Tender For Maintenance And Repair Of Electric Fittings Fixtures, Wiring And Connected Items At Airmen Mess & Billets, Hq Wac Building, Hq Wac (U) Bldg, Ge Office, Fire Section And Smq Area Of Wac Under Ge (Af) Subroto Park
Tender Overview
Project Description
Tender for Maintenance And Repair Of Electric Fittings Fixtures, Wiring And Connected Items At Airmen Mess & Billets, Hq Wac Building, Hq Wac (U) Bldg, Ge Office, Fire Section And Smq Area Of Wac Under Ge (Af) Subroto Park
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 06-Oct-2026 | Corrigendum_01 | BOQ | 14-Oct-2026 |
| 2 | 14-Oct-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 21-Oct-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Taking down carefully copper/aluminium point wiring light ,fan, light fittings,socket or power complete, such as switches, ceiling roses, pendents, regulators, sockets etc.removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditioned separately) and making good disturbed surface of walls, floors etc. complete all as specified and directed by Engineer-in-Charge. |
| 2 | M&L for point wiring using approved colour coding as per IS, with stranded copper conductor 1.5 Sq.mm (nominal area), single core, PVC insulated and unsheathed stranded cable 1100 volts grade (FRLS), ISI-694 marked drawn through in and including heavy duty, PVC concealed conduit after cutting, chasing the wall etc and making good of disturbed surface, including all accessories etc, heavy duty ISI marked, including powder coated mild steel sunken boxes concealed in walls with 3 mm thick laminated hylam sheet top cover for fixing switches, switch socket outlets etc including PVC insulated stranded copper conductor 1.5 Sqmm (nominal area) (FRLSH) single core cables as earth continuity conductor to common earth and connecting to earth dolly. (Note- Piano switch and sockets will be measured and paid separately) but for one light point/fan point controlled by one SP switch. complete all as specified and directed. |
| 3 | All as per item No-2 above but for one bell point controlled by one bell push. |
| 4 | All as per item No-2 above but for one 3 pin socket out let, 6 Amps on same board |
| 5 | All as per item No-2 above but for one 3 pin socket out let, 6 Amps on Independent board |
| 6 | All as per item No 2 above but with 2.5 Sq mm cable for Independent board one 3 pin 15 Amps socket outlet including Single core 2.5 Sq mm PVC insulated copper conductor unsheathed 1100 v grade IS -694 FRLS cable for continuous earth wire 2.5 sqmm FRLS (Only one 15 Amp point will be in one circuit) |
| 7 | S & F Modular switch 1 way 6A, 1 modules suitable for 240 volt AC Complete all as specified and directed by Engineer-in-Charge. |
| 8 | S & F Modular Socket, 6A -3 pin combined 2 module, suitable for 240 volt AC Complete all as specified and directed by Engineer-in-Charge. |
| 9 | S & F Modular switch 1 way 16A ,1 module suitable for 240 Volt AC complete all as specified and directed by Engr-in- Charge. |
| 10 | S & F Modular Socket, 16A -3 pin combined 2 module, suitable for 240 volt AC Complete all as specified and directed by Engineer-in-Charge. |
| 11 | S & F in replacement Electronic modular Fan Regulator rotary flush step type 120 watt, 2 module , 240 volt 50 Hz AC complete |
| 12 | S & F Bell push Modular flush type 6 Amps suitable for 240 volt AC Complete all as specified and directed by Engineer-in-Charge. |
| 13 | M&L for point wiring for one light point/fan point controlled by one SP switch using approved colour coding as per IS, with stranded copper conductor 1.5 Sq.mm (nominal area), single core, PVC insulated and unsheathed stranded cable 1100 volts grade (FRLS), ISI-694 marked drawn through in and including heavy duty, PVC concealed conduit after cutting, chasing the wall etc and making good of disturbed surface, including all accessories etc, heavy duty ISI marked, including powder coated mild steel sunken boxes concealed in walls with 3 mm thick laminated hylam sheet top cover for fixing switches, switch socket outlets etc including PVC insulated stranded copper conductor 1.5 Sqmm (nominal area) (FRLSH) single core cables as earth continuity conductor to common earth and connecting to earth dolly. (Note- Piano switch and sockets will be measured and paid separately) complete all as specified and directed. |
| 14 | All as per item No 13 but for one light point controlled by two way SP switches |
| 15 | All as per item No 13 but for one bell point controlled by one bell push |
| 16 | All as per item No-13 above but for one 3 pin socket outlet, 6 Amps on same board with the cable 1.5 Sqmm size. |
| 17 | All as per item No-13 above but for one 3 pin socket outlet, 6 Amps on Independent board with the cable 1.5 Sqmm size. |
| 18 | All as per item No 13 above but with 2.5 Sq mm cable for Independent board one 3 pin 15 Amps socket outlet including single core 2.5 Sq mm PVC insulated copper conductor unsheathed 1100 v grade IS -694 FR LS cable for continuous earth wire of required size. |
| 19 | M&L for point wiring for one light point/fan point controlled by one SP switch using approved colour coding as per IS, with stranded copper conductor 1.5 Sq.mm (nominal area), single core, PVC insulated and unsheathed stranded cable 1100 volts grade (FRLSH), ISI-694 marked drawn through in existing steel/ PVC concealed conduit and making good of disturbed surface, , excluding mild steel sunken boxes but includes 3 mm thick laminated hylam sheet top cover for fixing switches, switch socket outlets etc including PVC insulated stranded copper conductor 1.5 Sqmm (nominal area) (FRLSH) single core cables as earth continuity conductor to common earth and connecting to earth dolly. complete all as specified and directed.(Note- Piano switch and sockets will be measured and paid separately) |
| 20 | All as per item No-19 above but for one light point controlled by two Way SP switches |
| 21 | All as per item No-19 above but for one bell point controlled by one No bell push |
| 22 | All as per item No-19 above but for one 3 pin socket out let, 6 Amps on same board with the cable 1.5 Sqmm size. |
| 23 | All as per item No-19 above but for one 3 pin socket out let, 6 Amps on Independent board with the cable 1.5 Sqmm size. |
| 24 | All as per item No 19 above but with 2.5 Sq mm cable for Independent board one 3 pin 15 Amps socket outlet including single core 2.5 Sq mm PVC insulated copper conductor unsheathed 1100 v grade IS -694 FRLSH cable for continuous earth wire of required size. |
| 25 | M&L for point wiring using approved colour coding as per IS, with stranded copper conductor 1.5 Sqmm (nominal cross-sectional area), single core, PVC insulated and unsheathed stranded cable 1100 volts grade (FRLSH) conforming to IS-694 with multistranded copper conductor drawn thorugh and including PVC casing and capping /surface conduit complete with all fittings and accessories, fixed to walls/ceiling, including sunk type pressed steel terminal boxes 60mm deep, conforming to IS-5133 (Part-I) with 3 mm thick plastic laminated sheet cover (ISI marked) for mounting switches/regulator etc and including 1.50 Sqmm (nominal area) , PVC insulated unsheathed multistranded FRLSH copper conductor cable 1100 volts grade, single core for earth continuity conductor connected to common earth dolly for light/fan/bell point controlled by one switch and making good disturbed surfaces of walls, floors etc for light/fan/bell point complete all as specified and directed.Note- Piano switch and sockets will be measured and paid seperately) |
| 26 | All as per Item No 25 herein before but one 3 pin socket outlet, 5 Amps, independent board. |
| 27 | All as per Item No 25 herein before but one three pin switch socket 5 Amps plug point on same board |
| 28 | All as per item No 25 herein before but point wiring with 2.5 Sqmm single core multi stranded copper conductor FRLSH, for one three pin socket 15 Amps on independant board controlled by one 15 Amps Switch including continuous earth wire PVC insulated 2.5 Sqmm single core multi stranded copper conductor connected to common earth dolly. |
| 29 | S & F Switch piano 5 amps flush type single pole one way suitable for 240 volt AC Complete all as specified and directed by Engineer-in-Charge. |
| 30 | S & F Socket outlet flush type 3 pin 6 amps suitable for 240 volt AC Complete all as specified and directed by Engineer-in-Charge. |
| 31 | S & F Switch piano 5 Amps flush type single pole two way suitable for 240 volt AC complete all as specified and directed. |
| 32 | S & F Switch piano 16 amps flush type single pole one way suitable for 240 volt AC Complete all as specified and directed by Engineer-in-Charge. |
| 33 | S & F Socket outlet 2 in 1, 5 pin 16 amps flush type suitable for 240 volt AC Complete all as specified and directed by Engineer-in-Charge. |
| 34 | S & F Bell push flush type 5 Amps suitable for 240 volt complete all as specified and directed. |
| 35 | Supply and fixing ding dong bell AC 230 volt single pole complete all as specified and directed |
| 36 | Supply and fixing of ceiling roses, surface bakelite 65x50mm 2 or 3 terminals , PVC/Polycarbonate, isolated body fixed on PVC round block complete all as specified and directed by Engineer-In- Charge. |
| 37 | Taking down old unsv VTPN DB of any size complete all as specified and directed. |
| 38 | Supply and fixing DB VTPN 12 ways with provision for FP MCB/isolator/ RCCB/ MCCB etc 'A' Frame as incomer and SP/TP as outgoing double door IP 54 complete prewired including 250 Amp bus bar etc suitable for operation on 415 volts 50 Hz AC supply, suitable for TP incomer MCCB of 125/160 Amps including necessary provision for inserting the DBs in wall by cutting the brick/stone masonry etc and making good of disturbed surfaces to match with existing colour of wall complete all as specified and as directed by Engineer-in-Charge including MCCB 4 pole 125 Amps capacity rup capacity 10 KA (Ics= 100% Icu) complete all as specified and directed. Note :- MCB SP/TP shall be measured and paid separately. Cat Part No DHDLVDRWAOFO12 of Havells, BVL312DDBQ of L&T and 5077-53 of Legrand |
| 39 | All as per item no 38.00 but TPN 8 way. Cat Part No DHDLVDRWAOFO08 of Havells, BVL308DDBQ of L&T and 5077-52 of Legrand |
| 40 | All as per item no 38.00 but TPN 6 way. Cat Part No BVL306DDBQ of L&T and 5077-51 of Legrand |
| 41 | All as per item no 38.00 but TPN 4 way. Cat Part No DHDLVDRBATFO04 of Havells, BVL304DDBQ of L&T and 5077-50 of Legrand |
| 42 | Taking down old unsv MCB SPN DB of any size complete all as specified and directed. |
| 43 | M & L MCB distribution board with bus bar 200 A, neutral link, earth bar made out of CRCA mild steel sheet with double door category of protection type IP- 42 factory made with tinned copper 200 Amps rated bus bar suitable for MCB SPN 04 way 230 Volts, horizontal type ,concealed in wall such that front cover shall be seen flush with the wall surface complete all as specified and directed. Note :- MCB SP/SPN shall be measured and paid separately. |
| 44 | All as per item no 43 but SPN 8 way |
| 45 | All as per item no 43 but SPN 12 way |
| 46 | S&F in replacement of MCCB 200 Amps FP 415 volts 3 phase 50 HZ ,Ics=100%Icu, breaking capacity 36 KA complete all as specified and directed. |
| 47 | S&F in replacement of MCCB 160 Amps FP 415 volts 3 phase 50 HZ ,Ics=100%Icu, breaking capacity 36 KA complete all as specified and directed. |
| 48 | S&F in replacement of MCCB 125 Amps FP 415 volts 3 phase 50 HZ, ,Ics=100%Icu,breaking capacity 16 KA complete all as specified and directed. |
| 49 | S&F as in repair MCB SP 6 to 32 Amps 10 KA, 240 volt 'B' Series complete all as specified and directed by engineer-in-charge. |
| 50 | S&F as in repair MCB SP 40 Amps 10 KA, 240 volt 'B' Series complete all as specified and directed by engineer-in-charge. |
| 51 | S&F as in repair MCB SPN 40 Amps 10 KA, 240 volt 50 Hz 'B' Series complete all as specified and directed by engineer-in-charge. |
| 52 | S&F as in repair MCB TP 25-63 Amps 10 KA, 415 volt 50 Hz 'B' Series complete all as specified and directed by engineer-in-charge. |
| 53 | Taking down unserviceable submain wiring of alluminium of any size cable including batten/conduit complete etc and making good disturbed surfaces complete all as specified and directed. |
| 54 | M & L for in submain wiring with two run of 10.0 sqmm single core PVC insulated but unsheathed FRLS cable of specified size of multistranded copper conductor 1100 volts grade IS:694 marked and one run of 10.0 sqmm PVC insulated but unsheathed FRLS cable for earth continuty conductor drawn through and under suitable size of rigid non metallic PVC conduit , medium grade, ISI marked ( not less than 25 mm dia) complete with all acessories and fittings all laid/fixed concealed in wall and surface conduit on ceiling portion only complete all as specified and directed.(Note:- 3 Runs of 10.0 Sqmm single core cable and one run of PVC conduit will be used as one unit for payment purpose). |
| 55 | All as per item no 54 above but for 6.0 sqmm wire(Note:- 3 Runs of 6.00 Sqmm single core cable and one run of PVC conduit will be used as one unit for payment purpose) |
| 56 | All as per item no 54 above but for 4.0 sqmm wire(Note:- 3 Runs of 4.0 Sqmm single core cable and one run of PVC conduit will be used as one unit for payment purpose) |
| 57 | M & L for in submain wiring with four run of 10.0 sqmm single core PVC insulated but unsheathed FRLS cable of specified size of multistranded copper conductor 1100 volts grade IS:694 marked and one run of 10.0 sqmm PVC insulated but unsheathed FRLS cable for earth continuty conductor drawn through and under suitable size of rigid non metallic PVC conduit , medium grade, ISI marked ( not less than 25 mm dia) complete with all acessories and fittings all laid/fixed concealed in wall and surface conduit on ceiling portion only complete all as specified and directed.(Note:- 5 Runs of 10.0 Sqmm and one run of PVC conduit will be used as one unit for payment purpose). |
| 58 | All as per item no 57 above but for 6.0 sqmm wire(Note:- 5 Runs of 6.0 Sqmm single core cable and one run of PVC conduit will be used as one unit for payment purpose) |
| 59 | Supply installation commissioning testing as in repair of earthing in any kind of soil/strata complete with copper bonded earthing electrode chemical earthing system outer electrode dia 25 mm and 3 mtr long tightly filled with crystalline conductor mixture 250 microns copper coated along with bag of back bill compound 50 kg buried directly in the ground (earth pit not less than 2.25 meter deep below ground level) connected to and including galvanized iron strip 4 mm dia as earth lead by means of GI bolts,nuts,check nuts and washers and connecting earthing test point ,including CI covers ,frame and PCC (1:3:6) type C-2 using 20 mm graded stone aggergate as in earthing pit with CI cover and framing including necessary earth work etc complete all as specified and directed. Note- PCC chamber shall be constructed at least one meter away from the building shall be provided in slanting manner.Note- PCC cover pit shall be precast of RCC 1:2:4 type B-I 80 mm thick reinforced with XPM weighting not less than 4 kg (sqm in liew of CI) |
| 60 | Material and labour as in repair for galvanised iron strip 25 X 4 mm with saddles and fixing screws and connected as per site requirement comlete all as specified and as directed by Engineer-in-Charge. |
| 61 | All as per item no 60 but 4mm dia GI wire |
| 62 | Taking down of light fittings of any wattage complete all as specified and directed. |
| 63 | Supply and fixing wall mounted LED batten extruded aluminium heat shrink provided for efficient heat dissipation and integrated electronic driver ,20 watt LED fitting with 100 lumen/watt, 6000K , 230 Volts, diffused optics ,etc complete with all accessories , connecting up with twin core twisted flexible copper conductor cable from ceiling rose to fitting, and testing complete all as specified and directed by the Engineer- In- Charge. Note - Cat Part No CCS-103-20-65-SL-DP-NWH of Crompton, Dawn AL 20W CW PD of Bajaj and LUMILINEPLUSPROBS20WLED865SPCSSIND of Havells. |
| 64 | Supply and fixing wall mounted LED batten extruded aluminium heat shrink provided for efficient heat dissipation and integrated electronic driver ,10 watt LED fitting with 100 lumen/watt, 6000K , 230 Volts, diffused optics ,etc complete with all accessories , connecting up with twin core twisted flexible copper conductor cable from ceiling rose to fitting, and testing complete all as specified and directed by the Engineer- In- Charge.- Note - Cat Part No CCS-103-10-65-SL-DP-NWH of Crompton, Dawn AL 10W CW PD of Bajaj and LUMILINEPLUSPROBS10WLED865SPCSSIND of Havells. |
| 65 | Supply and fixing wall mounted LED bulk head fittings, 10 watt, , 230 Volts, diffused optics ,etc complete with all accessories , connecting up with twin core twisted flexible copper conductor cable from ceiling rose to fitting, and testing complete all as specified and directed by the Engineer-In- Charge. Note - Cat Part No TIS-303-10-57-SL-DP-NWHof Crompton, BLPB 10W CW PD of Bajaj and RUGBYGENXFTS10WLED865SSYMBOPC of Havells. Please Enable Macros to View BoQ information |
| 66 | Supply and fixing wall mounted LED bulk head fittings, 10 watt, , 230 Volts, diffused optics ,etc complete with all accessories , connecting up with twin core twisted flexible copper conductor cable from ceiling rose to fitting, and testing complete all as specified and directed by the Engineer-In- Charge. Note - Cat Part No TIS-303-10-57-SL-DP-NWHof Crompton, BLPB 10W CW PD of Bajaj and RUGBYGENXFTS10WLED865SSYMBOPC of Havells. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 3 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 3 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender