Tender For Construction Of New Building For Chc Thumpamon Pathanamthitta
Tender Value
3.19 Crore
Estimated cost
Bid Submission
05 Oct 2026
6 days left
EMD
1 Lakhs
Bank guarantee accepted
Document Fee
8850
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Pathanamthitta → Kerala
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Construction Of New Building For Chc Thumpamon Pathanamthitta
BOQ
| Sl. No. | Item Description |
| 1 | CIVIL WORKS |
| 2 | SITE CLEARANCE |
| 3 | Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared |
| 4 | EARTH WORK EXCAVATION |
| 5 | Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil |
| 6 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 7 | Filling with contractor's own earth ( excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m as per direction of site Engineer-in-charge |
| 8 | PLAIN CEMENT CONCRETE |
| 9 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mmnominal size derived from natural sources) |
| 10 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering -All work above plinth level up to floor five level1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size) |
| 11 | RCC WORK |
| 12 | Providing and laying in position ready mixed concrete manufactured in BIS certified plants and transported to site of work in transit mixer for a lead of 25kms having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work including pumping of RMC transit mixer to site of laying, excluding the cost of centering, shuttering, finishing and reinforcement including cost of admixtures in recommended proportions as per IS9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer in charge. Minimum cement content shall satisfy exposure conditions but not less than 330kg/m3. (The entire process such as mixing, transit, pumping, laying and consolidation etc shall be completed within 2hrs. The quality of concrete such as strength and workability is to ensured at site by conducting appropriate tests by the site Engineer concerned. Charges if any conducting tests etc is to be born by the contractor)M25 grade of concrete |
| 13 | Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more |
| 14 | Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo - Mechanically Treated bars of grade Fe-500D or more |
| 15 | Providing concrete grade 1:5:10 upto floor V level to cast Dummy columns to cover the projecting reinforcement of columns just below finished floors (for a length equal to lap length in compression but not less than 24d) to lap reinforcement for future vertical extension of columns for subsequent floors so as to prevent rusting/corrosion of bars due to environmental influences. It should be ensured that the columns so casted will cover the full height of projecting bars and no part shall left uncovered. The concrete in Dummy columns so casted will be demolished prior to vertical extension of columns is susequent floors |
| 16 | Reinforced cement concrete work in beams, suspended floors, roofs, having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 17 | Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical localtion in load application areas that accommodates multi directional seismic movement without stress to it's components. System shall consist of metal profiles with a universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions. The Self – centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in-Charge . (Material shall confirm to ASTM 6063).Floor Joint of 150 mm gap. |
| 18 | Providing and fixing of expansion joint system related with wall joint (internal/ external) location as per drawings and direction of Engineer-In-Charge. The joints shall be of extruded aluminum base members, self aligning / centering arrangement and support plates as per ASTM B221-02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement. (Material shall confirm to ASTM 6063).Wall Joint of 100 mm gap. |
| 19 | FORM WORK |
| 20 | Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete |
| 21 | Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 22 | Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform |
| 23 | Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers |
| 24 | Centering and shuttering including strutting, etc. and removal of form for:Stairs, (excluding landings ) except spiral - staircases) |
| 25 | Centering and shuttering including strutting, etc. and removal of form for: Edges of slabs and breaks in floors and wallsUnder 20 cm wide |
| 26 | Centering and shuttering including strutting, etc. and removal of form for:Weather shade, Chajjas, corbels etc., including edges |
| 27 | Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts |
| 28 | MASONRY WORKS |
| 29 | Solid block masonry using pre cast solid blocks ( factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 part 1 of 1979 for foundation and plinth with thickness 20 cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc complete |
| 30 | Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement: 6 coarse sand) etccomplete. |
| 31 | Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x10 cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level for 10 cm thick wall in : CM 1:6 ( 1 cement : 6 coarse sand) including cost of scaffolding complete |
| 32 | PLASTERING |
| 33 | 12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand) |
| 34 | 6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand) |
| 35 | 20 mm cement plaster of mix:1:4 (1 cement : 4 fine sand) |
| 36 | STEEL WORK |
| 37 | Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.) |
| 38 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Hot finished welded type tubes |
| 39 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+0.05%), total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling/self tapping screws of size (5.5x55mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 40 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters.80x1.25 mm M.S. laths with 1.25 mm thick top cover |
| 41 | DOORS AND WINDOWS |
| 42 | Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately), using good quality Anjili wood /jack wood |
| 43 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of I st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters.35 mm thick Fixing with hinges of required size and necessary screws (Note: Hinges and necessary screws hall be paid separately) |
| 44 | Extra for providing ISI marked Stainless Steel butt hinges instead of M.S. pressed butt hinges bright finished of required size with necessary screws. ( Shutter area to be measured) |
