Tender For Straightening Of Energy Saving Measures At S. V. Airport, Raipur.
Tender Value
15.45 Lakhs
Estimated cost
Bid Submission
15 Oct 2026
19 days left
EMD
30916
Bank guarantee accepted
Document Fee
1180
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Raipur → Chhattisgarh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Straightening Of Energy Saving Measures At S. V. Airport, Raipur.
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.Group C |
| 2 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as requiredGroup C |
| 3 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)4 way (4 + 12), Double door |
| 4 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 5 | Supplying and fixing 63 A rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 6 | Supply of 4 core X 16 Sq.mm. size aluminium conductor XLPE insulated, PVC sheathed, armoured power cable of 1.1 KV grade conforming to IS-7098 Part 1(1988) amended up to date. |
| 7 | Laying and fixing of one number PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size on wall surface asrequired.Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 8 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 9 | Supplying and making end termination with brass compression gland and aluminium lugs for 4 X 16 sq. mm of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 10 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/submain wiring/ cable as required. |
| 11 | Supply of single phase, 300mm dia. 900 RPM sweep Heavy Exhaust fan having thermal overload protection, with Louver and shutter/safety Guard from foreign objects, etc. complete as required suitable for use on 230 volts, 50 Hz, single phase, A.C. supply. |
| 12 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. (i) Upto 450mm |
| 13 | Supplying, laying,fixing, testing and commissioning of 32mm thickness closed cell elastrometric nitrile rubber of class 'O' applied by adhesive confirming to standard specifications, as per specifications and as required complete in all respect. |
| 14 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/Class -II of IS: 3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of 150mm dia sizes complete as required. |
| 15 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required |
| 16 | 50mm dia |
| 17 | 80mm dia |
| 18 | Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot / normal water circulation as specified.80mm dia |
| 19 | Providing and fixing in position industrial type pressure gauges with gun metal / brass valves complete etc. as required |
| 20 | Providing and fixing in position the mercury in glass industial type thermometers. |
| 21 | Supply, fabrication and installation of Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position including anchor fastener for any suspension from roof or wall and applying a priming coat of approved steel primer and two coats of synthetic enamel paint all complete as required. |
| 22 | Supplying and fixing of nominal 2.00mm +/- 10% thick, 1000mm wide anti-skid Antistatic Electric Insulation mats confirming to IS 15652:2006 with up to date amendments and CPRI/ERDA tested suitable for 3.3 kV installation along with adhesive sealing material and similar type of taping on sealing at joints and corners as per recommendations etc. as required. |
| 23 | Providing and fixing Polyisocyanurate insulated sandwich panels with 0.5mm GI sheet on both side , The insulated Roofing shall be 50+30mm thick PIR insulated Sandwich panels with density of more than 40 Kg/m3. The top covering on roof panels will trapezoidal Pre-coated galvanized iron sheet with crest height 30±1mm,crest width 24±1mm and pitch 200±1mm & bottom covering on roof panels shall be micro ribbing Pre-coated galvanized iron sheet. Pre-Painted Galvanized Iron Sheet shall have minimum coating of 4-5micron epoxy primer and 25micron polyester top coat on the finish surface and 7-8micron primer alkyl base on reverse. The PPGI sheet shall have plastic protective guard film of minimum 25 microns to avoid scratches during transportation & installation. Material shall be Fire retardant type including CFC free PIR pannel should be GRIHA Certified. the cost shall also inclued the required hardware accessories such as required Channel, Clamling device threaded GI sheet down rods etc. complete as per direction and satisfaction of Engineer-in-Charge. |
| 24 | DSITC of vermin and dust proof front operated floor/wall mounted type single door sprinkler system made out of 1.5 mm thick for body and all partitions with CRCA sheet of size Hight 40mm X Length 50mm X Depth 20mm and size of internal boxing as per equipment which installed inside the panel with arrangment to collect condensate water from indoor unit of split AC and store through insulated high class SS body storage tank thickness upto 0.8 mm and spray on outdoor unit of split AC after filteration with suitable size of filter, pumping with suitable size of booster pump, sensor, switch with LED lamp for provision to work at night, 3/8 inch Pipe, SMPS (adopter), 1/4 inch PVC Pipe, Pipe Tee, jointer, stopper, socket, Pipe convertor socket Sprinkler, having size 1/4 inch- 3/8 inch, Tank to pipe connector nipple, Insulation material of size 1/4 inch-3/8 inch, 1.5 sqmm wire for motor switch socket power point, ON/OFF LED indicator including drain pipe of suitable size complete as required and as per direction and satisfaction of Engineer-in-Charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 25, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 15, 2026
17:00 IST