date corrigendum | Date | 10-Nov-2026 |
| 3 | 10-Nov-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 17-Nov-2026 |
| 4 | 17-Nov-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 23-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | \\" BOQ \\" BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority : GE BARRACKPORE NAME OF WORK: CONSTRUCTION OF BN/COY MOB STORE WITH ALLIED SERVICES AT BARRACKPORE MILITARY STATION UNDER GE BARRACKPORE. Contract No: GE/BKP/ OF 2026-2027 Bidder Name : GENERAL SUMMARY (SCHEDULE OF WORKS) (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # NUMBER # Sl.No. Description of Parts/ Item Item Code / Make No. orQty. Unit Pre Priced Rate (in. Rs.) as Defined by MES Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder Rs. Ps. Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT in Figure TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words Represent (%) Percentage having Above/ Below ( + or - denomination) the Lump sum pre price inserted by MES |
| 2 | NOTE:- (Applicable for all parts/items/):- The bidders/contractors are advised to read tender document, all drawings & all corrigendum/ amendments and General conditions of contracts before entry/quoting the rates. |
| 3 | SCHEDULE A PART (I) PREPRICED BUILDING SSR |
| 4 | Lumpsum price worked out by the tenderer for BUILDING & STRUCTURE WORK as listed in Schedule ‘A’ Part-I |
| 5 | Lumpsum price worked out by the tenderer for SITE CLEARANCE, SITE DEVELOPMENTS & EARTH WORKS as listed in Schedule ‘A’ Part-II |
| 6 | Lumpsum price worked out by the tenderer for ROAD/PATH/CULVERTS/HARD STANDING as listed in Schedule ‘A’ Part-III |
| 7 | Lumpsum price worked out by the tenderer for AREA DRAINAGE as listed in Schedule ‘A’ Part-IV |
| 8 | Lumpsum price worked out by the tenderer for INTERNAL ELECTRIFICATION as listed in Schedule ‘A’ Part-V |
| 9 | Lumpsum price worked out by the tenderer for EXTERNAL WATER SUPPLY as listed in Schedule ‘A’ Part-VI |
| 10 | SCHEDULE 'A' SEC-VII (MISCELLANEOUS ITEMS) NOTE: THIS SCHEDULE IS NOT PRE-PRICED BY MES AND THE PRE-PRICED RATE INDICATED AS \\"RS 0.00\\" UNDER COL. 5 SIGNIFIES THIS FACT ONLY. |
| 11 | Bringing approved earth (as approved by Garrison Engineer) from sources outside defence land including all costs such as royalty if any transportation taxes etc. for area filling / forming including raising earth spreading in layers not exc 30 cm thick each layer, watering, compaction with 8 tonne to 12 tonne power roller and finished to required size and shape etc, any high / depth from EGL. Notes:- (i) Earth required for the item shall be supplied by contractor out side MOD land of any lead at his own arrangement. (ii) All cost of procurement of earth including cost of transportation, compaction, royalties, tax etc. shall be deemed to be included in the unit rate quoted by the contractor. (iii) with reference to clause 3.6 of MES schedule Part-II on serial page no- 21 it is clarified that measurement of the above item shall be finished embankment/ traverse of filled earth after consolidation/ compaction and 5% deduction shall be made from measured and calculated volume to allow for increase in bulk. (iv) Total quantity/ partial of earth may not be available in Barrackpore area. The contractor shall bring the earth outside area it is advised to quoted the rate considering availability of soil and its lead involved complete all as specified and as directed. |
| 12 | M&L for Cutting the existing pipe of size 40 mm pipe and making new connection including provision of TEE complete all as specified and as directed. |
| 13 | S&F integral LED 4ft luminaire of CRCA / extruded aluminium housing and PC diffuser (Diffuser-Non yellowing type). The luminaire should have a 20 Watt LED with colour consistency SDCM< 5,CRI> 80 and colour temperature - 4000 to 6500K, Luminaire shall be designed to emit at least 2400 nominal lumens at a system efficacy of at-least 120 lumen/watt, power consumption should not be more than 20W (+5%). the life of fixture (including Driver): 50000 burning Hrs.@ L70B50 Lumen maintenance @ design ambient temp 50 deg C. The electronic driver used shall have a power factor >0.95 and THD < 10% suitable for an operating voltage range of 150-270V AC current Ripple<5% internal surge protection should be minimum 4KV, electrical insulation class should be Class I &driver should be of class B serviceability. The luminaire should be at least IP20 & IK02 rated. The luminaire driver shall be of the same make/manufacturer as that of LED luminaires. Luminaire manufacturer must have in house NABL accredited lab conduct LM79, type test as per IS10322 & \\"FAT\\" before dispatch as per IS 10322. The contractor must submit the NABL accreditation certificate for luminaire manufacturer along along with sample approval. The LED Luminaire & It's driver both should be BIS registered contractor shall submit the following reports before supply of material for approvals LM79 issued by NABL accredited lab, LM80 issued by LED manufacturer type test certificate for luminaire as issued by NABL accredited lab, RoHS compliance issued by LED luminaire manufacturer, BIS certificate for LED Luminaire & Driver complete all as specified and as directed. |
