Tender For Provn Of Dedicated Power Supply Alongwith Allied Works At Sarabhai Block Under Ge (Mcte) Mhow.
Tender Value
43.72 Lakhs
Estimated cost
Bid Submission
15 Oct 2026
11 days left
EMD
87500
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Indore → Madhya Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provn Of Dedicated Power Supply Alongwith Allied Works At Sarabhai Block Under Ge (Mcte) Mhow.
BOQ
| Sl. No. | Item Description |
| 1 | Supply, installation,commsssioning, & testing copper wound distribution Transformer step down, outdoor type, plinth mounted maximum total losses inaccoradance to energy efficient level three as per IS 1180 amended no IV (Part-I) of 11/0.433 KV capacity 315 KVA, AC 3 phase, 50 Hz oil immersed naturally cooled delta connected on primery side (11 KV HV side) Dyn -11 with neutral brought out on secondary side with tapping at + 2.5% + 5% off load tap changer gear in steps of 2.5 % including initial oil fill to appropriate level & all standard fitting all as per IS 1180 amended no IV Pt-1 March 2021 complete all as specified and directed. The unit rate for each transformer includes the cost of following accessories /fittings: |
| 2 | (a) Rating and terminal marking plates, non-detachable.(b) Earthing terminals with lugs -02 No's(c) Lifting lugs for main tank and toop cover(d) Thermometer pocket with cap. Along with dial type thermometer -01 No(e) Externally hand operated OFF circuit tap, changing devices with locking arrangement.(f) Oil conservator tank with fitting hole, drain plug prismatic oil level gauge.(g) Silica gel dehydrating breather charged with silica gel.(h) Top filter valve with plug Note-: (i) Transformer shall be inspected by inspecting officer nominated by accepting officer for testing and inspection at factory before dispatch. (ii) Precommissning shall be done by SEI. (iii) All cost deemed to be included in quoted rated for arrangment of test.No extra cost will be paid for any type of testing as directed by Engr-in Charge. |
| 3 | Supply, install and testing air break gang operated triple pole switch mechanically operated mounted on 12 insulators with dio fuse complete with operating mechanism work out from ground level including locking arrangement and steel frame up to current rating 200 Amps with expulsion fuse single pole element as required rupturing capacity. The switch having rating 11 KV including electrical connection and testing complete all as specified and directed. |
| 4 | Supply and erection of three piece metal oxide lightning arrestor suitable for 11 kV continuous operating voltage (3 phase) with rated voltage 12 kV (rms) with nominal discharge current rating of 65 KA and complete with galvanised clamping arrangements, GI bolts, nuts, washers etc. complete all as specified and directed. |
| 5 | M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed. |
| 6 | Supply, laying and testing in trenches/through pipes/ducts or on poles Cross linked polyethylene insulated (XLPE) armoured cable with aluminium conductor, 11 KV `E’, 3 core IS-7098 of cross sectional area 95 Sqmm complete all as specified and directed.Note :-(i) Excavation, earth work, cable joint, sand cushioning, protection cover and pipe shall be measured and paid for separately under respective items of this schedule. |
| 7 | Supplying, laying and testing LT underground cable of size 185 sqmm 4.0 core heavy duty, 1100 Volts, XLPE insulated and sheathed, armoured with multi-stranded aluminium conductor cable conforming to latest IS , laid in trenches/ducts duly protected in galvanised steel pipe of suitable sizes all bare conductor of cable duly insulated 1.1 KV grade heat shrinkable sleeve including cable gland and lugging etc at both ends complete all as specified and directed. |
| 8 | Excavating in trenches not exceeding 1.5 meter wide and not exceeding 1.5 metre deep and getting out in soft/loose soil complete all as specified and directed. |
| 9 | Returning filling in foundation / trenches including spreading leveling, watering and well ramming in layers not exceeding 25cm thick in soil complete all as specified and directed by Engineer-in-Charge. |
| 10 | Removing surplus soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed. |
| 11 | Sand cushioning for under ground cable with locally available sand for protection of cable 8cm before laying cable and 15cm deep over the cable including spreading and consolidations, complete all as specified and directed.Note :- Punned thickness will be measured and paid. |
| 12 | Supply and laying un-reinforced precast concrete cable cover class HVP type 2 with peak size 450 mm x 180 mm x 40 mm complete all as specified and directed by Engineer-in-Charge. |
| 13 | Supply and laying sub class 'B' bricks laid dry and flat across the length of cable for protection of cable including taking down old /broken bricks complete all as specified and directed. |
| 14 | M&L for 100 mm bore GI tubing 'light grade' with all necessary fittings laid in trenches/under road crossing/fixed on pole/wall/under floor including suitable mild steel FI clamps of required size complete all as specified and directed. |
| 15 | M&L for providing under ground boring using mechanical pneumatic drilling equipment / manually for passing electric cables through by providing/ supply HDPE pipe of 100mm dia heavy quality, pressure rating 6 kg/cm2 under the existing bituminous/WBM road/PCC hard standings, depth range not more than 1.5mtr deep and making good the distrubed surfaces is to match with its existing specifications complete all as specified and directed.Note : Any damage to the existing cables/water pipes/structures shall be made good by the contractor at his own expense. |
| 16 | Supply, installation, commissioning and testing of factory made LT panel Board confirm standards of IS/IEC 61439-1 & IEC 61439-2 of suitable size out door type (double door) 415 Volts, dust proof,vermin proof made out of CRCA sheet 3.15 mm thick duly compartmentalized inside panel with 2.00 mm thick CRCA sheet , to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading, suitable size(1.5 times of incoming switch gear capacity) Copper bus bar and mild steel cable glands for each cable to make it weather and vermin proof. double door hinged type, both side openable, air fins for ventilation, panel shall be mounted on ISMC Chanel of size (50 x 50 x 6 mm) & duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs suitable long each duly grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20 mm graded stone aggregate) incl all connections incoming / out going complete all as specified and comprising of following accessories :- |
| 17 | INCOMING (i) MCCB 4 pole 415 V 630 Amps 50 KA, Ics=100% Icu , with Microprocessor- 01 No OUTGOING (i) MCCB 4 pole 415 V 250 Amps 36 KA, Ics=100% Icu , Thermal Adjustable and magnetic adjustable -2 Nos (ii) MCCB 4 pole 415 V 160 Amps 36 KA, Ics=100% Icu , Thermal Adjustable and magnetic adjustable -3 Nos (iii) Multi function(VAF + PF) panel meter,digital type with 3 row display of legrand make (Cat No: 414979) or equivalent with suitable CTs - 1 No (iv) Phase indicator(RYB), LED type- set of three Note for Item No. 15 :- (1) All incoming & outgoing feeders to be marked with aluminium name plates duly rivetted on the front inner door of the feeder pillar.(2) All the cable entry / exit will be through bottom only, duly glanded with single compression type brass cable gland of suitable size. Cost of end termination of cable shall deemed to be included in the cost of feeder pillar.(3) All the inner / outer doors should have locking facility through castle locks(4) Cost of all civil work for brick pedestal, duly plastered, shall deemed to be included in the unit rate quoted, no separate payment shall be allowed for this.(5) The dimention of Panel Board as mentioned above is tentative & minimum. If it is required to be increased to accomodate the switchgears and maintaining the gaps as per IE Rules, it will be increased as per requirement without any extra cost to the department.(6) The Panel Board should be designed in such a way that adequete workable space is made available inside every compartments.(7) The drawing of the Panel Board shall have to be got approved by Garrison Engineer before starting of fabrication process. |
| 18 | M&L for earthing complete with using galvanized mild steel earth plate (electrode) 600 mm x 600 mmx 6 mm thick buried directly in ground, earth pit not less than 2.25 mtr deep below ground level with top edge of the earth plate not less than 1.50 m below ground level and earth plate surrounded with adequate quantity of charcoal dust mixed with salt to be packed thickness of 15 cm all round the plate using 32X6 mm GI earth strip as earth lead moulded and rivetted to earth plate at one end and connected to main equipment at switch/control board at another end, GI earth lead protected in and including 15 mm dia GI ‘medium grade’ pipe from upper end of earth plate upto equipment with & including 20 mm dia bore GI pipe ‘medium grade’ as water pipe from earth chamber to upper edge of the earth plate, GI funnel with wire mesh fixed on water pipe and provision of PCC 1:2:4 type B1(using 20 mm graded stone agg) as in pits chamber and RCC pit cover 50 mm thick of precast RCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) as per electrical plate No.3 of SSR Part-I 2010 and testing on completion all as specified and directed.(LA-02, LT Panel-32) |
| 19 | Construction of Plinth of size 2.0 mx 2.0 mx1.5 m for transformer, using 100 mm thick PCC 1:4:8 type D-2 as in lean concrete, flyash brick masonry in CM 1:6, the top of the plinth shall consist of 100 mm thick PCC 1:2:4 type B-1suitable reinforced (using 20 mm graded stone aggregates) over 75 mm thick PCC 1:4:8 type D-2 over compacted moorum filling, 10 mm thick rendering in CM 1:4 on brick surface with and including 25 cm thick stone aggregates of size 12.5 mm all around upto and including 1.5 m from the edge of the plinth including the Iron Gate and fencing with angle iron post complete all as specified and directed by the Engineer-in-charge. |
| 20 | M&L for spreading and levelling evenly (any thickness) hard core using 40mm graded stone aggregate at sub-station complete all as specified & directed. |
| 21 | S&F Solar LED light fitting 24 Watt high efficiency All-in One Solar street light mono Crystal , Lithium Ferro Phosphate battery with in-built BMS technology ,MPPT Solar Charger controller and aluminium extruded body with PIR motion sensor automatically control the dimming and brightness of light,battery capacity 30AH,IP65,temp 5700k complete all as specified and directed. |
| 22 | Supply and fixing cable route indicator, made of MS sheet of size 200 mm x 150 mm x 3 mm thick, spot welded with angle iron of size 40 x 40 x 5 mm thick, 750 mm long embedded in PCC (1:2:4) type B-2( using 40mm graded crushed stone aggregate) block 30cm x 30cm x 40cm in ground including one coat of synthetic enamel black paint over one coat of red oxide zinc chrome primer and writing with white paint showing size of cable LT complete all as specified & directed . Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 24, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 15, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 11 daysOct 17, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 13 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender