Tender For special Repair To Internal Wiring Of Ge (U) Office Complex And Provn Of Deficient Exhaust Fans, Ceiling Fans And 30X Geysers In Jcos/Or Md Accn Bldg No P-138,P-175,P-176,P-177,P-113,P-105 At Safilguda Pkt-I, Old Assy Line, New Map Line Und
Tender Overview
Project Description
Tender for special Repair To Internal Wiring Of Ge (U) Office Complex And Provn Of Deficient Exhaust Fans, Ceiling Fans And 30X Geysers In Jcos/Or Md Accn Bldg No P-138,P-175,P-176,P-177,P-113,P-105 At Safilguda Pkt-I, Old Assy Line, New Map Line Under Age E/M Of Ge (S) Secunderabad.
BOQ
| Sl. No. | Item Description |
| 1 | M & L for taking down copper/aluminium point wiring (light, fan, socket, power, security lights or bulkhead) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc. complete all as specified and as directed |
| 2 | M & L r for point wiring concealed type complete all as specified with 1100 Volts grade 1.5 Sqmm PVC insulated FR-LSH unsheathed cable with multistranded copper conductor conforming to IS:694:1990 with ISI marking in and including PVC rigid conduit medium grade of size minimum 20 mm with all accessories concealed in wall / ceiling including continous earth wire 1.5 Sqmm PVC insulated FR-LS unsheathed 1100 Volts multistranded copper conductor connected to common earth and earth dolly including modular metal flush boxes concealed in walls and modular white plate covers with frame for mounting of modular switches/sockets etc complete including making good of disturbed surfaces of wall / ceiling / floor all complete all as specified and as directed(a) onelight point/ ceiling /exhaust fan point/Bell |
| 3 | (b) One three pin switch socket 6 Amps outlet on independent board complete all as specified and as directed. |
| 4 | (c) One three pin switch socket 6 Amps outlet on same board complete all as specified and as directed. |
| 5 | All as per item No 2 here in before but with cable 2.5 sqmm multi stranded copper FR-LSH wire , 1100 Volts grade, unsheathed for one 3 pin socket out let 15 amps on independent board including continuous earth wire PVC insulated 2.5 sqmm copper stranded conductor FR-LSH, 1100 Volts grade, connecting to common earth and earth dolly complete all as specified and as directed |
| 6 | All as per item No 2 here in before but with cable 4 sqmm multi stranded copper FR-LSH wire , 1100 Volts grade, unsheathed for one 3 pin socket out let 15 amps on independent board including continuous earth wire PVC insulated 4 sqmm copper stranded conductor FR-LSH, 1100 Volts grade, connecting to common earth and earth dolly complete all as specified and as directed |
| 7 | S & F in repair Modular switch 1 way 6A , 1-module complete all as specified and as directed |
| 8 | S & F in repair Modular switch 1 way 16A with indicator, 1-module complete all as specified and as directed |
| 9 | S & F in repair Modular bell push 1 way 6A with indicator, 1-module complete all as specified and as directed |
| 10 | S & F in repair Modular socket, shuttered type, 6A - 3 pin 2 -module complete all as specified and as directed |
| 11 | S & F in repair Modular socket, shuttered type, 6/16A - combined 2-module complete all as specified and directed |
| 12 | S & F 3 pin, 6 A, 250 V ceiling rose having terminal capacity 3 X 1.5 mm² IP 20 protection complete all as specified and directed |
| 13 | M&L for Bells Ding dong AC 230Volts Single pole complete all as specified and as directed. |
| 14 | S & F Electronic fan regulator Modular type suitable for BLDC fans stepped socket type, suitable to work on 230 volts complete all as specified & directed |
| 15 | S & F ing ceiling fans complete with blades,copper winding, down rods and accessories, 230 V, 1200 mm sweep. Min air delivery not less than 210 CFM with service value more than equal to (≥) 6.00, BEE Five star rated with brushless direct current motor (BLDC) white colour complete all as specified and directed |
| 16 | S & F exhaust fan, metal body AC single Phase 230V of size 300 mm sweep,RPM 1200 with, copper winding,blades,rag-bolts, and frame and louvers complete including making suitable size hole in wall for fixing of fan complete all as specified and directed |
| 17 | S & F exhaust fan made of sturdy Engineering plastic body complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 250mm sweep complete all as specified and directed |
| 18 | S & F recess mounting LED light fitting 2' x 2' of capacity 36 Watts powder coated white CRCA full glow,efficacy 120 lumen/watts rated life 50000 burning hours suitable for false ceiling pop/grid ceiling including making electrical connection from ceiling rose to light fitting complete all as specified and as directed . |
| 19 | S & F surface mounting LED light fitting 2' x 2' of capacity 36 Watts powder coated white CRCA full glow,efficacy 120 lumen/watts rated life 50000 burning hours suitable for false ceiling pop/grid ceiling including making electrical connection from ceiling rose to light fitting complete all as specified and as directed . |
| 20 | S & F 20 W surface / wall mounted LED batten light fitting aluminium extrusion input voltage range 250 V, input frequency 50 Hz, efficacy not less than 120 Lumen/Watt, rated llife 50000 Burning hours including 2 nos PVC Connector blocks electrical connection with 3 core flexible Copper conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed |
| 21 | S & F lamp holder any angle insulated body surface bakelite with back plate suitable for angle / batten fittings complete all as specified and as directed |
| 22 | S & F LED security light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant,efficacy not less than 120 lm/Watts,rated life 50000 burning hours complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection with wall mounting bracket arm OD 35 mm to 42 mm including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate size and 1.5 m long bracket, having 40 mm diameter light grade GI pipe, including GI clamps, nuts, bolts & washers with two coats of synthetic enemal paint over a coat of red oxide primer complete suitable for pop/grid false ceiling in all respect as specified and directedcomplete all as specified and directed |
| 23 | S & F Single pole and Neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps (AC Box) incl taking down existing unserviceable Distribution boards with MCB's complete all as specified and as directed. |
| 24 | S&F of sheet metal enclosure TPN DBs with 200 Amps rated bus bar of 4 way 415 volts with blank plate complete with double door incl taking down existing unserviceable Distribution boards with MCB's complete all as specified and directed |
| 25 | S & F single pole & neutral, double door, metallic distribution board 8 ways conforming to IEC 61439-3, suitable for flush / surface mounting with provision for DP MCB as incomer and SP MCBs as outgoing, incl taking down existing unserviceable Distribution boards with MCB's complete all as specified and directed |
| 26 | S&F of MCB single phase and neutral (SPN), 40 Amps, 230 Volts, connecting with lugs, complete all as specified and directed |
| 27 | S&F of MCB SP 6 to 32 Amps 'C' series complete all specified and directed |
| 28 | S&F of MCB, single pole, 40 Amps, 240 Volts, connecting with copper lugs complete all as specified and directed |
| 29 | S&F of MCB three phase and neutral (TPN), 100 Amps, 415 Volts, connecting with lugs, complete all as specified and directed |
| 30 | M & L for submain wiring using 3 runs of 6 Sq mm 1100 V grade single core FR-LSH flexible cable conforming to IS 694: 2010, having multi-drawn thin strands of electrolytic copper conductors and insulation for phase, neutral and earth continuity conductor connecting to earth dolly, colour-coded as per IS 11353: 1985, drawn in medium grade PVC recessed conduits, conforming to IS 9537 (Part- 3): 1983, of size not less than 25 mm NB, including taking down old submain wire and making good of disturbed surfaces of wall / ceiling / floor all complete as specified and directed |
| 31 | M & L r for Earthing complete with galvanized steel earth plate electrode 60cmX60cmX6mm thick, buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of plate not less' than 1.5meters below normal ground level, earth plate connected to galvanized earth lead wire 4.00 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 of MES 2009 (part I Specifications) connected to earth test point all as specified or indicated including testing on completion, including necessary excavation and earth work in any type of soil and adequate quantity of common salt & charcoal for alternate layer around the earth plate, including PCC (1:2:4) pit and 10mm thick C.I. cover with arrangement of hinge to 40x40x6mm C.I. angle iron frame, including 20mm dia G.I. pipe for watering purpose with the arrangement of funel and wire mess, including GI pipe of 15 dia for earth lead protection complete incl taking down old one complete all as specified and as directed. |
| 32 | S & F Electric water heater, storage type,vertical, single phase, electric operated, 50Hz, steel body heating element up to 2 KW capacity 25 Ltrs, BEE 5 star rated innner tank as per OEM specification with minimum 2 years warranty on over all product (inner tank ,heating element & thermostat) complete with all accessories such as safety valve, thermostate, NRV, connection piece, FRLS multistranded copper conductor cable 3 core PVC insulated, plug top 3 pin 15 Amp , 15 mm dia, brass coupler, flexible pipe suitable to withstand upto 120 °C for hot and cold water, Anchor fastener- 04 Nos of suitable size etc. complete all as specified and as directed |
| 33 | M & L Submain concealed wiring with 2 runs of single core 2.5 sqmm PVC insulated FRLSH multistranded 1100 volts grade wire, copper conductor drawn through and including non-metalic rigid PVC surface conduit and accessories of medium grade not less than 20mm dia including one run of single core 2.5 sqmm PVC insulated sheated multistranded 1100 volts grade with copper conductor cable as earth continuity conductor along with the wiring and connecting from DB to geyser point/ power point complete all as specified and as directed.Note:-(i) The wiring shall be done in proper color coding using red,yellow,blue for phases , black for neutral and green for earth (ii) Three runs of copper conductor wire, one run of PVC conduit & connected accessories shall be measured as one running meter. |
| 34 | S & F ing Modular switch 1 way 16A, 1-module including suitable size modular PVC sunken box, modular cover plate & frame etc. as required complete all as specified and as directed |
| 35 | S & F ing multipurpose 3/6 Pin Modular socket outlet 16A, 230 volts, 2-module including suitable size modular PVC sunken box, modular cover plate & frame etc as required complete all as specified and as directed |
| 36 | S&F MCB SP 20 Amps, 240 volts, 10 KA, 'C' curve MCB in the existing MCB DB complete all specified and directed |
| 37 | S & F /lay GI pipe 15 mm dia medium grade for geysers raising main & down comer connections includning complete fittings and accessories complete all as specified and as directed |
| 38 | S & F chromium plated metallic bib tap 15 mm dia complete all as specified and as directed |
| 39 | S & F 15 mm dia metallic angle stop valve for iron pipe and fixing complete all as specified and as directed |
| 40 | M & L for Point wiring complete with two runs of 1.5 Sq mm (for Phase and neutral) PVC insulated unsheathed multi stranded ,copper conductor FRLSH cable of 1100V grade drawn through and including new non metallic rigid PVC conduit medium grade, ISI marked, 20 mm bore with conduit accessories for Modular surface/ recess wiring mount on wall or fixed on ceiling/roof/truss/columns etc, including provision of branded modular PVC terminal box of suitable sizes with 1.6mm thickness including modular cover frame & box of suitable size for modular switch boards any size of modules for housing modular switches, sockets, fan regulators etc and provn of 1.5 Sqmm PVC insulated unsheathed copper conductor FRLSH cable of green colour to common earth dolly etc. for one light point controlled by one switch complete all as specified and as directed .Note (1) The wiring shall be done in proper color coding using red, yellow, blue for phases, black for neutral and green for earth.(ii) Three runs of copper conductor wire & one run of PVC conduit, shall be measured as one point |
| 41 | S & F Modular switch 1 way 6A, 1-module complete all as specified and directed Please Enable Macros to View BoQ information |
| 42 | S & F Modular switch 1 way 6A, 1-module complete all as specified and directed Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 11 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 13 daysTender Documents