| 45 | Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width form 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete. |
| 46 | Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:200x10 mm |
| 47 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:125 mm |
| 48 | Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Twin rubber stopper |
| 49 | Providing and fixing bright finished 100 mm mortice lock with 6 levers without pair of handles of approved quality for aluminium door, with necessary screws etc complete as per direction of Engineer- in- charge. |
| 50 | Providing and fixing factory made uPVC door frame made of uPVC extruded sections having an overall dimension as below (tolerance ±1 mm), with wall thickness 2.0mm (±0.2 mm), corners of the door frame to be jointed with galvanized brackets and stainless steel screws, joints mitred and plastic welded. The hinge side vertical of the frames reinforced by galvanized M.S. tube of size 19 x 19 mm and 1 mm (± 0.1 mm) wall thickness and 3 nos. stainless steel hinges fixed to the frame complete as per manufacturer's specification and direction of Engineer-in-chargeExtruded section profile size 48x40 mm |
| 51 | Providing and fixing to existing door frames24 mm thick factory made PVC door shutters made of styles and rails of a uPVC hollow section of size 59x24 mm and wall thickness 2 mm (± 0.2 mm) with inbuilt edging on both sides. The styles and rails mitred and joint at the corners by means of M.S. galvanised/plastic brackets of size 75x220 mm having wall thickness 1.0 mm and stainless steel screws. The styles of the shutter reinforced by inserting galvanised M.S. tube of size 20x20 mm and 1 mm (± 0.1 mm) wall thickness. The lock rail made up of 'H' section, a uPVC hollow section of size 100x24 mm and 2 mm (± 0.2 mm) wall thickness,fixed to the shutter styles by means of plastic/galvanised M.S. 'U' cleats. The shutter frame filled with a uPVC multi-chambered single panel of size not less than 620 mm, having over all thickness of 20 mm and 1 mm (± 0.1 mm) wall thickness. The panels filled vertically |
| 52 | Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double acting hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge ( Door handle, lock and stopper etc to be paid separately) |
| 53 | Providing and installing in position PROPRIETARY FIRE DUCT DOORS of approved make Tata Pravesh or equivalent with Metal frame filled with Rockwool. The shutters shall be of Pressed Metal shutter with or without Vision panels finished with approved Powder coated as per the detail drawings & manufacturers specifications. The fire ratings shall be as called for and confirming to BIS standards as per the detail drawings & manufacturers specifications. This includes providing and fixing all brush finished iron mongery like locks, handles, tower bolts, door closer etc of Geze/Dorma as indicated in the detail drawing, and confirming to BIS standards as per the detail drawings & manufacturers specifications. This includes providing and fixing all brush finished iron mongery like locks, handles, tower bolts, door closer etc of Geze/Dorma as indicated in the detail drawing. Typical Uninsulated Door specifications 120Mins. Un Insulated fire door as per IS 3614 - Powder coated Pressed galvanized steel confirming to IS 277 with the following specification. Recommended fire door shall be tested to IS 3614 part 2/ISO 834-1 Part 1/BS 476 Part 20 & 22, CBRI/Spectra, for maximum rating of 120mins, in latched /unlatched condition (if used with deadbolts and pull handles). Labelled fire doors shall be with fire rated hardware and vision panel (if any) all as a complete assembly. Manufacturer test certificate shall cover sizes of all doors supplied, deviation in sheet thickness other than what is mentioned in the BOQ are not allowed. Door frame must be single rebate grooved profile of size 143 x 58mm made out of 1.60mm (16gauge) minimum thick galvanized steel sheet. Frames shall be mitered only. Frames shall be field assembled with self tabs. Bolted & butted joints are not acceptable. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frame should be filled with Mineral wool/ Fire rated PUF as recommended by the manufacturer or engineer in charge. Door leaf shall be minimum 46mm thick fully flush double skin door, Un-insulated with or without vision lite. Door leaf shall be manufactured from 1.20mm (18guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware of make Geze/Dorma. The infill material shall be resin bonded honeycomb core. The edges should be interlocked with a bending radius of 1.4mm, without any tack welding on edges. Vision lite wherever applicable should be 6mm clear borosilicate fire rated glass of make Saint Gobain/ Schott as per manufacturers recommendation with a clip-on arrangement. Door and frames shall be finished Pure Polyester Powder coated and shall have passed minimum 500 hours of salt spray test.Rate shall include supply and installation of frame and shutter as a complete assembly including hardware. Fire Door of size 1.2X2.1m with Metal frame of size 143x58mm with pressed metal single leaf shutter of size 46mm finished with Powder coated of approved colour and shade as per the Project Consultants approval with 2 Hours Fire rating. Rate of providing ironmongery as mentioned/recommended by manufacturer/engineer in charge. All fittings are of Brushed steel finish of Geze or approved make as per detail drawing. Ball bearing butt hinge, SS304, of size 100 x 75 x 3mm with screws in SSS, Panic Hardware, Door Closer, SSS finish, Vision Panel. |
| 54 | Supply of SS corner lock for toughened glass door of 12mm thick with weight upto 200kg |
| 55 | Supply of stainless steel handle for toughened glass door, H- type of size 450 mm and 25 mm dia with satin finish of reputed make . |
| 56 | Providing and fixing 1 mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer.Using M.S. angels 40x40x6 mm for diagonal braces |
| 57 | Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to openings/ wooden frames with rawl plugs screws etc |
| 58 | TILE WORKS |
| 59 | Providing and laying vitrified floor tiles-Size of Tile 600 x 600 mm (Thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. |
| 60 | Providing and laying Vitrified tiles -Size of Tile 600x600 mm. (Thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. |
| 61 | Chequered terrazo tiles 22 mm thick with graded marble chips of size up to 6 mm in floors, jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and polishing complete, on 20 mm thick bed of cement mortar 1:4 ( 1 cement : 4 coarse sand):Dark shade pigment using ordinary cement |
| 62 | Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm |
| 63 | Providing and laying Vitrified tiles in floor in 600*600mm (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. Glazed Vitrified tiles Matt/Antiskid finish of size Size of Tile 600 x 600 mm |
| 64 | Providing and fixing first-quality vitrified glazed wall tiles of approved make and size 300 × 600 mm, as approved by the Engineer-in-Charge, in skirting, step risers, and dado areas. The tiles shall be laid over a 12 mm thick cement mortar bed in the proportion of 1:3 (1 cement : 3 coarse sand). Joints shall be filled using grey cement slurry at the rate of 3.3 kg per sqm, and finished with white cement pointing mixed with matching pigment, complete in all respects. |
| 65 | cement concrete work for screed concrete in buiding with the mix of :1:1.5:3( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) |
| 66 | ALUMINIUM WORKS |
| 67 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately): For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron) |
| 68 | For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 69 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 4.0 mm thickness (weight not less than 10kg/sqm) |
| 70 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:75 mm |
| 71 | Providing and fixing glazing in door, window, ventilator shutters and partitions etc. with EPDM rubber /neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): toughened glass of 6 mm thickness. |
| 72 | PAINTING WORKS |
| 73 | Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work |
| 74 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of special primer applied @ 0.75 ltr /10sqm |
| 75 | Finishing walls with water proofing cement paint of required shade:New work (Two or more coats applied @ 3.84 kg/10 sqm) |
| 76 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work |
| 77 | PLUMBING AND SANITARY FITTINGS |
| 78 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 10Kgf/cm2 - External work - Exposed on wall |
| 79 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS: 893115 mm nominal bore |
| 80 | Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:W.C. pan with ISI marked white solid plastic seat and lid |
| 81 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tap |
| 82 | Flexible pipe40 mm dia |
| 83 | Providing and fixing PTMT Waste Coupling for wash basin and sink, of approved quality and colour.Waste coupling 31 mm dia of 79 mm length and 62 mm breadth weighing not less than 45 gms |
| 84 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete:20 mm nominal bore |
| 85 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank :ISI 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 86 | Providing and fixing PTMT extension nipple for water thank pipe, fittings of approved quality and colour .20 mm nominal bore, weighing not less than 40 gms |
| 87 | Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2 |
| 88 | Providing and fixing PVC pipes including fixing the pipe with clamps/ clips/ at 1.00 m spacing . This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 110 mm dia 6 Kgf/cm2 - External work- Exposed on wall |
| 89 | Providing and fixing CP Square gratings complete as per direction of engineer in charge |
| 90 | Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge. |
| 91 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 25 mm pipe 12 kgf/cm2 |
| 92 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 32 mm pipe 6Kgf/cm2 |
| 93 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 94 | Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gms |
| 95 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fitting arrangement of approved quality and colour450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm. weighing not less than 170 gms |
| 96 | Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer- in- Charge. Concealed work, including cutting chases and making good the wall etc. 15 mm pipe 12 Kgf/ cm2 |
| 97 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.15 mm nominal dia pipes |
| 98 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.20 mm nominal dia pipes |
| 99 | Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110 mm dia Elbow |
| 100 | Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement- 110 mm dia Bend |
| 101 | Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes including jointing with PVC solvent cement 110x110x110 mm dia Tee |
| 102 | Providing and fixing PVC moulded fittings /accessories for Rigid PVC pipes, including jointing with PVC solvent cement -110 mm dia Vent cowl |
| 103 | Providing and fixing white vitreous china laboratory sink with C.I brackets, C.P. brass chain with rubber plug 40 mm C.P brass waste and 40 mm C.P. brass trap with necessary C.P. brass unions complete, including painting of fittings and brackets, cutting and making good the wall wherever required:Size 450x300x150 mm |
| 104 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I. clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required:One urinal basin with 5 litre white P.V.C. automatic flushing cistern |
| 105 | Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in Charge and finished smooth.White Agaria Marble Stone |
| 106 | Supplying and placing of 5000 Litre 1mm thick stainless steel water tank of 1750mm dia , 2600mm height, Stainless steel mounted stand around 180kg and grade of ASTM A240 gr.304/ SS316 BA/2B as per the direction of Engineer in-charge. The rate inclusive of all the transportation, Steel stand support, loading and unloading charges, fixing charges, Labour charges, etc. Nothing shall be additionally paid in this item |
| 107 | Making soak pit 2.5 m diameter 3.0 metre deep with 45 x 45 cm dry brick honey comb shaft with bricks and S.W. drain pipe 100 mm diameter, 1.8 m long complete as per standard design.With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 108 | SIGNAGES |
| 109 | Design, providing and fixing Digital Printed vinyl signage boards with transparent 3mm acrylic Sheet with 4 nos. SS Studs of Size 16\\" x 10\\". Complete as per the per the direction of Engineer in charge. |
| 110 | NAME BOARD ACP SHEET WITH MULTIWOOD LETTERING :Design, Supplying and fixing Name Board as per the technical specifications given -1 Inch GI pipe frame (16Guage) for Frame (Size proportional), Primer Paint & Black Painted Pipes for Frame.,5mm ACP sheets (Aluminum Composite Panel) for Box area, 18mm thick Multi wood Lettering for Name Board as approved by Engineer in charge. For Measurement purpose, only area of ACP sheet to be measured. |
| 111 | ELECTRICAL WORKS |
| 112 | POINT WIRING |
| 113 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group B |
| 114 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C |
| 115 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C |
| 116 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required |
| 117 | Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Independent plug - Short point |
| 118 | CIRCUIT WIRING |
| 119 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire |
| 120 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 121 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 122 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 123 | SWITCH , SOCKET AND METAL BOXES |
| 124 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 125 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet |
| 126 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 127 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet |
| 128 | Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A SP switch with indicator |
| 129 | Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket |
| 130 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.TV antenna socket outlet |
| 131 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm) |
| 132 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 133 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm) |
| 134 | Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )2 module moulded plastic box on surface |
| 135 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.1 or 2 Module |
| 136 | Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface |
| 137 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module |
| 138 | Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )6 module moulded plastic box on surface |
| 139 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.6 Module |
| 140 | Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 141 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 142 | DB,ENCLOSURE AND ITS ACCESSORIES |
| 143 | Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/TP MCB as outgoing (IP 42/43) |
| 144 | Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/TP MCB as outgoing (IP 42/43) |
| 145 | Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43) |
| 146 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way, Double door |
| 147 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 148 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 149 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker with overcurrent protection (RCBO), having a sensitivity current upto 100 mA in the existing MCB DB complete with connections,testing and commissioning etc. as required. 25A-40A, 4P, 100mA |
| 150 | Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole |
| 151 | Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps |
| 152 | Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole |
| 153 | Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 154 | Supplying and fixing FP CRCA sheet steel enclosure with provision to mount MCB/Isolator/ RCCB/RCBO and other modular devices on surface/ recess complete with connections, testing and commissioning etc. as required. |
| 155 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25A DP Isolator complete with connections, testing and commissioning etc. as required. |
| 156 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 157 | PANELS |
| 158 | SMDB-1 (8 WAY) - Supply, installation, Testing and Commissioning of factory fabricated OEM 415 V 50 Hz 4 way complying to IEC 61439 part 1 & 2. The Enclosure shall be IP42 with cable end box, cable alley, pre wire meter chamber with all meters & indicating lamps, Aluminium bus bar, neutral link, DIN bar with all accessories etc, complete with necessary control wiring and protection of control shall be with DIN rail mounted 2A SP MCB. Doors shall be earthed as per prevailing standards. The main earth bus shall be of suitable size copper. All copper joints shall be tinned. Knock outs of proper diameter shall be provided on gland plates. The height of the operating handle of switch gear shall be minimum 300 mm and maximum upto 1800mm from the finished floor level complete as per the directions of engineer in charge. Incomer -1 no. 160 A 36 kA TP MCCB, Outgoing: 3 Nos 63A TP 25 kA MCCB, 2 Nos 32A TP 25kA MCCB, 1 No 25A TP 25 kA MCCB. |
| 159 | CABLE SUPPLY AND LAYING |
| 160 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 120 sq mm |
| 161 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredaluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp |
| 162 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredaluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp |
| 163 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredaluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 10 sq mm with factory made clamp |
| 164 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 10 sq mm with factory made clamp |
| 165 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredaluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 6 sq mm with factory made clamp |
| 166 | CABLE TERMINATION |
| 167 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm) |
| 168 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm) |
| 169 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm) |
| 170 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 10 sq. mm (22mm) |
| 171 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm) |
| 172 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm) |
| 173 | CABLE TRAY |
| 174 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections,joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 225 mm width X 50 mm depth X 1.6 mm thickness |
| 175 | Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.225 mm width X 50 mm depth X 1.6 mm thickness |
| 176 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 225 mm width X 50 mm depth X 1.6 mm thickness |
| 177 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm width X 50 mm depth X 1.6 mm thickness |
| 178 | Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150mm width X 50 mm depth X 1.6 mm thickness |
| 179 | EARTHING PROTECTION |
| 180 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc.(but without charcoal/ coke and salt) as required |
| 181 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.75 mm copper conductor (6 SWG) |
| 182 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG) |
| 183 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 184 | Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required. |
| 185 | LIGHT AND FAN FIXTURES |
| 186 | SITC of 4 feet surface/suspended mounted LED batten type luminaire with a power consumption not more than 20 W, luminaire lumen output of 2200 lumens, luminaire efficacy > 110 lm/W with an operating voltage range from 140 V - 270 V. The luminaire shall have a sleek design with extruded aluminium section, white CRCA housing with optically efficient poly carbonate diffuser to provide uniform illumination and wider light distribution. The luminaire shall have a CCT of 4000K /6500 K, CRI > 80, power factor >0.95, SDCM < 5, THD <10%. The luminaire shall be EMI/ EMC compliant and shall have an internal surge protection of 3 kV with 50,000 burning hours as per L70B50 criteria. The luminaire and driver shall be BIS approved and test certificates of LM79 and LM80 reports from NABL. including all accessories necessary as required to complete installation. |
| 187 | SITC of 2 feet surface/suspended mounted LED batten type luminaire with a power consumption not more than 10 W, luminaire lumen output of 1100 lumens, luminaire efficacy > 110 lm/W with an operating voltage range from 140 V - 270 V. The luminaire shall have a sleek design with extruded aluminum section, white CRCA housing with optically efficient poly carbonate diffuser to provide uniform illumination and wider light distribution. The luminaire shall have a CCT of 4000K/6500 K, CRI > 80, power factor >0.95, SDCM < 5, THD <10%. The luminaire shall be EMI/ EMC compliant and shall have an internal surge protection of 3 kV with 50,000 burning hours as per L70B50 criteria. The luminaire and driver shall be BIS approved and test certificates of LM79 and LM80 reports from NABL accredited labs. The luminaire shall have flicker content <5% and shall have high and low cut off with auto restart feature, including all accessories necessary as required to complete installation. |
| 188 | SITC of 10W LED BULKHEAD LIGHT fixture , System efficacy>=100 lm/W and system lumen output not less than 1000 lm. , driver with minimum 2.50 KV internal surge protection with electronic drive system, power factor >0.95, THD<10%, rated life of 50,000 hours at L70 with a CRI > 80, SDCM<5 and CCT in between 4000K to 5700K. ANSI rated LEDs from reputed makes should be provided and including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. all necessary accessories as required for the light fixture.LM79, LM80, type test certificate & BIS certificate shall be submitted, Luminaire/Drive shall be BIS approved of same make |
| 189 | Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 190 | Supplying and fixing of required length 32 mm dia G.I. Pipe (light class) including painting etc. as required. |
| 191 | Supply, installation, testing and commissioning of 1200 mm sweep BEE-5 star rated ceiling fan with brushless direct current motor (BLDC) , class of insulation B , 3 no:s blades , 30 cm long down rod , 2no:s canopies, shackle kit, safety rope , copper winding, power factor not less than .9, service value (CM/M/W) minimum 6.00, Air delivery minimum 210 cum/min,350 RPM (tolerance as per IS :374-2019, THD less than 10% remote or electronic regulator unit for speed control and all remaining accesories including safety pin, nut and bolts , washers, temperature rise equal to 75 deg celsius ( maximum) , insulation resistance more than 2 Megaohm , suitable for 230V,50 Hz, single phase AC supply , earthing etc., complete as required: |
| 192 | SITC of 450mm sweep Wall fan having speed control, oscillation control at bottom as suitable for operation on single phase 230 volt AC supply complete with continuous duty motor and all accessories including mounting as required for complete installation. |
| 193 | SITC of 250mm sweep Exhaust Fan, 900rpm light duty exhaust fan shutter type white colour, 9" or 10" star rated as per BEE, with its all accessories including mounting as required for complete installation. |
| 194 | FAN CLAMP |
| 195 | Providing and fixing M.S. fan clamp type I or II of 16 mm dia M.S. bar, bent to shape with hooked ends in R.C.C. slabs or beams during laying, including painting the exposed portion of loop, all as per standard design complete. |
| 196 | Supply installation, testing and commissioning of following three phase to three phase UPS with battery backup, indoor (IP20) in stand alone configuration, true online double conversion DSP based UPS system, with min 30 min backup battery with, input pf>.9, less input current consumption, IGBT rectifier and IGBT inverter. It shall be 100% generator compatible with efficiency > 90% and output power factor > 0.8 and including all accessories etc as required. The UPS system shall be with manual maintenance bypass switch facility. The system shall comply to IEC /EN 62040-1 and relevant IS standard and.The acoustic noise of the system should be less than 58dB. The system shall comply to IEC /EN 62040-1, EN/IEC 62040-2, EN/IEC 62040-3 and relevant IS standard. 10kVA UPS - 1 Nos, Battery Circuit Breaker-1 nos, Battery Required nos. of SMF for providing 30 Minutes Backup and Battery Accessories like battery rack, interconnecting cables etc. |
| 197 | PUMP SET |
| 198 | SITC of 3 HP Pure Copper Winding Domestic/ Industrial Three Phase Self Priming Monoblock Pump Discharge Range minimum 10.7 lps |
| 199 | S & F Motor starters of the following ratingsThree phase DOL starters for 0.25HP to 7.5 HP motor |
| 200 | Design, Manufacture, Installation, Testing and Commissioning of gearless electric traction type elevator of the following types and capacities suitable for operation on 415 V, 50 Hz, three phase AC supply with Variable Voltage and Variable Frequency (VVVF) drive for the main drive motor as well as door opening motor which comply with power quality requirements as per the latest version of IEEE 519 with electromagnetic brake system, correction drive to next level,,simple operation/ simplex full selective collective operation with/ without attendant, operating control panel with luminous buttons, overload warning indicator, battery operated alarm bell, LED type emergency lamp, intercom suitable for hook-up to EPABX (wiring for the intercom shall be terminated near to the main control panel), infrared ray curtains to the full height of the door, protections for reverse power, loss of phase & overload etc., limit switches, over speed governor, fireman?s switch at the ground floor etc. Car body shall be made of 304 grade SS with hairline finish, flooring with 2.50 mm fluted SS, with centre/ side opening doors, hand rails on 3 sides, mirror on the rear side, digital car position indicators in the car and at all landings with UP/DOWN directions, control panel with braille markings, occupancy sensor operated LED lighting in the car to maintain at least 150 lux and ventilating fan, ARD with battery etc. The landing doors shall be made of the same material as of the car body with fire rating as per current Standards. The installation shall include necessary scaffolding, all required minor civil works, construction of buffer blocks with springs, supply and fixing all supporting steel structures, architraves with 16 mm granite/ large format ceramic tile of approved size and pattern, all required electrical works including wiring inside the shaft and providing necessary light fittings, receptacles etc., supply and fixing necessary control panels and controls as per Standards, all power and control wirings encased in metal/ PVC conduits/ troughs etc. The electrical work shall be done in conformity with NEC 2023 and other relevant Standards. The manufacture and installation of the lifts shall be in compliance with the latest versions of IS 14665, IS 17900, IS 17106 and other relevant Standards. The efficiency of the lift shall be class A according to IS 17515. All certificates/ documents to prove the compliance shall be submitted on completion of work Machine Room Less (MRL) type 20 passenger (1360 kg) bed lift having a speed of 1 m/s in the available lift shaft of size 3100 mm (D) x 2400 mm (W) with a total travel distance of 10 m with 2 stops and 2 openings on the same side, minimum door opening size 1200 mm (W) x 2000 mm (W) with stretcher impact protection on 3 sides. |
| 201 | LIFT PANEL :Fabrication, supply, erection, testing and commissioning of floor or wall mounting dust and vermin proof, cubicle type, front operated MV panel board as per IS 8623 - CPRI Certified made out of 16 SWG thick CRCA sheet (7 tank treatment) fully compartmentalized complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel including all components as shown in the schematic drawing. The panel shall be with Top/bottom entry to receive incoming & outgoing. Providing all connections and interconnections as required and providing all accessories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided.Incomer - 125A 16kA TM based MCCB , 100A 433V, 25kA best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc. complete as required. Multifunction meter having multiline LED display with following parameters -Phase wise instantaneous and Average values–Voltage, Current, Power Factor, Phase wise instantaneous and Average values–Active Power, Reactive Power lead & lag, Apparent Power, Import & Export Cumulative values– Active Energy, Reactive Energy lead & lag, Apparent Energy, PF for 3 phases and average, Instantaneous Frequency, Total Harmonics Distortion – Phase wise Voltage and Phase wise Current - 1 Set RYB phase indicating LED lamps with control fuses and switches - 1 set. Outgoings: 63A 100mA 4P RCBO - 1 nos. , 25A 30mA DP RCBO - 1 nos., 6A SP MCB- 3Nos |
| 202 | SPLIT AC |
| 203 | Supply, Installation, Testing and Commissioning of 1.0TR BEE 3 STAR rated INVERTER-Type Air-Cooled Hi-Wall Split-Type Air Conditioners, complete with Indoor Unit (IDU), Outdoor Unit (ODU), surface/concealed copper refrigerant piping with insulation (closed-cell elastomeric nitrile rubber tubular pipe section) up to 3 meters (IDU to ODU), copper power cable up to 3.5 meters (IDU to ODU), including drain pipe, R-32/R-410A/R-407C green refrigerant, wireless remote control, suitable for working between 180–260V with low & high voltage cutoff and 50 Hz, singlephase AC supply, capable of performing cooling, dehumidification, and air circulation of the following capacity with scroll/rotary compressor—the system shall be able to deliver 100% of the rated capacity up to 42°C. The unit must be able to operate up to 50°C (outdoor ambient temperature). WARRANTY: The system must include a MINIMUM 5-year Original Equipment Manufacturer (OEM) warranty for PCB, 10-year warranty on compressor, and 1-year warranty for the total machine. Warranty Certificate to be submitted for approval. Approved Make : Hitachi, Daikin, Toshiba, Trane, O-General, Mitsubishi Electric, Voltas, Bluestar, Carrier |
| 204 | Supply, Installation, Testing and Commissioning of 1.5TR BEE 3 STAR rated INVERTER-Type Air-Cooled Hi-Wall Split-Type Air Conditioners, complete with Indoor Unit (IDU), Outdoor Unit (ODU), surface/concealed copper refrigerant piping with insulation (closed-cell elastomeric nitrile rubber tubular pipe section) up to 3 meters (IDU to ODU), copper power cable up to 3.5 meters (IDU to ODU), including drain pipe, R-32/R-410A/R-407C green refrigerant, wireless remote control, suitable for working between 180–260V with low & high voltage cutoff and 50 Hz, singlephase AC supply, capable of performing cooling, dehumidification, and air circulation of the following capacity with scroll/rotary compressor—the system shall be able to deliver 100% of the rated capacity up to 42°C. The unit must be able to operate up to 50°C (outdoor ambient temperature). WARRANTY: The system must include a MINIMUM 5-year Original Equipment Manufacturer (OEM) warranty for PCB, 10-year warranty on compressor, and 1-year warranty for the total machine. Warranty Certificate to be submitted for approval. Approved Make : Hitachi, Daikin, Toshiba, Trane, O-General, Mitsubishi Electric, Voltas, Bluestar, Carrier |
| 205 | Supply, Installation, Testing and Commissioning of 2.0TR BEE 3 STAR rated INVERTER-Type Air-Cooled Hi-Wall Split-Type Air Conditioners, complete with Indoor Unit (IDU), Outdoor Unit (ODU), surface/concealed copper refrigerant piping with insulation (closed-cell elastomeric nitrile rubber tubular pipe section) up to 3 meters (IDU to ODU), copper power cable up to 3.5 meters (IDU to ODU), including drain pipe, R-32/R-410A/R-407C green refrigerant, wireless remote control, suitable for working between 180–260V with low & high voltage cutoff and 50 Hz, singlephase AC supply, capable of performing cooling, dehumidification, and air circulation of the following capacity with scroll/rotary compressor—the system shall be able to deliver 100% of the rated capacity up to 42°C. The unit must be able to operate up to 50°C (outdoor ambient temperature). WARRANTY: The system must include a MINIMUM 5-year Original Equipment Manufacturer (OEM) warranty for PCB, 10-year warranty on compressor, and 1-year warranty for the total machine. Warranty Certificate to be submitted for approval. Approved Make : Hitachi, Daikin, Toshiba, Trane, O-General, Mitsubishi Electric, Voltas, Bluestar, Carrier |
| 206 | Supply and installation of automatic voltage STABILIZERS suitable for 2.0TR split AC units, complete with all necessary wiring, connectors, and wall mounting hardware. The stabilizer shall feature intelligent microprocessor-based control with SMT/PTH IC technology, ±1% output voltage accuracy, and startup time delay protection. It shall operate within 170V-270V AC input range (50Hz) with auto-reset low/high voltage cut-off, manual-reset thermal overload protection, short-circuit and surge protection |
| 207 | Supply and installation of automatic voltage STABILIZERS suitable for 1.0TR/1.5TR split AC units, complete with all necessary wiring, connectors, and wall mounting hardware. The stabilizer shall feature intelligent microprocessor-based control with SMT/PTH IC technology, ±1% output voltage accuracy, and startup time delay protection. It shall operate within 170V-270V AC input range (50Hz) with auto-reset low/high voltage cut-off, manual-reset thermal overload protection, shortcircuit and surge protection |
| 208 | Supply and installation of heavy-duty mild steel (M.S) OUTDOOR STAND for split AC units, comprising of powder-coated mounting brackets with anti-corrosion treatment including all necessary galvanized mounting bolts, nuts, washers, and anchor fasteners. Installation shall be as per manufacturer guidelines and Engineer-inCharge’s directions, ensuring level alignment with wall/floor mounting options |
| 209 | Supply and installation of insulated PVC condensate DRAIN PIPING for split AC units including wall chasing, solvent-welded joints, and complete with clamps at regular intervals. Installation shall be with adequate slope towards drainage point. Work includes all necessary bends, couplings, P-traps and termination into designated drainage system. |
| 210 | Supply and installation of ADDITIONAL REFRIGERANT PIPING KIT for split AC units, comprising of Seamless copper tubing with wall thickness as per AC manufacturer's specifications, flame retardant elastomeric nitrile rubber insulation of minimum 13mm thickness all including necessary power and control cabling. |
| 211 | Supply, installation, testing and commissioning of CAT6 Information Outlet, RJ45 with all accessories required at site to complete the work as per technical specification |
| 212 | Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable |
| 213 | Supply, Installation, Testing & Commissioning of 16 Port POE Switch with 16 No's of 10/100/1000 ports GIGA Switch |
| 214 | SITC OF 4U Rack with PDU unit with Suitable for all type of DVR Box & Double DVR / Network Switch / Server Rack with 4 Power Socket & Cable , Tray (1No) - 1 Cooling Fan Lock & Key. |
| 215 | Supply and installation of Cat 6 UTP patch cord, 1m length. |
| 216 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Telephone socket outlet |
| 217 | Supply of User Phone- Analog phone |
| 218 | \\"Supply , Installation of PBX System with below features and accessories - 1 PRI Port(T1/E1) expandable upto 4 PRI ports - 4 Analog Trunk Lines - Extensions - 16 ( Analog or IP as required )\\" |
| 219 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.2 Pair |
| 220 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 221 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 222 | DOCUMENTATION AND APPROVAL |
| 223 | DOCUMENTATION AND APPROVAL \\"Charges for Preparation of all drawings submitting and getting approval from KSEB, submitting of Completion certificates and arranging inspection, getting sanction and energization certificates from KSEB, obtaining power allocation & power connection etc. including feasibility study. for commissioning of the whole installation. All statutory payments will be reimbursed on production of the original receipts. (for modification works) |
| 224 | SERVICE CUBICLE: Fabrication, supply, erection, testing and commissioning of Outdoor type CT metering panel cubicle type, dust and vermin proof, wall mounted, front operated, MV panel board made out of 16 SWG thick CRCA sheet fully compartmentalized complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel including all components. It consist of 100A, 36KA, 433V, FP MCCB - 1No RYB phase indicating LED lamps with control fuses and switches - 1No,100A HRC fuse 3nos and provision for 100/5A, CL:0.5, 15VA cast resin CT, provision for kWh meter after testing at Electricity Board TMR Division. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all accessories as required for complete installation as instructed by engineer in charge/consultant. |
| 225 | FIRE FIGHTING AND FIRE ALARM |
| 226 | TERRACE PUMP AND AIR VESSEL |
| 227 | Supplying, installation, testing and commissioning of electric driven450lpm at 35m Head |
| 228 | supplying and fixing air vessel made of 250 mm dia 8 mm thick MS sheet , 1200 mm in height with Air release valve on top and flanged connection to riser , drain arrangement with 25 mm dia Gun metal wheel valve with required accessories , pressure guage and painting with synthetic enamel paint of approved shade as required. |
| 229 | Power Control Panel- Supply, Installation, testing and commissioning of combined type automatic motor control panel with necessary star delta starters, indication lamps etc. for terrace fire pumps |
| 230 | PIPE AND ACCESSORIES |
| 231 | Supplying and fixing 63 m dia,15m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required: Stainless steel (Grade 304) |
| 232 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. (a) 20 mm nominal Internal dia water hose thermoplastic (Textile reinforced) type-2 as per IS:12585 (b) 20 mm nominal internal dia gun metal globe valve &nozzle (c) Drum and brackets for fixing the equipments on wall. (d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 m |
| 233 | Supplying and fixing 63 mm dia gun etal short metal branch pipe ith 20 mm nominal interanal diameter size nozzle conforming to IS 903 suitable for Instantaneous connection to Interconnect hose pipe coupling as required:Supplying and fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required: |
| 234 | Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:50 mm dia |
| 235 | Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:100mm dia |
| 236 | Supply, installation, testing and commissioning of weather proof hose boxes wall/pedestal type of size 600 x 250 x 400 mm made out of 18 gauge MS sheet steel with front side glass, locking arrangement and painted with approved colour completed as required and as per specifications. |
| 237 | VALVES ,SWITCHES AND GAUGES |
| 238 | Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts ,washers ,gaskets conforming to IS 13095 of following sizes as required:100 mm dia |
| 239 | Providing,installation,testing and commissioning of non-return valve of following sizes conforming to IS :5312 complete with rubber gasket, GI bolts , nuts, washers etc as required.100 mm dia |
| 240 | Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required |
| 241 | Providing, installation ,testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel , Grade 304,sheet with3 mm dia holes with stainless steel flange.100 mm dia |
| 242 | Providing and fixing of pressure switch in MS pipeline including connection etc as required: |
| 243 | Providing and fixing of flow switch in MS pipe including connection etc as required:100 mm dia |
| 244 | Supplying and fixing single headed internal hydrant valve with instantaneous Gun metal or stainless steel coupling of 63mm dia with cast iron wheel ISI marked conforming to IS 5290(Type A) with blank Gun metal or Stainless steel cap and chain as required:Single headed stainless steel |
| 245 | FIRE EXTINGUISHERS |
| 246 | Supplying, installing and commissioning Portable Fire extinguishers of following type & capacity.Co2 type Fire Extinguisher, made from brand new seamless Steel cylinder, as per IS: 7285 and CCE approval, fitted with Discharge hose and horn and Wheel type valve with initial Charge and mounted on Rubber Wheels / wall mounted brackets as per IS: 16018 specification, bearing ISI Mark. 4.5 Kgs |
| 247 | Supply and installation of ABC Stored pressure type Fire Extinguisher 6 Kgs Capacity Mono Ammonium Phosphate based Dry Chemical Powder as per IS 14609 with ISI Mark for Fighting ABC Class of Fire, stored Pressure type of Mild steel body pressurized by Nitrogen Gas. The Extinguisher shall have pressure gauge for indicating inside pressure with opening and closing lever of squeeze grip type with tamper proof seal, complete with wall bracket. The Extinguisher should be manufactured strictly as per IS: 15683:2006 with ISI mark |
| 248 | AUTHORITY APPROVAL AND SIGNAGES |
| 249 | AUTHORITY APPROVALS AND COORDINATION: Preparation of all drawings, submitting and getting approval from fire department, submitting of completion certificates and arranging inspection, getting sanction, etc. for commissioning of the whole installation in the premises.(All statutory payments will be reimbursed with original receipts.) |
| 250 | SITC of self glowing \\"FIRE EXTINGUISHER\\" sign boards of size (150 X 150 mm) in triangular shape fixed on the wall and shall be as per IS code 9457:2005, IS 12349, IS 12407. |
| 251 | Supply, installation, testing and commissioning of Fire Exit Light, Laser type, with High Glow LED, size:300x 178 x 32 mm. or 390 x190 x 60mm, Ceiling Mounting type with hanging clamps, on/off switch, Red /Green Colour option with minimum of 25 Mtr. viewing distance, power consumption: 5.0 Watt per face (maximum) Double Side Display and shall be as per IS code 9457:2005, IS 12349, IS 12407. |
| 252 | Supply, installation, testing and commissioning of Fire Exit Light, Laser type, with High Glow LED, size:300x 178 x 32 mm. or 390 x190 x 60mm, Ceiling Mounting type with hanging clamps, on/off switch, Red /Green Colour option with minimum of 25 Mtr. viewing distance, power consumption: 5.0 Watt per face (maximum), with Single Side Display and shall be as per IS code 9457:2005, IS 12349, IS 12407. |
| 253 | Providing and fixing in position the signage \\" FIRE ORDER\\" on 3mm thick \\"Opaque\\" PVC foam board of computerized cut, PVC non reflective self adhesive vinyl painted foam board of 2' x 3' and shall be as per IS code 9457:2005, IS 12349, IS 12407 |
| 254 | Providing and fixing of Floor Identification Signage (MAIN STAIRCASE, FIRE STAIRCASE, FIRE ASSEMBLY POINT, PUMP ROOM, FIRE CONTROL ROOM, ELECTRICAL ROOM, FIRE LIFT, PASSENGER LIFT Etc.) on every floor, lettering size shall be 5 Cm. with contrasting colour from background. Size shall be 15cm x 30cm and shall be as per IS code 9457:2005, IS 12349, IS 1240 |
| 255 | Providing and fixing of Floor identification signage (e.g., GROUND FLOOR, FIRST FLOOR, etc.) will be placed at each stair enclosure on every floor, displaying the floor number in words. The letter size will be 5 cm, with a contrasting color to the background. The dimensions of the signage will be 15 cm x 30 cm, and it will comply IS Code 9457:2005, IS 12349, and IS 12407. |
| 256 | Providing and fixing of signage : \\"IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE\\" with red letters, each 1.25 cm in height, on a white background. The board dimensions will be 25 cm x 30 cm and will be mounted at a height of 2 meters from the finished floor, positioned near manual call points. The signage will comply with IS Code 9457:2005, IS 12349, and IS 1240 standards. |
| 257 | FIRE BRIGADE |
| 258 | Supplying and fixing fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia M.S. Pipe connection conforming to IS 904 as required:3 way-150 mm dia M.S.Pipe |
| 259 | FIRE ALARM SYSTEM |
| 260 | FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning of smoke detector with built-in LED and mounting base complete with all connections etc. as required. |
| 261 | FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning of manual call boxes of MS Construction in surface/recess with stainless steel chain & hammer assembly Complete with glass and push button etc. as required. |
| 262 | FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required |
| 263 | Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required.4 Zone |
| 264 | CABLING & WIRINGSupplying & laying of 2x1.5 sq mm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 24, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 05, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysOct 06, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 7 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender