Tender For Electrical Work For Establishment Of E-Library At Ashok Udhyan Jodhpur
Tender Value
40.53 Lakhs
Estimated cost
Bid Submission
07 Oct 2026
4 days left
EMD
81060
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jodhpur → Rajasthan
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Electrical Work For Establishment Of E-Library At Ashok Udhyan Jodhpur
BOQ
| Sl. No. | Item Description |
| 1 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminum round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 6 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. |
| 2 | Short point (up to 3 mtr.) |
| 3 | Medium point (up to 6 mtr.) |
| 4 | Long point (up to 10 mtr.) |
| 5 | Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminium round tiles, 2 Nos Hot Dipped Galvanized M.S Modular box of 1.2 mm thick with earth terminal,2 Nos 6 A two way Modular switch, 3 pin ceiling rose / holder / 3 way connector ,Modular face plate with grid plate, screws, making connections, testing etc. as required. |
| 6 | Short point (up to 3 mtr.) |
| 7 | Medium point (up to 6 mtr.) |
| 8 | Long point (up to 10 mtr.) |
| 9 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 6 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required. |
| 10 | On board |
| 11 | Short point (up to 3 mtr.) |
| 12 | Medium point (up to 6 mtr.) |
| 13 | Long point (up to 10 mtr.) |
| 14 | S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including making jhiri in the wall,clamps at suitable spacing, covering conduit and making good the same as required. |
| 15 | 25 mm |
| 16 | 32 mm |
| 17 | Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. |
| 18 | 2 x 1.5 sq.mm |
| 19 | 1 x 2.5 sq.mm |
| 20 | 1 x4.0 sq.mm |
| 21 | 1*6.0 sqmm |
| 22 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. |
| 23 | Single pole MCB (With B/C curve tripping Characteristics) |
| 24 | 6 A to 32 A rating |
| 25 | Four pole MCB (With B/C curve tripping Characteristics) |
| 26 | 40 A rating |
| 27 | 50/63 A rating |
| 28 | Providing & Fixing of 240/415 V isolator ISI marked IS:13947-III/conforming to IEC 60947-3, suitable for AC22A utilization catagory, 4KV impulse withstand voltage, true contact indication, Red colour dolly / lever shall have single mould covering over all poles for operation , two position din rail mounting, minimum phase termination capacity of 25sq.mm. IP 20 contact protection and fitted in existing distribution board / sheet including making connections, testing etc. as required. |
| 29 | Double pole isolator |
| 30 | 63 A rating |
| 31 | Four pole Isolator |
| 32 | 40 A rating |
| 33 | 63 A rating |
| 34 | Providing & Fixing of 240/415 V Residual current circuit breaker (RCCB) conforming to (IS:12640-1)/ IEC 61008 -1 , rated 4 KV impulse withstand voltage truly current operated and shall operate on CBCT mechanisum, provision for pad lock, min. Electrical operation 10,000 upto 63 A rating and 5000 for 100 A rating and minimum phase termination capacity of 25 sq.mm. rigid wire , IP 20 contact protection with existing distribution board / sheet including making connections, testing etc. as required. |
| 35 | Two pole 30 mA sensitivity |
| 36 | 63A Rating |
| 37 | Four pole 30 mA sensitivity |
| 38 | 40 A rating |
| 39 | 63 A rating |
| 40 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door (Metal / Glazed / Acrylic) Distribution board with Metal end box made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, complete with 100 amp. insulated copper bus bar/shorting link , brass neutral link with shrouds, brass earth link , door earthing arrangement, color coded interconnecting wire set of minimum 10.0 sqmm size and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. |
| 41 | Metal door (Three phase) IK-09 and IP-43 with Metal end box |
| 42 | 8 Way (8 incomer + 24 Outgoing) |
| 43 | 12 Way (8 incomer + 36 Outgoing) |
| 44 | Providing & Fixing of ISI marked (IS:371) 6 amp surface type 3 pin ceiling rose with CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal & captive screws including making connection testing etc. as required. |
| 45 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- |
| 46 | (a) Thickness of CRCA sheet shall not be less than 1.6 mm upto 450 mm length/ width of any compartment and be 2.0 mm above 450 mm, load bearing structure shall be 2.0 mm thick sheet supported by base M.S. channel if required, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided |
| 47 | (b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side(Inner & Outer side) of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. |
| 48 | [c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra ) |
| 49 | (d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. |
| 50 | (e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. |
| 51 | (f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra ) |
| 52 | (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. |
| 53 | (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI type Test certificates for Temp. rise test, Short circuit test for 50 kA and IP test is to be submitted) |
| 54 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator, with short circuit withstand capacity of 31 MVA for 1 Sec. , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. |
| 55 | Electrolytic grade Aluminium bus bar 6010 grade |
| 56 | Providing & Fixing of IS: 13875 & IEC :61326/IEC:62053-22 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT opertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. |
| 57 | Three phase Ammeter with Inbuilt Selector Switch |
| 58 | Three phase Voltmeter with Inbuilt Selector Switch |
| 59 | Frequency Meter |
| 60 | Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 27 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. |
| 61 | Red/yellow/Green colour |
| 62 | Blue / white Colour |
| 63 | Providing & Fixing of Electrical insulating rubber matts confirming to IS: 15652 / 2006 with one side anti skid aberration marks and pasting the mat with synthetic rubber adhesive as required. |
| 64 | 3.3 KV, class A 2 mm thick with proof voltage 10 KV AC (rms) and Break Down Voltage 30 KV AC (rms) |
| 65 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. |
| 66 | 4 pole MCCB With Thermal Magnetic release |
| 67 | 125 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 68 | 250 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 69 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 70 | 95.0 Sq. mm |
| 71 | 3.5 core |
| 72 | 50.0 Sq. mm |
| 73 | 3.5 core |
| 74 | 25.0 Sq. mm |
| 75 | 3.5 core |
| 76 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. |
| 77 | 8 SWG G.I. ( Hot Dipped ) Wire |
| 78 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. |
| 79 | Providing & Fixing of BEE Star rated copper wounded with class of Insulation 'F', double ball bearing capacitor start, aluminium body & aluminium blade ceiling fan conforming to all the performance requirements laid down in IS 374:2019 with down rod up to 30 cm with secondary support safety cable ( steel rope) , cotter pin, shackle kit with 3 x 1.5 sq.mm pvc insulated flexible copper conductor and making connection testing etc. as required. |
| 80 | 1200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 ) |
| 81 | Providing & Fixing of 400 mm Sweep BLDC technology Oscillating type Wall mounting / Pedestal type fans with Three speed, ON and OFF position, Double Wall bearing with front and back 120 or more ribs guard; Three no. blades, noise level should be <= 75 dB, including fixing with anchor bolts, making connection testing etc. as required. ( With Remote ) |
| 82 | Wall mounting type with Service value 2.0 CMM /W, Min. Air Delivery 71 CMM |
| 83 | Providing & Fixing of of M.S. J- hook of standard design made out of 16 mm dia. M.S. round bar and fixed with cement concrete mortar with required support as required. |
| 84 | P & F 1.2 mm thick M.S. Recessed fan box and top lid screwed on Box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 150 mm length extended on each side as required. |
| 85 | Providing & Fixing of IS 11037 marked non modular socket size flush type 100 watt rotary minimum 5 step fan regulator with CM/L no. printed and made out from industrial grade Polycarbonate material including making connection testing etc. as required. |
| 86 | SITC of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output only at CW (5700K to 6500K) , internal surge protection of 4.0 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 87 | 1170mm(+/-10%) LED batten with min. lumen output 4400 lm |
| 88 | SITC of IP-20 LED Recessed / Surface Mounted, Round / Square backlit & SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS compliance 4.0 KV surge protected Isolated driver, with Short & Open circuit protection input 320VAC-48 hr protection, input 350VAC-2 hr protection), having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt,at CW (5700K to 6500K) , THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 89 | Surface Mounting (with extruded alumn. Housing ) |
| 90 | Minimum lumen output 2400 lm |
| 91 | SITC of Radiator Cooled Silent DG Set (As per latest CPCB-IV+ emission norms) having specifications as per A, B, C, D, E, F & G : |
| 92 | A) Diesel Engine : Turbo charged Diesel Engine ( conforming to BS:649/5514), multi cylinder, dynamically balanced flywheel, electric start of suitable BHP at 1500 rpm capable of taking 10% over loading for one hour after 12 hours of continuous operation., Dry exhaust mainfold with silencer and Diesel oxidation catalyst & selective catalyst reduction system (isolated from main DG chamber), up to 1.50 M exhaust piping (with LRB insulation & Alum. cladding ) as required .Diesel engine should have Precise emission control by treatment with Diesel exhaust fluid (DEF)/Aqueous urea tank (above 82.5 KVA) as per CPCB 4+ norms |
| 93 | B) Alternator : AC Brush less SPDP Synchronous alternator rated of appropriate KVA, 415 volts at 1500 rpm, 3 phase, 50 Hz, ac supply with 0.8 lagging power factor. Alternator conforming to BS 5000 (part 99) or IS/IEC 60034-1. . Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown). |
| 94 | C) Canopy : CPCB / ARAI approved Standard canopy with Weatherproof, powder coated Accoustic enclosure for DG set for sound attenuation fabricated from CRCA sheet steel (structure) including sidewals & filled with glasswool (96Kg/m3) /PU Foam. as per IS8183 and the thickness of the doors should be 28/40/50/85 mm as per rating . All doors/opening are sealed with neoprene /EPDN gaskets. The DG Set has Inbuilt / External in fuel tank to run 6 to 8 Hrs along with DEF tank (as per OEM standards). There should be provision of protection and tripping of DG set for temperature greater than 50 degree centigrade. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dB at a distance of 1 Mtrs. in open free field environment as per ISO 8528 part 10 duly certified by authorised agency etc. |
| 95 | D) Instruments : Electronic / Mechanical governor, Manual & electric Start ,Batteries with battery charger, Electronic fuel system, advanced after treatment system (ATS), Exhaust gas recirculation(EGR) System along with Diesel oxidation catalyst(DOC) and Selective catalytic reduction (SCR) , supply module and DCU to control and monitor DEF. Engine instruments panel should have microprocessor based Genset monitoring system capable of displaying Running Hour, RPM, lubbrication oil pressure indication, lubrication oil temperature, battery charging indication, overspeed indication, fuel level etc. The control Panel should equipped with MCCB/ACB of suitable rating. |
| 96 | E) Base frame and foundation : Both the engine and alternator shall be mounted on suitable base frame made of MS channel & coupled through a flexible coupling or close coupled which shall be installed on existing cement concrete foundation and vibration isolation arrangements as per recommendation of manufacturer. |
| 97 | F) First filling of the FUEL Tank and DEF tank shall be done by contractor. |
| 98 | G) DG set will be offered for Inspection and Testing at OEM's Works ( as per approved QAP ) in presence of Departmental Engineers .In case of 13 hour running testing at OEM's works, cost of actual consumables will be reimbursed. |
| 99 | Note: 1. During the DLP, the contractor shall arrange for servicing of the DG set through authorized dealer of OEM, as per the manufacturers guidelines. The actual cost of consumables used during servicing will be reimbursed to the contractor by the end user department.2. Manufacturer / OEM must have its authorized service dealer in Rajasthan. Which can provide service within 6 Hours of compalint registration. |
| 100 | 58.5 KVA at 0.8 pf 415V 50Hz 3-ǿ with 4 Cylinder Engine |
| 101 | SITC of Auto main failure (AMF) Panel fabricated from CRCA sheet steel 2 mm Thick , Powder coated finish , Engine Start & Stop commands, control Relays , Ammeter & Voltmeter with selector switches, Control & 2 nos of required size 4 pole AC1 duty Power Contactors with 2 no. of required size 4 pole MCCB with Icu=100% Ics 25KA breaking capacity upto 200KVA & 50 KA above 200 KVA rating with adjustable O/L & fixed Short circuit, Timers, Electronic Hooter ,Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for following capacity DG sets: ( M S / RCC structure required for AMF panel will be paid extra ) |
| 102 | 50 to 82.5 KVA |
| 103 | P&F metal clad / Polyamide industrial plug top & socket unit with pin and sleeve type contact on porcelain/ bakelite base in Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet , powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. (without MCB) including making connections, testing etc.as required. |
| 104 | 20 amp, (2P + E), 3 Module |
| 105 | Providing & Fixing of modular type 100W Step Fan regulator duly ISI marked (IS 11037) with CM/L no. printed made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including making connections, testing etc as required. |
| 106 | 5 step fan regulator 2 Module |
| 107 | Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect. |
| 108 | 3 Module |
| 109 | 6 Module |
| 110 | 8 Module |
| 111 | Providing & Fixing of Hot dipped Galvanized metal box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required. |
| 112 | 1-2 Module |
| 113 | 6 / 8 module |
| 114 | 10 / 12 module |
| 115 | Providing & Fixing of Four Pole By pass Change Over Switch confirming to IS:13947(Part 3) : IEC:60947-3-1 and IEC:60947-6-1, Open execution type in the following ratings. |
| 116 | 400 A |
| 117 | Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 marked in existing opening including making connections testing etc. as required. |
| 118 | 450 mm sweep(1400 RPM) |
| 119 | Supply , Installation, Testing and Commissioning of Inverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and 50 hz , single phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. Min 5 year Original Equipment Manufacturer (OEM) warranty of both compressor and Printed Circuit Board (PCB). |
| 120 | Cooling capacity 6800-7000 Watt, ISEER not less then 3.8 |
| 121 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. |
| 122 | 25 mm |
| 123 | Supply, Fixing and testing of following capacity IS:8448 marked wall mounted stabilizer having output voltage variation from 200 V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time delay facility from 2 to 4 minute and high cutoff at 270 V with providing of 16 Amp /20 Amp Industrial plug top making connection etc complete in all respect. |
| 124 | 5 kVA |
| 125 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia |
| 126 | 100 mm dia per running inch length |
| 127 | Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC. All as per pre approved by Engineer in charge. |
| 128 | SITC of Interconnecting refrigerant copper pipe for split/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizes as per OEM requirement & specifications including class 'O' Nitrile rubber sleeves (size as per item no. 22.43),7 mil Glass Cloth with 3 coats of anti UV paint (on area which is exposed to weather) chase cutting, supports, making good the same with sand cement plaster etc. as required. |
| 129 | Supply & Fixing of CO2 type Fire Extinguisher conforming to IS:15683:2018, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.0 Mtr. Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability, including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. |
| 130 | Capacity 4.5 Kg. |
| 131 | Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC type Fire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. |
| 132 | Supply , Installation, Testing and Comissioning of IS:1475 marked self contained drinking water cooler with hermetically sealed compressor,non CFC refrigerent suitable for operation on 230V/1pH/50Hz AC supply,Full stainless steel (SS304)body (0.8 mm thick) and tank (0.5 mm thick) , stainless steel water tray,minimum two nos Brass Chrome plated faucets and suitable drainage system complete in all respect with required height MS fabricated and Painted Angle iron frame ( Cost of frame to be paid Extra )complete in all respect of the following capacity. |
| 133 | cooling capacity 150 Ltr./Hr. and storage capacity 150 Ltrs |
| 134 | SITC of RO water system with Filteration stages = Particilate filter- Membrane life enhancer filter- sediment filter- pre carbon filter- RO membrane filter- post carbon filter. Input power rating -230V AC, 50Hz, percentage of rejection TDS-90% or better, having following features (a) Double purification by RO with ESS or latest technology with TDS indicator. (b) Spin welded RO membrane housing to prevent tempering. (c) Push fit component for leak proof performance. (d) Fully automatic operation with auto start and auto off. (e) SS/ABS construction for corrosion free lifespan. (f) Equally suitable for water from all borewells, overhead storage tanks, water tankers and even municipal taps. (g) RO membrane flushing - Auto flush@ every start, every stop and every one hour of working for one minute, complete in all respect with following capacity. |
| 135 | Purification capacity - 50LPH, duty cycle 270-500 liters/day |
| 136 | Supply & Installation of IP-20 & IK-08 , Wall mounted Double Section Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet, front sturdy sheet steel frame folded from one piece and welded with minimum 5mm toughened glass door,Vertical Mounting Rail 1.6 MM with 'U'Marking , with All round protective channel on the door aperture, lock integrated on front door, top and bottom cover with cable entry provision with gland plates, integrated side walls, 2 pair of 19\\" angles with wall mounting provision on wall. Accessories like: 1 No of 19\\" 1U Horizontal Cable manager, 1 No of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 1 No of 19\\" 1U, mountable socket strips with 5 nos of 5A universal sockets with 2 mts long power chord for supplying power to switches, fans etc along with earth continuity kit, indicator, moulded power supply cable. fixing on wall with Suitable Anchor fastner etc as required. |
| 137 | 6 U Rack with Width 600 mm & Depth 400 mm + 100 mm |
| 138 | 15 U Rack with Width 600 mm & Depth 400 mm + 100 mm |
| 139 | Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, U/UTP (Unscreened/Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by LSZH Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies ranging from 250 to 500 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. |
| 140 | Supply , Installation, Testing and Comissioning of Unmanaged Switch Plug-and-play - easy setup with no configuration or no software needed, following Port fast ethernet - 8 port 10/100/1000 MBPS auto-negotiation RJ45 ports, IEEE 802.3x flow control ,supports auto-MDI/MDIX, eliminating the need for crossover cables including making connection etc as required complete in all respect. |
| 141 | 24 Port |
| 142 | Providing & Fixing of following modular accessories, made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required. |
| 143 | RJ-45, Cat 6 computer jack with shutter |
| 144 | Supply , Installation and Testing of 4 pair, 100 Ohm impedance, Cat 6/6A /Class E/Ea patch cords should be constructed of minimum 23/24 AWG, stranded bare Copper cable with LSZH Jacket, with an enhanced performance by factory moulded RJ45 connectors with strain relief boots as per ANSI/TIA/EIA 568-C.2 suitable for Cat 6/6A application complying to latest ammendments Category 6/6A Standards, According. to TIA568C.2, ISO/IEC 11801, EN 50173, IEC 60603-7-51, EN 60603-7, IEEE 802.3an minimum requirement for 1G BASE-T to 10G BASE-T performance. Patch cords shall be straight thru cable compatible with both T568-A and T568-B wiring schemes, should support IEEE 802.3af / IEEE 802.3at for POE applications, Minimum 750 to 1000 mating cycles in plug contacts for long durability, Should support Ethernet 10GBASE-T, 1.2 Gb/s ATM, Token ring 4/16, Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP). |
| 145 | Cat 6, U/UTP (Unscreened/Un-sheilded Twisted Pair) Patch Cord |
| 146 | 1 Mtr |
| 147 | 2 Mtr |
| 148 | Supply, Drawing and OLTS Testing, of stranded OS2 Single mode (9/125 µm) glass optic fiber cable G652D as per latest ammendments of TIA/EIA 568/ISO/IEC with outer sheath, cable should be used for LAN and WAN back bones, for indoor/outdoor installations these sheathed cable be placed in existing MS/PVC /HDPE Conduits/ slotted channels with ferruling at both ends for identification complete in all respect. |
| 149 | 6 fiber |
| 150 | Supply, Installation, & Testing of 19\\" 1U Rack Mounted/ surface mounted aluminum/ CRCA powder coated, OM2 multimode glass Fiber Optic Cable Patch panel/LIU loaded with flangeless/screwable adapters for SC/LC/SN/CS type, It should have easy removable Top plate with push buttons, there should be a splice tray installed in the Patch panel/LIU which can handle the fiber cores, splice tray should be PC+ABS material, it should include accessories like mounting hardware, gormetts, heat shrink tubes/sleeves, screws, nuts to install the panel for rackmount applications as per requirement. All as per pre approved by Engineer in charge. |
| 151 | Multi Mode LIU 24 Ports |
| 152 | Supply, Installation, & Testing of Indoor duplex Singlemode patch cord (9/125 µm (OS2) made of glass fiber optic with LSZH jacket, F8 2.0x4.1 mm, yellow, singlemode G652.D (9/125 µm (OS2) Mounted on both sides with SC/LC/SN/CS type Duplex connectors in acc. with IEC 61754-20. Zirconia (ceramic) ferrule with a PC polished endface geometry, connectors should be tuned in accordance with IEC 61755-3-1 and qualified in acc. with IEC 61753-1 for category U (uncontrolled environment, duplex clip and white plastic dust cover, should comply to delta IL < 0.2 dB after 500 mating cycles, there should be an optional Visual coding, mechanical coding and lock protection on the patch cords which can be added on later stage. patch cords's performance should be acc. to IEC 61753-1 (Table A.12) as per latest ammendments of TIA/EIA 569B.3, as per requirements. |
| 153 | Single Mode Patch Cord 1 Mtr. |
| 154 | Single Mode Patch Cord 2 Mtr. |
| 155 | Supply, installation, Testing and Commissioning of 1000 base-LX/LH single mode/Multi mode fibre to 1000 base-T copper giga bit , Media Convertor complete as required complete in all respect. |
| 156 | Supply, Installation, OTDR/OLTS Testing & Fusion Splicing of Fiber OM2 Multimode Pigtail (50/125 µm) made of glass fiber optic, should be fitted at one end with any one type of single SC/LC/SN/CS type connector in acc., as per latest ammendments of TIA/EIA 569 Standard Specification as per requirments complete in all respect. |
| 157 | SITC of IP Based 2MP Dome camera: 1/2.8\\" or larger Progressive Scan CMOS Sensor with resolution: (1920 x 1080) @30 fps with a varifocal 2.8mm to 12mm lens or better. Should Support H.264, H.265, MJPEG, Quad/Triple streaming profiles, Frame rate upto 1-30 fps, IR Range - 40mtr or higher, 120dB WDR, 2DNR/3DNR, BLC. Camera should support Open standard to support ONVIF (PROFILE S, PROFILE G, PROFILE T), 1/1 Audio In/Out or better and 1/1 Alarm In/Out or better, onboard storage upto 512GB (SD card not included). The camera supports advanced Video Analytics (VA) including motion detection and alarm should be trigger on Tampering, Network disconnect, IP address conflict. CCTV should have password protection, privacy mask, IP address filtering, Metal Housing, Vandal-proof housing, IP67, IK10, DC 12V & PoE, Complete with Junction box for cable management. Operating Conditions within -20°C to 60°C or better. The MAC address of Camera/NVR must be registered in the name of OEM. Regulatory approvals include FCC, BIS/UL, CE. CCTV cameras must be BIS Registered Cyber Security Certified by STQC as per IoTSCS and meet the Essential Requirement (ER) issued by MeitY for security. The CCTV OEM should have its service/ support center in Rajasthan. |
| 158 | SITC of IP Based 2MP Bullet camera: 1/2.8\\" or larger Progressive Scan CMOS Sensor with resolution: (1920 x 1080) @30 fps with a varifocal 2.8mm to 12mm lens or better. Should Support H.264, H.265, MJPEG, Quad/Triple streaming profiles, Frame rate upto 1-30 fps, IR Range - 50mtr or higher, 120dB WDR, 2DNR/3DNR, BLC. Camera should support Open standard to support ONVIF (PROFILE S, PROFILE G, PROFILE T), 1/1 Audio In/Out or better and 1/1 Alarm In/Out or better, onboard storage upto 512GB (SD card not included). The camera supports advanced Video Analytics (VA) including motion detection and alarm should be trigger on Tampering, Network disconnect, IP address conflict. CCTV should have password protection, privacy mask, IP address filtering, Metal Housing, Vandal-proof housing, IP67, IK10, DC 12V & PoE, Complete with Junction box for cable management. Operating Conditions within -20°C to 60°C or better. The MAC address of Camera/NVR must be registered in the name of OEM. Regulatory approvals include FCC, BIS/UL, CE. CCTV cameras must be BIS Registered Cyber Security Certified by STQC as per IoTSCS and meet the Essential Requirement (ER) issued by MeitY for security. The CCTV OEM should have service/ support center in Rajasthan. |
| 159 | SITC of 16CH NVR for 2/5 MP cameras with minimum 2 SATA HDD Support with minimum 20 TB Capacity (minimum 10TB Capacity per slot - Hard Disk Not Included), minimum 1 HDMI output port, Video comression - H.265/H.264/JPEG, 1/1 Audio In/Out. NVR should support minimum 160 Mbps throughput bandwidth (80 incoming bandwidth), ONVIF compliance (Profile S/G/T). Recording resolutions up to 4K/8MP, minimum 2 USB Ports, minimum 1 Ethernet Ports (RJ-45) 10/100/1000Mbps. The system shall operate in 0°C to +50°C or better with BIS, FCC, CE . The CCTV OEM should have its service/ support center in Rajasthan. |
| 160 | SITC of 3.5\\" 4TB internal HDD for cctv recording ,capable for 24x7 operation, hdd rpm capacity shoud be 7200 rpm or better, Buffer should be 512 MB as required of following size. |
| 161 | SITC of following diagonal size professional Display, 4k Resolution, Brightness(Typ.) 440 nit and above , Contrast Ratio-2000:1 and above, Viewing Angle(H/V)-178/178, Response Time(G-to-G) 8ms, Input: RGB- Analog D-SUB, Video- HDMI 2.0 (2), HDCP- HDCP 2.2, Audio- Stereo mini Jack, USB- Only F/W upgrade, Outputs: RGB- DP1.2(Loop- out), Audio- Stereo mini Jack, External Control- RS232C(in/out), RJ45, External Sensor Detachable type(IR Ambient). Operation Hour 24/7. mounting bracket etc. as required. |
| 162 | 65 inch |
| 163 | Supply , Installation, Testing and Comissioning of Unmanaged Switch Plug-and-play - easy setup with no configuration or no software needed, following Port fast ethernet - 8 port 10/100/1000 MBPS auto-negotiation RJ45 ports, IEEE 802.3x flow control ,supports auto-MDI/MDIX, eliminating the need for crossover cables including making connection etc as required complete in all respect. |
| 164 | 8 Port |
| 165 | Supply, Installation, & Testing of Indoor duplex OM2 Multimode patch cord (50/125 µm made of glass fiber optic with LSZH jacket, 2.0x4.1 mm, Multimode ITU G 651 Mounted on both sides with SC/LC/SN/CS type Duplex connectors in acc. with IEC 61754-20. Zirconia (ceramic) ferrule with a PC polished endface geometry, connectors should be tuned in accordance with IEC 61755-3-1 and qualified in acc. with IEC 61753-1 for category U (uncontrolled environment, duplex clip and white plastic dust cover, should comply to delta IL < 0.2 dB after 500 mating cycles, there should be an optional Visual coding, mechanical coding and lock protection on the patch cords which can be added on later stage. patch cords's performance should be acc. to IEC 61753-1 (Table A.12) as per latest ammendments of TIA/EIA 569B.3, as per requirements. |
| 166 | 3 Mtr |
| 167 | Supplying, Installation, Testing and commissioning of Outdoor Wireless Access Point having features and specifications etc. as mentioned here under - WIFI 6 Certified, 1 x RJ45 console port, MG 2.5G LAN POE Port, factory reset, 4 x internal antennas, the transmission coverage of shall be minimum 80 meters in radius, AP should have transmission power minimum of 22 dBm, The AP shall provide a minimum of 29 dBm EIRP for both 2.4 GHz and 5 GHz frequencies. Field deployment shall be with EIRP as per regulatory guidelines, AP shall have dual-band Omni-directional Antenna, either internal or external. Field deployment shall be with EIRP as per the WPC guideline, WPA/WPA2/WPA3TM Personal/ Enterprise, WEP 64/128-bit, SSID broadcast disable, MAC address access control, Internal RADIUS server, SNMP, Customizable Captive Portal, Auto Channel, Works as Access Point, WDS, WDS with AP, Wireless Client, Web (HTTP), Secure Socket Layer (SSL), Traffic control, Support ATF/Fast Roaming/Band Steering, Supports enhanced security – WPA- PSK/WPA2-PSK/WPA3-PSK and RADIUS client, and Cipher negotiation, and MAC/ IP ACL for networks, IP68 water/dustproof standard, 6KV Surge Protection; 4KV ESD Protection (contact), 6KV (air), Operating ambient temperature (-5~50 °C), Grounding point support, IEC 60601-1-2 EMC Medical Electrical Equipment Testing and Certification, EN50121-1 & EN50121-4 for Wireless Application. Certifications:MTCTE, CE, FCC. Works as Standalone, Compatible with S/W & H/W Controller with additional features like - Real-Time Monitoring and Alerts, Rich Advanced Features, Centralized Device Management, Role- Based Administration, Real-Time Monitoring, VLAN and Access Control, Auto RF Management and Bandwidth Optimization, Multi-SSID and Captive Portal Authentication. OEM/Product must be on Trusted Telecom Portal of Department of Telecommunication, Government of India etc. as required. |
| 168 | Complete Server with 16GB RAM, 512Gb SHD, 1 Tb Hard Disk , Screen 22.5inch with Key Board Mouse in all respect |
| 169 | Providing, installation, testing and commissioning of ONLINE UPS SYSTEM, 3 Phase 415 V, 50 Hz with 2 hour backup SMF battery bank as per specification |
| 170 | 7.5 KVA |
| 171 | SITC of Multi-Biometric Time Aendance & Access Control System with EM lock and Rim lock. Face Capaci ty : 1500 Fingerpri nt Capacity :5000 Card Capaci ty : 10,000 Transacon Capaci ty : 200,000 Displ ay : 2.4-i nch touch Screen FacialRecognion Al Fingerpri gorithm : eSSLFace 3. nt 5 FacialRecognion Speed : <1s FacialRecognion Di stance : 0.5m to 2m Communicaon : TCP/IP, WiFi(Oponal), IP65 dust & waterproof rang Wiegand Input/Output, RS485 Operaon System : Linux Standard Funcons : ADMS, DST, Camera, 14-di git User ID, Access Level s,Groups,Hol idays,An passback,Record Query, Tamper Switch Al arm, Mulple An-Passback Ha Hardware : 1.2GHz DualCore CPU,256MB RAM/512MB Flash, 1MP Binocular Camera Adj ustabl e LED FillLi Access ControlI nterface :3rd Party El Exit Buon, Alarm output,Auxi liary I Power Supply : 12V 3A Ingress Protecon Rang : IP65 Operang Temperature : -5°C to 45°C Ope Operang Humidity : 10% to 90% RH Dimensions(L*W*D) :185*58. 5*20mm Supported Softwares in all respect as per direction of Engineer Incharge. (Access 3 year) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 28, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 07, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysOct 08, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents
Download All (ZIP) ↓
Disclaimer