| 14 | S&F LED street light fitting of high-quality group control enabled integrated LED Bldg Security light with a minimum system lumen of min 4900 lm and system wattage not less than 35W with a nominal system efficacy of 140 lumen/watt. The LED used shall have CCT of 5700K, SDCM ≤ 5 and CRI≥70. The housing should be made of LM6/ADC12 Alloy, non-corrosive Single Piece pressure die-cast aluminum, to withstand extreme environments. The spigot shall be part of “Single Piece Pressure Die-cast housing” & shall not be bolted to the luminaire housing to ensure robust design. The name of the brand should be embossed/engraved & should not be mentioned using sticker/screen printing. It should have corrosion resistant powder coating to pass NSS of 500 Hrs. The luminaire LED shall have declared Lifetime of 50K hours@L70B50. The product should be designed for continuous operation (10-12 Hrs. per day). The Ingress protection should be minimum IP66 & impact resistance shall be IK10. Control gear compartments shall be Top maintainable without accessing/opening the optical compartment. The Luminaire should have a minimum 20 KV/10KA SPD duly bolted in the Luminaire. The SPD should be able to sustain a minimum 15 hits of 10KA rating i.e. Total of 45 hits across all the three modes as per IEEE 62.41.2. The luminaire should be of Class B Serviceability. The Driver should be asphalt potted & should be a BIS approved driver. The driver shall have operating voltage of 120V to 270V, PF≥0.95 @ full load, THD≤10% @ full load. The driver should be capable of withstand voltage stress of 440V for 8 Hrs., should have an auto shutdown @ 325V(±15V) and have an auto recovery feature. The driver shall comply to IEC61547 & IEC 61000-3-2. The luminaire driver & it’s SPD shall be of the same make/manufacturer as that of LED luminaires. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79, Type test as per IS10322 & \\"FAT\\" before dispatch as per IS 10322. The contractor must submit the NABL accreditation certificate for Luminaire manufacturer along with Sample Approval. The LED Luminaire & it's driver both should be BIS registered. The contractor shall submit the following reports before supply of material for approvals: LM79 issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test report for luminaire as issued by NABL accredited lab, RoHS compliance issued by LED luminaire manufacturer, BIS certificate for LED Luminaire & Driver complete complete all as specified and as directed. |
| 15 | S & F security light bracket made out of GI pipe 32mm dia medium grade (bent to shape as directed ), 1.20 M long, fixed with MS flat iron clamps made out of 32 mm x 6 mm - 02 Nos with nuts, bolts, washers and other connected items of required size, suitable for steel tubular poles/wall and painting with one coat of aluminium paint over a coat of red oxide zinc chrome primer complete all as specified and as directed. |
| 16 | M & L for earthing in replacement complete with galvanised steel earth plate electrode 60 Cm X 60 Cm X 6 mm buried directly in ground vertically to a depth not less than 2.25 mtr deep below ground level with top edge of earth plate at a depth not less than 1.5 m below normal ground level connected to galvanised earth lead wire 4.0 mm dia by means of bolts, check nuts and washers, galvanised steel and protected by GI pipe 15 mm bore light grade & connected to main switch board or main control board as directed and including concrete pit in PCC (1:3:6) type C1, precast RCC (1:2:4) type B1 cover slab 30 cm X 30 cm X 5 cm with 10mm dia TMT bars 8 cm C/c both ways and one handle for lifting made out of 8 mm dia TMT bar, funnel, wire mesh, 20mm bore galvanised iron pipe (medium grade) for watering, charcoal or coke and salt in alternative layers, necessary excavation and earth work in any type of soil and including necessary testing complete all as shown in Electrical Plate No 3 of SSR part -I complete all as specified and as directed. Total in Figures 0.0 0.0 INR Zero Only Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-3 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-4 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 1 dayBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 4 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender