Project Description

Tender for Repair/Maintenance & Replacement Of Lt Oh Line And, Ug Cables, Pole Painting & Other Connected Electrical At Charri C And Dharamshala Mil Stn Under Ge Pal Ur

BOQ

Name of Work:- Repair/maintenance & Replacement of LT OH line and, UG Cables, pole painting & other connected electrical at Charri c and Dharamshala Mil stn under GE pal ur
Sl. No. Item Description
1Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth and getting out in any type of soil complete all as specified and directed.
2All as per Srl No 1 above but depth exceeding 1.5 metre but not exceeding 3.0 metre complete all as specified and directed.
3Returning filling in including ,spreading ,levelling, watering and well ramming in layers not exc 25cm thick each complete all as specified and directed
4Removing excavated material to a distance not exc 50m and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and directed
5M&L in trenches for sand cushioning for under ground cables complete all as specified and directed.
6Material and labour for sub class (B* brick, old size, brick covering laid dry, flat transversally along the length of cable on sand cushioning, with width equal to the length of the brick complete all as specified and directed.
7Material & Labour PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as in bottom of pit in bed concrete of poles complete all as specified.
8Material & Labour PCC 1:3:6 type C2 ( using 40mm graded stone aggregate) as in bottom foundation of poles and stay etc complete all as specified and directed.
9Material & Labour PCC 1:3:6 type C1 (using 20mm graded stone aggregate) as in coping for Poles etc complete all as specified and directed.
10Supply, laying & replacement of existing unserviceable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volt grade of cross sectional area 240 Sqmm 3.5 Core complete all as specified and directed.
11All as per Srl No 10 above but size 150 sqmm 3.5 core complete all as specified and directed.
12All as per Srl No 10 Above but size 120 sqmm 3.5 core complete all as specified and directed.
13All as per Srl No 10 above but size 95 sqmm 3.5 core complete all as specified and directed.
14All as per Srl No 10 above but size 70 sqmm 3.5 core complete all as specified and directed.
15All as per Srl No 10 above but size 50 sqmm 3.5 core complete all as specified and directed.
16All as per Srl No 10 above but size 35 sqmm 3.5 core complete all as specified and directed.
17All as per Srl No 10 above but size 25 sqmm 3.5 core complete all as specified and directed.
18All as per Srl No 10 above but size 16 sqmm 3.5/4.0 core complete all as specified and directed.
19Supply and fixing GI tubing light grade 40 mm bore for passing through cables under the floor, along the wall or along the pole complete all as specified and directed.
20Supply and fixing GI tubing light grade 50 mm bore for passing through cables under the floor, along the wall or along the pole complete all as specified and directed.
21Supply and fixing GI tubing light grade 80 mm bore for passing through cables under the floor, along the wall or along the pole complete all as specified and directed.
22Supply & fixed 1.1 KV, LT UG XLPE cable end terminal joints (heat shrinkable) indoor/outdoor type along with Pole, panel etc and testing after jointing cable of size 185-300 sqmm complete all as specified and directed.
23Supply & fixed UG LT PVC insulated armoured heavy duty cable end terminal joints (heat shrinkable) indoor/outdoor type of along Pole etc suitable for aluminium conductor cable and testing after jointing cable of size 70-150 sqmm complete all as specified and directed.
24Supply & fixed UG LT PVC insulated armoured heavy duty cable end terminal joints (heat shrinkable) indoor/outdoor type of along Pole etc suitable for aluminium conductor cable and testing after jointing cable of size 25-50sqmm complete all as specified and directed.
25Dismantling of unserviceable/perished ACSR conductor of any size from LT over head lines and removing the same from site complete all as specified and directed.
26S & F aluminium conductor steel reinforced (ACSR) any size as directed on overhead LT electric line with stretching and tensioning with reqd span sag and binding the conductor with pin/shackle insulator with aluminium binding wire not less than 2mm dia complete all as specified and directed.
27Stretching / restring only ACSR conductor in position on LT over head lines of any size, type, span length with permissible span sag and binding with pin/shackle insulator with new aluminium binding wire not less than 2mm dia complete all as specified and directed.
28Dismantling of rusted/corroded cross arms fixed on LT poles and removing unserviceable cross arms from site complete all as specified and directed.
29Fixing only old serviceable cross arms obtained from Sch 'A' ser Item No 28 above with providing new bolts, nuts and washers as required including painting with one coat of aluminium paint after preparation of old surfacecomplete all as specified and directed.
30S&F cross arms made out of mild steel channel or angle section of reqd size and shape including clamp back plate with bolts, nuts, washers drilled for insulator bolts, welding, binding cold or hot in any shape or size and directed and painted with two coats of aluminum paint over a coat of red oxide primer after necessary preparation of surfaces complete all as specified and directed.
31Galvanized steel wire 4mm dia for earth wire on LT /HTpoles stretched without links, bends and binding with wire and fabrication of cradles hexagonal/rectangular guards etc complete all as specified including taking down old wire of any type shape and size and removing from site.complete all as specified and directed.
32Dismantling and taking down of existing unserviceable Wood/PCC/steel tubular pole any size complete all as specified and directed.
33Supply and fixing for steel tubular swaged poles complete with cast iron base plate, finial each tapper plug, bolts, nuts and screws as specified type 410 SP-31 (9.00 metres long), erected to truly vertical position including one coat of red oxide primer and two coats of aluminium paint and making 30cm wide strips 5 Nos with white and black paint alternately on external surface above PCC benching/ground level including making pole identification number and figure with synthetic enamel paint of Ist quality and painting with bituminous paint internally and externally for portion embedded in PCC. , complete all as specified and as directed.
34M&L for painting of LT panel outdoor/indoor off sizes removing existing old paint with the help of sand/emery paper etc. Preparing surfaces externally including cleaning etc. Applying externally one coat synthetic enamel paint including cleaning and surface dressing upto 25cm depth around 1 mtr of the panels complete all as specified and directed.
35Painting to existing steel tubular poles 09 mtr long including cross arms, clamps etc. with two coats of aluminum paint on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with yellow and black paint alternatively on external surface above PCC copping including preparation of old painted surfaces by scraping complete all as specified and directed.
36Dismantling of old unserviceable stay assembly including stay wire complete with necessary demolition of concrete excavation and earth work as required and removing the same from site complete all as specified and directed.
37S&F stay assembly complete with all accessories and stay clamps, stay wire all as shown in electrical plate No 1 of SSR Part I with using stay rod of 16 mm dia 1.8 mtr long and stay plate galvanized steel 23cmx23 cmx6mm thick, incl Loop type insulator, concrete foundation and stay wire, stay clamps complete all as specified and directed.
38Dismantling of unserviceable insulators of any size and type from LT overhead lines complete all as specified and directed.
39S&F shackle type porcelain vitreous white, brown or green insulator of size 75mm height, 90mm dia (maximum) including mild steel straps of section 31mmx3mm, washers, 12mm dia insulator bolt and nut suitable for working pressure 1100 volts grade complete all as specified and directed.
40Fixing only old serviceable shackle type insulators obtained from Sch 'A' ser Item No 39 Above complete all as specified and directed.
41M & L for cutting of existing road/ floor/ plinth/drain for taking outlaying of UG cable through GI pipe including necessary earth work excavation and making good to match with existing surface complete all as specified with PCC 1:3:6 type C2 by (using 20mm graded stone aggregate) complete all as specified and directed.
42S&F PVC line separator and spacer of 10 mm dia fixed on LT over head line of 4/3/2 span including taking down old unserviceable one complete all as specified and directed.
43M & L for MCCB 4 Pole, 415 Volt Adjustable type,400 Amp with breaking capacity 36 KA, with extended terminal & suitable size of cable lugs and taking down old one complete all as specified and directed.
44All as per item 43 above but MCCB, 350 Amp with breaking capacity 36 KA, complete all as specified and directed.
45All as per item 43 above but MCCB, 250 Amp with breaking capacity 36 KA, complete all as specified and directed.
46All as per item 43 above but MCCB, 200 Amp with breaking capacity 36 KA, complete all as specified and directed.
47All as per item 43 above but MCCB, 160 Amp complete all as specified and directed.
48Cutting /trimming tree branches along the over head HT/LT lines up to 2.0 mtr from each location as directed by Engr in Charge, including necessary excavation of earth and work and dismantling of PCC works complete all as specified and directed.
49Taking down 9 mtr long steel tubular pole from existing position to re-fixing to another location as directed by Engr in Charge, including necessary excavation of earth and work and dismantling of PCC works complete all as specified and directed. Note : Excavation and PCC work in new location shall be measured and paid separately.
50M/L for earthing with galvanized steel earth plate 60cm X 60cm X 6 mm thick, buried directly in ground(earth pit not less than 2.25 mtr deep below ground level) with the top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanized earth lead wire 4.0 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth plate surrounded by packed layers of coal dust and common salt 15 cm thick all around top and bottom all as shown in electrical plate No 5 connected to pole all as directed including PCC (1: 3:6) type C1 earth pit, cast iron pit cover, funnel with wire mesh,watering pipe 20mm dia light grade,1.5mtr long and 15mm bore light grade from earth plate to pole upto the height of 3mtr as protection pipe fixed with 40x3mm flat iron clamps and GI wire connected to earth wire on OHL and testing on completion including excavation earth work and disposal of surplus soils including takingout old earthing complete all as specified and directed.
51All as per item no 50 but galvanised iron strip 32x6 mm as earthing lead,complete all as specified and directed. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57694351
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE Ref. Documents
LAST DATE 08-10-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/Maintenance & Replacement Of Lt Oh Line And, Ug Cables, Pole Painting & Other Connected Electrical At Charri C And Dharamshala Mil Stn Under Ge Pal Ur
Basic Detail
Tender No GEP-66/2026-27
Bidding Type Tender
Location
City Kangra
State Himachal Pradesh
Key Dates
Publish Date 24 Sep 2026
Submission Date 08 Oct 2026
Open Date 12 Oct 2026
Finance
Tender Value Ref. Documents
Tender Fee 500
EMD 40000
Exemption Not Available
Document List
2e5b0589-8a29-4141-af5a-9d2aa13294ca.html
BOQ_886664.xls
td.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 24, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Oct 08, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 6 days
Oct 12, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 10 days

Tender Documents

Download All (ZIP) ↓
html

2e5b0589-8a29-4141-af5a-9d2aa13294ca.html

xls

BOQ_886664.xls

pdf

td.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders