Tender For Providing, Fixing, Testing And Commissioning Of Co2 Flooding System In Palika Kendra.
Tender Value
45.63 Lakhs
Estimated cost
Bid Submission
01 Oct 2026
4 days left
EMD
91268
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
New Delhi → Delhi
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Providing, Fixing, Testing And Commissioning Of Co2 Flooding System In Palika Kendra.
BOQ
| Sl. No. | Item Description |
| 1 | Providing, fixing, testing and commissioning of CO₂ gas cylinder of 45 kg capacity, seamless steel, manufactured as per IS: 7285-1988, duly inspected and certified by BIS (ISI) and approved by the Department of Explosives, Nagpur, complete with ISI-marked valve and painted red, including all accessories etc. complete as directed by the Fire Officer / Engineer-In-Charge. |
| 2 | Providing, fixing, testing and commissioning of following typical cylinders modular frame assembly with inbuilt locking arrangement, fabricated out of 1.6 mm thick MS square tubes, powder-coated in approved shade, complete with fixing arrangement for manifold, manifold hoses, master solenoid valve, slave solenoid valve, pressure switch, safety valve, inter-connecting hoses, NRV, etc., suitable for NFPA-12 system, including online gas weighing monitor device / weighing scale etc. complete as directed by the Fire Officer / Engineer-In-Charge. |
| 3 | a) 4 Cylinder digital weighing monitor scale. |
| 4 | Providing, fixing, testing and commissioning of CO₂ pressurized valve of approved make and quality, suitable for manual and automatic gas release etc. complete as directed by the Fire Officer / Engineer-In-Charge. |
| 5 | Providing, fixing, testing and commissioning of 2 kg capacity Nitrogen pilot cylinder, fabricated from heavy-duty seamless steel tube, complete with specially designed valve suitable for pressure gauge mounting and gun-metal rod, inclusive of all required accessories etc. complete as directed by the Fire Officer / Engineer-In-Charge. |
| 6 | Providing, fixing, testing and commissioning of 8 mm dia x 24\\" long wire-braided main header hose pipe for connection between main cylinder and manifold etc. complete as directed by the Fire Officer / Engineer-In-Charge. |
| 7 | Providing, fixing, testing and commissioning of heavy-duty wire-braided R-1 flexible pipe (20\\" length × 8 mm dia) for nozzle connection etc. complete as directed by Fire Officer / Engineer-in-Charge. |
| 8 | Providing, fixing, testing and commissioning of wire-braided flexible pipe (6 mm dia × 14\\" length) for cylinder interconnection etc. complete as directed by Fire Officer / Engineer-in-Charge. |
| 9 | Providing, fixing, testing and commissioning of gun-metal lever for manual gas release of approved make and quality etc. complete as directed by Fire Officer / Engineer-in-Charge. |
| 10 | Providing, fixing, testing and commissioning of gun-metal non-return valve of standard size and approved make etc. complete as directed by Fire Officer / Engineer-in-Charge. |
| 11 | Providing, fixing, testing and commissioning of CO₂ discharge nozzle made of gun metal, specially designed to prevent high-velocity CO₂ discharge and resultant system unbalance, with nozzle drilled to the required orifice size as per design flow rate, including all required fittings and accessories etc. complete as directed by the Fire Officer / Engineer-in-Charge. |
| 12 | Providing, fixing, testing and commissioningof ASTM Schedule-40 pipes of following diameters for system interconnection etc. complete as directed by Fire Officer / Engineer-in-Charge. |
| 13 | a) 25mm dia |
| 14 | Providing, fixing, testing and commissioning of manifold made of ASTM A106 pipe complete with brackets and clamping arrangement, including all required fittings and accessories etc. complete as directed by Fire Officer / Engineer-in-Charge. |
| 15 | Providing and fixing in position industrial type pressure gauges with gun metal / brass valves complete etc. as required. |
| 16 | Providing, fixing, testing and commissioning commissioning of solenoid valve 24V DC etc. complete all as specified and as directed by Fire officer/ Engineer-in-change |
| 17 | Providing, fixing, testing and commissioning of Two zone Gas Release Panel facility to connect Manual abort/release switches.The panel shall provide potential free contacts for first knock, second knock, trouble/fault status. The panel shall be complete with red colour. Housing, monitored power supply unit, Battery charger & batteries Gas release panel shall be capable to connect main & stand by electrical actuators. All gas release panel shall have main/ stand by selector switch. |
| 18 | Providing, fixing, testing & commissioning of ceiling/ wall mounted hooter cum flashe. |
| 19 | Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required |
| 20 | Providing, fixing, testing & commissioning manual Gas abort switch compete with all mounting accessories, complete with MS power coated junction Box for mooting on surface, cable lugs at Ends, cable compression glands, cable tags and ferruling. |
| 21 | Providing, fixing, testing & commissioning manual Gas release switch compete with all mounting accessories, complete with MS power coated junction Box for mooting on surface, cable lugs at Ends, cable compression glands, cable tags and ferruling. |
| 22 | Providing, fixing, testing & commissioning of circuit integrity cable Fire suppression, power and signaling cable 4 corex x 1.5 mm, multistranded AT copper, Fire retardant, zero halogen low smoke armored cable, RED in colour, laid on surface with GI saddle-spacers every 0.30 meters. complete with GI junction box, lugs, cable compressing lands, cable. |
| 23 | Providing, fixing, testing & commissioning relay control module |
| 24 | Providing, fixing, testing & commissioning heat detector MS junction box Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 24, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 01, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysOct 01, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 4 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender