Tender For Provn Of Defi Md Accn For 50 Officers , 24 Jcos And 84 Hav/Ors At Jaipur Mil Stn
Tender Value
74.24 Crore
Estimated cost
Bid Submission
28 Oct 2026
24 days left
EMD
15 Lakhs
Bank guarantee accepted
Document Fee
3000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jaipur → Rajasthan
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender For Provn Of Defi Md Accn For 50 Officers , 24 Jcos And 84 Hav/Ors At Jaipur Mil Stn
BOQ
| Sl. No. | Item Description |
| 1 | Schedule \\"A\\" \\"BUILDING WORKS\\" PART IA is not prepriced by MES and prepriced rate indicates 0.0 under Column 5 signifies this fact only. This schedule includes construction buildings mentioned under serial item No. 1 to 8 of Schedule \\"A\\" PART IA (BUILDING WORKS) on page No. 52 & 53 of tender documents. |
| 2 | Lump sum price worked out by the contractor for \\"BUILDING WORKS\\" as listed in Schedule ‘A’ Part-IB representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 3 | Lump sum price worked out by the contractor for \\"INTERNAL WATER SUPPLY \\" as listed in Schedule ‘A’ Part-II representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 4 | Lump sum price worked out by the contractor for \\"INTERNAL ELECTRIFICATION\\" as listed in Schedule ‘A’ Part-III representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 5 | Lump sum price worked out by the contractor for \\"ROAD, PATH, CULVERT AND HARD STANDING\\" as listed in Schedule ‘A’ Part-IV representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 6 | Lump sum price worked out by the contractor for \\"SEWAGE DISPOSAL (B/R & E/M)\\" as listed in Schedule ‘A’ Part-V representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 7 | Lump sum price worked out by the contractor for \\"AREA DRAINAGE \\" as listed in Schedule ‘A’ Part-VI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 8 | Lump sum price worked out by the contractor for \\"COMPOUND WALL ,FENCING AND GATE \\" as listed in Schedule ‘A’ Part-VII\\" representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 9 | Lump sum price worked out by the contractor for \\"RAIN WATER HARVESTING\\" as listed in Schedule ‘A’ Part-VIII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 10 | Lump sum price worked out by the contractor for \\"EXTERNAL WATER SUPPLY\\" as listed in Schedule ‘A’ Part-IX representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 11 | Lump sum price worked out by the contractor for \\"EXTERNAL ELECTRIFICATION\\" as listed in Schedule ‘A’ Part-X representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 12 | Lump sum price worked out by the contractor for \\" LIGHTING PROTECTION \\" as listed in Schedule ‘A’ Part-XI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 13 | Lump sum price worked out by the contractor for \\"FIRE FIGHTING SYSTEM AND SMOKE DETECTOR\\" as listed in Schedule ‘A’ Part-XII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 14 | Lump sum price worked out by the contractor for \\"LIFT WORK\\" as listed in Schedule ‘A’ Part-XIII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 15 | Lump sum price worked out by the contractor for \\"DG SETS SUPPLY\\" as listed in Schedule ‘A’ Part-XIV representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 16 | Lump sum price worked out by the contractor for \\"HOT WATER SUPPLY\\" as listed in Schedule ‘A’ Part-XV representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 17 | Lump sum price worked out by the contractor for \\"SITE CLEARANCE, SITE DEVELOPMENT AND EARTH WORK\\" as listed in Schedule ‘A’ Part-XVI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 18 | Sch 'A' Part-XVII MISC ITEMS (TO BE QUOTED BY CONTRACTOR) Notes: (i) This schedule is not pre-priced by MES and the pre-priced rate indicated as \\"Rs 0.00\\" under column 5 signifies this fact only. (ii) Excavation and earth work except for the items which categorically includes for same shall be measured and paid separately under SCH A PART-XVI SITE CLEARANCE, SITE DEVELOPMENT AND EARTH WORK schedule). |
| 19 | INTERNAL WATER SUPPLYS&F for two way bib cock with wall flange quarter turn (Low-flow) 15/16 mm dia. etc complete all as specified and directed by Engineer-in-Charge |
| 20 | S&F CP wall mixer of Bathroom 3 in 1 system with provision for both hand & over head shower with 115 mm long bend pipe cinnecting legs & wall flange etc complete all as specified & as direcetd. |
| 21 | S & F Gun-metal, globe or gate valves, painted finish with forged brass handle and iron wheel head, screwed both ends internally IS:778 class 2 for iron pipe or for unions of size 80mm dia complete all as specified and directed. |
| 22 | INTERNAL ELECTRIFICATIONS&F for RG6 cable for TV point etc complete all as specified and directed |
| 23 | S&F for modular type 1 module co-axial type TV socket etc complete all as specified and directed |
| 24 | S&F for modular type 1 module RJ-11 telephone socket with shutter etc complete all as specified and directed |
| 25 | S&F for modular type 1 blanking plate etc complete all as specified and directed |
| 26 | Supply and fixing for wall mounting fan,230 Volts,50Hz,300mm sweep, 4 star rated with swing/oscillation type, with necessary accessories for wall mounting fan and electrical connections from ceiling rose to fan teriminal including writting the MES Number with synthetic enamel paint complete all as specified and as directed. |
| 27 | SEWAGE DISPOSAL (B/R & E/M)Supply install,testing and commissioning of Submersible Dewatering pump (Sewage) with cast iron impeller and cast iron delivery casing of suitable capacity ,Three phase , 415 volt with IP -68 protection ,Class F insulation,Double Mechanical seal ,10 Mtr long pvc insulated copper cable with epoxy sealed cable entry,suitable for sewage application as per IS: 14220 with delivery size 80 mm, speed 2900 RPM, frequency 50 Hz, minimum head 8 mtr, Max head 23.5 mtr ,discharge 1440 LPM , vortex type impellers (Non Clog) allows smooth passage of solid waste or debris of 35 mm including cast iron auto coupling with guide rail system 02 Nos 40 mm dia SS 304 guide pipes,SS 304 lifting chain (06) mtr and pulley block arrangement complete all as specified and directed bu Engr-in-Charge. |
| 28 | Supply,laying and testing of centrifugally cast (spun)100 mm dia ductile iron (DI) pressure pipes with spigot and socketed ends, class K-7 , ISI marked (IS 8329-2000), internally lined with cement mortar as per IS 8329-2000, externally coated with Zinc 130gsm and finishing layer of bitumen (70 microns) as per IS 8329-2000, jointing with and including rubber gasket joints; including fixing of fittings with and including suitable jointing material, complete all as specified and as directed. |
| 29 | Supply,laying and testing of centrifugally cast (spun) 80 mm dia ductile iron (DI) pressure pipes with screwed joint double flanged end, class K-7 , ISI marked (IS 8329-2000), internally lined with cement mortar as per IS 8329-2000, externally coated with Zinc 130gsm and finishing layer of bitumen (70 microns) as per IS 8329-2000, jointing with and including rubber gasket joints including fixing of fittings with and including suitable jointing material, complete all as specified and as directed. |
| 30 | Supply,Install,Testing and Commissioning LT panel Outdoor type, dust and vermin proof totally enclosed ,with sloping canopy fabricated out of steel sections, the door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 54 standard double shutter gears front and rear frame work and 2 mm thick MS sheet duly powder coated made of 40 x 40 x 6 mm thick angle iron frame including necessary PCC work all as specfified suitable for 415 Volts, 50 Hz 3 phase and neutral system and shall be completed with copper bar of capacity 125 Amps with bus bar chamber,internal wiring with suitable size of PVC insulated copper cable copper lugs comprising of following accessories:- |
| 31 | Incoming:-(i) MCCB 63 Amps,16 KA, 4 pole with fixed thermal and fixed magnetic setting-01 No(ii) Phase indicator LED Red blue yellow -01 set of three(iii) LED Multifunctional meter accuracy class 1.0,0.5,input voltage measurement range 50-520 VAC(P-P),Aux supply 80-300VAC,Flush mounting 96x96mm,Site selectable 1A/5A,CT/PT site programmable with RS485 port along with Following parameters :-VA,F,PF,kW,kVA,Old energy,On and Run hours,site selectable KWH/KVAH- 01 No(iv)Automation contol switchOutgoing:-(i) MCCB 40 Amps,16 KA, 4 pole with fixed thermal and fixed magnetic -02 Nos(ii) MCB SPN 20 A,10 KA,'C' Cruve-01 No(iii) DOL Starter suitable for 1440 LPM at 8-23.5 mtr head-02 Nos including overload relay, auto timer & single phase preventer suitable range of digital ammeter with selector switch, voltmeter with selector, Start/Stop Push buttons, indicating lamps (LED) & bakelite fuse showing RYB phase, internal wiring with copper conductor etc complete(iv) Automation of pump by providing 02 Nos Float switch (1 for High Level,1 For low level) with 10 Mtr cable and level controller in panel - 02 Nos |
| 32 | BOREWELL FOR RAIN WATER HARVESTING(a) Provision of trail bore by drilling with reverse rotary system upto 400 mm bore upto 52 m depth incl all works pertaining to boring complete in all respect in aluvium soil/ strata incl hard stone / boulder etc.(b) M&L for 200 mm bore CPVC pipe assembly jointing, lowering in any position upto the reqd depth below given level incl jointing the pipe by solvent & screwing 04 Nos screws in each joint complete.(c) Ditto as item 30(b) above but slotted pipe(d) M& L for packing with Pea gravel of 4.6 mm to 8mm size of approved quality as ordered to pack arround the casing / slooted pipe in borewell complete.(e) M&L 25 mm bore perforated CPVC pipe 52 mtr long for vent pipe etc complete all as specified and directed. |
| 33 | EXTERNAL WATER SUPPLY Supply and laying Ductile Iron (DI) pressure pipe of size 150 mm dia with spigot and socketed ends, class K-7,ISI marked (IS 8329-2000) ,internally lines with cement mortar as per IS 8329-2000 ,externally coated with Zinc 130 gsm and finishing layer of bitumen (70 micron) as per IS 8329-2000,jointing with and including rubber gasket joints, including fixing of fittings with and including suitable jointing material complete all as specified and directed by Engr-in-Charge.Note: The rate quoted by contractor are inclusive of all type of Joints. |
| 34 | M & L for cutting/connection from existing DI pipelines/header of size upto 200mm dia for taking branch connection along with insertion of DI Tee of size 150 mm x150mm x150 mm dia and connecting material such as joint rubber sheet 3 mm thick,nut,bolt,washer,end plate etc all as required at site. (Note:- Cost of welding, threading on pipes and connected items are inclusive of above quoted price.) |
| 35 | Supply,Install,Testing and Commissioning LT panel Indoor type, dust and vermin proof totally enclosed ,with sloping canopy fabricated out of steel sections, the door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 42 standard double shutter gears front and rear frame work and 2.00 mm thick MS sheet duly powder coated made of 40 x 40 x 6 mm thick angle iron frame including necessary PCC work all as specfified suitable for 415 Volts, 50 Hz 3 phase and neutral system and shall be completed with Aluminium bus bar of capacity 160 Amps with bus bar chamber,internal wiring with suitable size of PVC insulated copper cable copper lugs comprising of following accessories (Main Haldi Ghati Pump House) |
| 36 | Incoming:- (i) MCCB 100 Amps,25 KA, 4 pole with fixed thermal and fixed magnetic setting-01 No (ii) Phase indicator LED Red blue yellow -01 set of three(iii) LED Multifunctional meter accuracy class 1.0,0.5,input voltage measurement range 50-520 VAC(P-P),Aux supply 80-300VAC,Flush mounting 96x96mm,Site selectable 1A/5A,CT/PT site programmable with RS485 port along with Following parameters :-VA,F,PF,kW,kVA,Old energy,On and Run hours,site selectable KWH/KVAH- 01 No.Outgoing:-(i) MCCB 63 Amps,16 KA, 4 pole wiith fixed thermal and fixed magnetic setting-02 Nos (Motor-1 and Motor-2 )(ii) MCB SPN 20 A,10 KA ,'C' Curve-01 No(iii) Star delta Starter fully automatic suitable for 1100 LPM at 40 mtr head-02 Nos including overload relay, auto timer & single phase preventer suitable range of digital ammeter with selector switch, voltmeter with selector, Start/Stop Push buttons, indicating lamps (LED) & bakelite fuse showing RYB phase, internal wiring with copper conductor etc complete |
| 37 | Supply,Install,Testing and Commissioning LT panel Indoor type, dust and vermin proof totally enclosed ,with sloping canopy fabricated out of steel sections, the door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 42 standard double shutter gears front and rear frame work and 2.00 mm thick MS sheet duly powder coated made of 40 x 40 x 6 mm thick angle iron frame including necessary PCC work all as specfified suitable for 415 Volts, 50 Hz 3 phase and neutral system and shall be completed with Aluminium bus bar of capacity 200 Amps with bus bar chamber,internal wiring with suitable size of PVC insulated copper cable copper lugs comprising of following accessories(Offrs Accn ) |
| 38 | Incoming:- (i) MCCB 125 Amps,25 KA, 4 pole with fixed thermal and fixed magnetic setting-01 No(ii) Phase indicator LED Red blue yellow -01 set of three(iii) LED Multifunctional meter accuracy class 1.0,0.5,input voltage measurement range 50-520 VAC(P-P),Aux supply 80-300VAC,Flush mounting 96x96mm,Site selectable 1A/5A,CT/PT site programmable with RS485 port along with Following parameters :-VA,F,PF,kW,kVA,Old energy,On and Run hours,site selectable KWH/KVAH- 01 NoOutgoing:-(i) MCCB 63 Amps,16 KA, 4 pole with ith fixed thermal and fixed magnetic setting-04 Nos(ii) MCB SPN 20 A,10 KA ,'C' Curve-04 Nos(iii) Star delta Starter fully automatic suitable for 520 LPM at 60 mtr head -04 Nos including overload relay, auto timer & single phase preventer suitable range of digital ammeter with selector switch, voltmeter with selector, Start/Stop Push buttons, indicating lamps (LED) & bakelite fuse showing RYB phase, internal wiring with copper conductor etc complete |
| 39 | Supply,Install,Testing and Commissioning LT panel Indoor type, dust and vermin proof totally enclosed with sloping canopy fabricated out of steel sections, the door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 42 standard double shutter gears front and rear frame work and 2 mm thick MS sheet duly powder coated made of 40 x 40 x 6 mm thick angle iron frame including necessary PCC work all as specfified suitable for 415 Volts, 50 Hz 3 phase and neutral system and shall be completed with Aluminium bus bar of capacity 240 Amps with bus bar chamber,internal wiring with suitable size of PVC insulated copper cable copper lugs comprising of following accessories(JCOs and ORs Accn) |
| 40 | Incoming:- (i) MCCB 160 Amps,25 KA, 4 pole with fixed thermal and fixed magnetic setting-01 No(ii) Phase indicator LED Red blue yellow -01 set of three(iii) LED Multifunctional meter accuracy class 1.0,0.5,input voltage measurement range 50-520 VAC(P-P),Aux supply 80-300VAC,Flush mounting 96x96mm,Site selectable 1A/5A,CT/PT site programmable with RS485 port along with Following parameters :-VA,F,PF,kW,kVA,Old energy,On and Run hours,site selectable KWH/KVAH- 01 NoOutgoing:-(i) MCCB 40 Amps,16 KA, 4 pole with ith fixed thermal and fixed magnetic setting-08 Nos(ii) MCB SPN 20 A,10 KA ,'C' Curve-08 Nos(iii) Star delta Starter fully automatic suitable for 520 LPM at 40 mtr head-08 Nos including overload relay, auto timer & single phase preventer suitable range of digital ammeter with selector switch, voltmeter with selector, Start/Stop Push buttons, indicating lamps (LED) & bakelite fuse showing RYB phase, internal wiring with copper conductor etc complete |
| 41 | Supply, installation and testing of centrifugal type pump set, electric motor driven not less than 520 LPM at 40 mtr head in load suitable for pumping treated water comprising of the following specification:(i) Centrifugal Pump and discharge not less than 520 LPM at 40 mtr head ,1440 RPM having bronze impeller and stainless-steel shaft single stage directly coupled with electric motor through flexible coupling. (ii) Suitable HP Squirrel cage induction motor as per manufacturer recommendation, TEFC,3phase 415 +10-volt,50 C/S AC supply suitable RPM directly coupled to centrifugal pumped. (iii) Common base foundation of ISMC -100 suitable for installation of above pump set duly drilled holes and painted with two coats of synthetic enameled paint over a coat of red oxide primer.(iv) Above ISMC foundation shall be grouted in PCC 1:3:6 type C-2 using 40 mm graded aggregate 30 cm above Ground level and 15 cm below GL and per size of common base foundation as per manufacturer specification or as directed by Engr-in-charge.(v) Bourdons type pressure gauge 3’’ dia dial type-01 No(vi) Air release valve-01 No(vii) M & Lfor lowering of GI suction pipe flanged type heavy grade welded with flange of dia not less than the dia suitable to match the suction of pumps from foot valve at suction flange of pump |
| 42 | (viii) M & L for GI delivery pipe flanged type heavy grade welded with flange of dia not les than the dia suitable to match the pumps from pump sluice valve and from sluice valve to NRV(ix) Supply & fix foot valve of size as per suction pipe dia dia as per IS 4038 flanged type including fixing on any pipe with nut bolt,washer .(x) Priming arrangement using 25 mm GI pipe and 01 No PVC tnk 750 Ltrs capacity and connected items.(xi) M & L for Three core copper cable of suitbale size as per motor capacity from motor to LT panel.(xii) Sluice valve & Non return valve etc shall be measured and paid separately in respective schedule (08 Nos for JCO and ORs Qtrs 04 Working+04 Stand by) |
| 43 | Supply, installation and testing of centrifugal type pump set, electric motor driven not less than 520 LPM at 60 mtr head in load suitable for pumping treated water comprising of the following specification:(i) Centrifugal Pump and discharge not less than 520 LPM at 60 mtr head ,1440 RPM having bronze impeller and stainless-steel shaft single stage directly coupled with electric motor through flexible coupling (ii) Suitable HP Squirrel cage induction motor as per manufacturer recommendation, TEFC,3phase 415 +10-volt,50 C/S AC supply suitable RPM directly coupled to centrifugal pumped (iii) Common base foundation of ISMC -100 suitable for installation of above pump set duly drilled holes and painted with two coats of synthetic enameled paint over a coat of red oxide primer.(iv) Above ISMC foundation shall be grouted in PCC 1:3:6 type C-2 using 40 mm graded aggregate 30 cm above Ground level and 15 cm below GL and per size of common base foundation/stranded Engr practice or as directed by Engr-in-charge.(v) Bourdons type pressure gauge 3’’ dia dial type(vi) Air release valve-01 No(vii) M & Lfor lowering of GI suction pipe flanged type heavy grade welded with flange of dia not less than the dia suitable to match the suction of pumps from foot valve at suction flange of pump |
| 44 | (viii) M & L for GI delivery pipe flanged type heavy grade welded with flange of dia not les than the dia suitable to match the pumps from pump sluice valve and from sluice valve to NRV(ix) Supply & fix foot valve of size as per suction pipe dia as per IS 4038 flanged type including fixing on any pipe with nut bolt,washer etc.(x) M & L for Priming arrangement using 25 mm GI pipe and 01 No PVC tnk 750 Ltrs capacity(xi) M & L for Three core copper cable of suitbale size as per motor capacity from motor to LT panel. (xii) Sluice valve & Non return valve etc shall be measured and paid separately in respective schedule (04 Nos for Offrs Qtrs 02 Working+02 Stand by) |
| 45 | Supply, installation and testing of centrifugal type pump set, electric motor driven not less than 1100 LPM at 40 mtr head in load suitable for pumping treated water comprising of the following specification:(i) Centrifugal Pump and discharge not less than 1100 LPM at 40 mtr head ,1440 RPM having bronze impeller and stainless-steel shaft single stage directly coupled with electric motor through flexible coupling (ii) Suitable HP Squirrel cage induction motor as per manufacturer recommendation, TEFC,3 phase 415 +10-volt,50 C/S AC supply suitable RPM directly coupled to centrifugal pumped (iii) Common base foundation of ISMC -100 suitable for installation of above pump set duly drilled holes and painted with two coats of synthetic enameled paint over a coat of red oxide primer.(iv) Above ISMC foundation shall be grouted in PCC 1:3:6 type C-2 using 40 mm graded aggregate 30 cm above Ground level and 15 cm below GL and per size of common base foundation/stranded Engr practice or as directed by Engr-in-charge.(v) Bourdons type pressure gauge 3’’ dia dial type.(vi) Air release valve-01 No(vii) M & L for lowering of GI suction pipe flanged type heavy grade welded with flange of dia not less than the dia suitable to match the suction of pumps from foot valve at suction flange of pump |
| 46 | (viii) M & L for GI delivery pipe flanged type heavy grade welded with flange of dia not les than the dia suitable to match the pumps from pump sluice valve and from sluice valve to NRV(ix) Supply & fix foot valve of size as per suction pipe dia dia as per IS 4038 flanged type including fixing on any pipe with nut bolt,washer .(x) Priming arrangement using 25 mm GI pipe and 01 No PVC tnk 750 Ltrs capacity.(xi) M & L for Three core copper cable of suitbale size as per motor capacity from motor to LT panel.(xii) Sluice valve & Non return valve etc shall be measured and paid separately in respective schedule (02 Nos for 01 Working +01 StandbyHaldhi ghati pump house ) |
| 47 | M&L boring of road crossing of size 250 mm dia at suitable depth not less than 1 mtr by using machinery / equipments complete without damaging the surface for passing pipes / cables etc including removing excavated soil to a distance not exceeding 50m, complete all as specified and as directed.Note :- (i) Location of boring holes shall be decided by the Engr-in-Charge as per requirement, nothing extra shall be payable on account of variation in length of crossing of road etc. (ii) During boring soil strata may be changed, hence nothing extra shall be paid to the contractor for boring of holes through different strata/different type of soil. Tenderer is hereby advised to keep in mind this aspect while Quoting his rates.(iii) After completion of job disturbed surface to be match with existing surface including material and labour for reparing. |
| 48 | M & L for MS ERW pipe 100 mm nominal bore and 8.00 mm thick heavy duty conforimng to IS 3589 pipe including necesary fabrication,cutting, welding ,bending, drilling holes for bolts in any shape or size for providing incoming and outgoing pipe connection including painting on outer side of ERW pipe by applying one coat or redoxide and two coats of synthetic enamel paint complete all as specified and directed. |
| 49 | S & F Heavy duty chemical dosing system plunger type suitable to inject solution up to 25 LPH working pressure10 kg/cm2 comprising dosing pump coupled with three phase electric motor of capacity 0.5 HP , 1440 RPM assembly with agitatorinone motor, agitator with SS sweep bladeduly FRP coated, FRP tank150 Ltr capaity, completed unit mounted on heavy duty MS fabricated frame duly anti corrosive paint complete with chemical grade PVC NRV, along with control panel for Dosing pump suitable for SSAPS/CDSPT/25made of powder coated MS febricated box consisting of LED indicator, digital volt meter, Amp Meter, single phase preventer, High voltage low voltage protection complete all as specified and directed. |
| 50 | Supply, installing, testing and commissioning of heavy duty perforated MS cable tray suitable to accommodate the cables of pump house from LT Panel to all pumps. The cable tray shall be MS sheet, Minimum thickness 2.00mm or as per load calculation, hot dip galvanized after fabrication (HDG, 80-120 microns zinc coating), with 50 mm side height and adequate width (typically 150-300mm) finalized as per actual cable quantity with 30% spare capacity). The tray shall include all bends, tee, reducers, couplers, covers (where required, splice plate, nuts & bolts, support on MS angle/channels supports at maximum 1-1.5mtr spacing, properly earthed, aligned, and fixed on wall/ceiling as required and directed by Engr-in-Charge. |
| 51 | M&L for construction of valve chamber of brick masonry from the top of surface with MS covers 3.15 mm thick and 40x40x6 mm MS angle with hinges for locking arrangement including excavation and earth works PCC (1:3:6) type C2 for foundation PCC bed/coping in cement concrete (1:2:4) type B1, plastering in CM 1:3 painting with two coats of synthetic enamel paint over a coat of red oxide primer for the size of chamber 900 mm x 600 mm x 1000 mm (internal dimention) all as per TD drg No TD/2004/26 sheet No 1/3 tp 3/3 etc complete all as specified and directed. |
| 52 | S & F FRP scale conventional water level indicator complete with FRP scale ,MS Fabricated scale holding frame,FRP/GI float wire,Float guide pipe,bracket & pulley,conter wieght,indicator pin etc complete all as specified and directed. |
| 53 | S & F of cast iron air release valve (ARV) single head outet conforming to IS 14875 of size 50 mm dia bore and fixing up to cast iron water supply mains of DI pipe150 mm dia including connected items such as nut,bolt,washer and rubbber sheet complete all as specified and directed. |
| 54 | EXTERNAL ELECTRIFICATIONSupply, Installation, Testing and Commisioning of 11 KV Compact Sub Station with 11 KV 630 Amps 21 KA for 3 Sec,SF6 insulated Non Extinsible compact switchgear consisting of 01 No Fixed Manually operated Vacuum Circuit Breaker in SF6 insulated stainless steel enclosure,HT Cable/Bus bar ,1 No transformer 500 KVA,11KV/433 ONAN corrugated tank type & associated LT devices(ACB/MCCB/bus bar/Cable) complete including comprising of items as detailed below:- |
| 55 | (A) HT SWITCHGEAR11kV, 630Amps 21KA for 3 Sec. SF6 insulated Non-Extinsible Compact switchgear (Type DV) consisting of One No Fixed Manual Vacuum Circuit Breaker(VCB) having inbuilt load break switch and earth switch & One no Direct Cable Module within SF6 insulated robotically welded non ferrite non magnetic stainless steel enclosure of thickness 2.5mm having IP 67, with series trip, Aux powered microprocessor based numerical 3 O/C & 1 E/F relay (IDMTL + Inst.) protection along with metering panel.-01 NoRelay shall be Self powered of C&S/Ashida Make. ( 50,50N,51,51N) with RS485 communication port-01 NoProtection CT shall be 50/1A 2.5VA 5P10.-01 SetStandard Manometer (SF6 Gas Pressure Indicator)-01 NoVoltage presence indicator (VPIS) for incoming Healthy Indications-03 SetManual push button for breaker ON/OFF-01 SetMechanical Indication for Breaker & LBS ON/OFF/EARTHED.-03 NosOperating handle-01 NOAll incoming modules of the RMU shall be suitable cable termination of 1RX3CX300SQ.MM. Termination kit required for Cable shall be in purchaser scope only. |
| 56 | (B)TRANSFORMER SECTION(i)TRANSFORMER 500 KVA , 11/0.415 KV ,DYn11 copper Wound Oil cooled (ONAN) distribtion Trabsformer with Off circuit links,Off circuit Tap links (OCTL),Tapping range +5% to -5% in steps of 2.5 % (4Steps/5Positions) -01 No(ii)Transformer Losses:As per IS 1180 latest amendment 2021,Energy Efficiceny Level 3(iii)Insulation class:A(iv)Temp Rise shall for Oil/Winding be 40/45 Deg.C over an ambient of 50 degree cent .(v)Percentage impedenace (%Z) shall be 4.5 % (Subject to IS )(vi)Rating and diagram (R&D) plate plate (fitted on tarnsformer)-01 No(vii)OTI and WTI with alarm & trip-01 No |
| 57 | (C) LT PANEL1000A Al Busbar (100% for Phase & 50% for Neutrals) Current density 1.0amp/sqmm, having IP2X, Fabrication using 1.5/2mm CRCA sheet steel complete with internal wiring consisting of following:-INCOMER From transformer (a) 800 Amps 4P 50Hz 50KA Electrically Operated Manually drawout Type (EDO) Air Circuit Breaker (ACB) with microprocessor based Ekip Touch release for Overload (O/L), Short circuit (S/C) & Earth Fault (E/F) protection, (Thermal memory). -01 No(b) L/R and TNC switch-01 Set(c) LED type Indicating Lamp - RYB, ON-OFF-TRIP -01 Set(d) LT side metering CT 800A/ 5A, 5VA, Cl:0.5-01 Set(e) Digital Multifunction Meter (MFM), CL-0.5 Accuracy with RS485 Port-01 No(f) Metering CT ratio:- 800/5A, Class 1, 5VA(g) Digital A-METER, Cl-1(h) Digital V- METER, Cl-1(i) R,Y,B, LED for Phase Indication AC, (j) ON OFF, TRIP LED for Phase Indication AC(k)Aluminium Busbar - LT ACB INCOMER to OUTGOING 800A RATED (100% PH & 50% N with 1.0A/Sqmm Current Density)(l)Misc items - Terminals, Heaters, Sleeve,insulator, Hardware ,locks,handle,gasket, tie rods and other misc itmes |
| 58 | (D) OUTDOOR ENCLOSUREOutdoor type enclosure having construction of Galvanised Sheet Steel having 1.5mm thickness for Non-load bearing & 2 mm for Load bearing partition sheets & Door with ISMC base frame. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP23 degree of protection for Transformer compartment. The enclosure exterior shall be Powder Coated (Colour Light gray and dark gray ) C3 Class. Each compartment will be provided with the door and pad locking arrangement. The Compartment illumination lamp with door operated switch shall be provided for MV & LV compartment. As per IEC 62271-202 -01 Set |
| 59 | (E) INTERCONNECTION AND EARTHINGInterconnection Between HT switchgear & Transformer using 1Cx3Rx95 Sq.mm XLPE Single Core Aluminum Unarmored Cable & Interconnection between Transformer & LT switchgear using Al Busbars with Copper flexible. Internal earthing connections by using 50X6mm GI strips for body and Transformer Neutral by using 50X6 mm CU-01 Set |
| 60 | Supply, Installation, Testing and Commisioning of 11 KV Compact Sub Station with 11 KV 630 Amps 21 KA for 3 Sec,SF6 insulated Non Extinsible compact switchgear consisting of 01 No Fixed Manually operated Vacuum Circuit Breaker in SF6 insulated stainless steel enclosure,HT Cable/Bus bar ,1 No transformer 630 KVA,11KV/433 ONAN corrugated tank type & associated LT devices(ACB/MCCB/bus bar/Cable) complete including comprising of items as detailed below:- |
| 61 | (A) HT SWITCHGEAR11kV, 630Amps 21KA for 3 Sec. SF6 insulated Non-Extinsible Compact switchgear (Type DV) consisting of One No Fixed Manual Vacuum Circuit Breaker(VCB) having inbuilt load break switch and earth switch & One no Direct Cable Module within SF6 insulated robotically welded non ferrite non magnetic stainless steel enclosure of thickness 2.5mm having IP 67, with series trip, Aux powered microprocessor based numerical 3 O/C & 1 E/F relay (IDMTL + Inst.) protection along with metering panel.-01 NoRelay shall be Self powered of C&S/Ashida Make. ( 50,50N,51,51N) with RS485 communication port-01 NoProtection CT shall be 50/1A 2.5VA 5P10.-01 SetStandard Manometer (SF6 Gas Pressure Indicator)-01 NoVoltage presence indicator (VPIS) for incoming Healthy Indications-03 SetManual push button for breaker ON/OFF-01 SetMechanical Indication for Breaker & LBS ON/OFF/EARTHED.-03 NosOperating handle-01 NOAll incoming modules of the RMU shall be suitable cable termination of 1RX3CX300SQ.MM. Termination kit required for Cable shall be in purchaser scope only. |
| 62 | (B)TRANSFORMER SECTION(i)TRANSFORMER 630 KVA , 11/0.415 KV ,DYn11 copper Wound Oil cooled (ONAN) distribtion Trabsformer with Off circuit links,Off circuit Tap links (OCTL),Tapping range +5% to -5% in steps of 2.5 % (4Steps/5Positions) -01 No(ii)Transformer Losses:As per IS 1180 latest amendment 2021,Energy Efficiceny Level 3(iii)Insulation class:A(iv)Temp Rise shall for Oil/Winding be 40/45 Deg.C over an ambient of 50 degree cent .(v)Percentage impedenace (%Z) shall be 4.5 % (Subject to IS )(vi)Rating and diagram (R&D) plate plate (fitted on tarnsformer)-01 No(vii)OTI and WTI with alarm & trip-01 No |
| 63 | (C) LT PANEL1250A Al Busbar (100% for Phase & 50% for Neutrals) Current density 1.0amp/sqmm, having IP2X, Fabrication using 1.5/2mm CRCA sheet steel complete with internal wiring consisting of following.INCOMER From transformer (a) 1000Amps 4P 50Hz 50KA Electrically Operated Manually drawout Type (EDO) Air Circuit Breaker (ACB) with microprocessor based Ekip Touch release for Overload (O/L), Short circuit (S/C) & Earth Fault (E/F) protection, (Thermal memory). -01 No(b) L/R and TNC switch-01 Set(c) LED type Indicating Lamp - RYB, ON-OFF-TRIP -01 Set(d) LT side metering CT 630A/ 5A, 5VA, Cl:0.5-01 Set(e) Digital Multifunction Meter (MFM), CL-0.5 Accuracy with RS485 Port-01 No(f) Metering CT ratio:- 800/5A, Class 1, 5VA(g) Digital A-METER, Cl-1(h) Digital V- METER, Cl-1(i) R,Y,B, LED for Phase Indication AC, (j) ON OFF, TRIP LED for Phase Indication AC(k)Aluminium Busbar - LT ACB INCOMER to OUTGOING 1000A RATED (100% PH & 50% N with 1.0A/Sqmm Current Density)(l)Misc items - Terminals, Heaters, Sleeve,insulator, Hardware ,locks,handle,gasket, tie rods and other misc itmes |
| 64 | (D) OUTDOOR ENCLOSUREOutdoor type enclosure having construction of Galvanised Sheet Steel having 1.5mm thickness for Non-load bearing & 2 mm for Load bearing partition sheets & Door with ISMC base frame. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP23 degree of protection for Transformer compartment. The enclosure exterior shall be Powder Coated (Colour Light gray and dark gray ) C3 Class. Each compartment will be provided with the door and pad locking arrangement. The Compartment illumination lamp with door operated switch shall be provided for MV & LV compartment. As per IEC 62271-202 -01 Set |
| 65 | (E) INTERCONNECTION AND EARTHINGInterconnection Between HT switchgear & Transformer using 1Cx3Rx95 Sq.mm XLPE Single Core Aluminum Unarmored Cable & Interconnection between Transformer & LT switchgear using Al Busbars with Copper flexible. Internal earthing connections by using 50X6mm GI strips for body and Transformer Neutral by using 50X6 mm CU-01 Set |
| 66 | S&F poly carbonate junction box, weather and vermin proof of size 250X250X160mm including provn of 4 Nos aluminium strip 25x3.15mm size bus bar single phase and neutral suitable mounted on bus bar insulators, including one No. MCB, SP 6 Amps for light control, drilling of holes and provn of MS clamps made out of 25 x 3mm MS flat iron with GI nuts, bolts, double washers and fixing on LT steel tubular poles with locking arrangement complete all as specified and directed. |
| 67 | Supply, installing, testing and commissioning, factory made and tested, automatic power factor control panel (APFC Panel) out door type of Cap 125 KVAR , cubical front opening type, The panel shall be of protection class IP-54 and made out of 3.15 mm CRCA MS sheet and front operated and rear frame work fabricated from 3.15 mm thick CRCA MS sheet with hinged, gasketted (metal based neoprene) and lockable doors having structural reinforcement with suitable angle/channel/T/flat section, air dissipation louvers including 3mm thick gland plate on top and bottom,fifting hooks duly powder coated paint finish of approved shade over metal surface cleaned and treated with seven tank precess,internal wiring with PVC insulated, solid copper conductor, FRLS cables of adequate size and comprising of following accessories, IS-694 marked, 1100 volts grade of appropriate size but not less then 4.0 sqmm and comprising of the following and copper bus bar 600 Amp rating :- |
| 68 | Incoming : (a) MCCB,4P,415V, 320 Amp rating, 36 KA rating with adjustable thermal and fixed magnetic setting for O/C & S/C protection : 01 No.(b) Microprocessor based, modular type, intelligent APFC relay capable of having self adjustment to any capacitor value suitable to maintain power factor between 0.95 to 0.99 with digital indication of power factor three phase sensing relay with 03 Nos CTs, preset parameters and having in built capability of indication and elimination of defective capacitor steps. (c) Indicator Lamps LED type (RYB)-01 Set. (d) Digital Voltmeter with built-in selectror switch -01 No. (e) Digital Ampere meter with built-in selectror switch -01 No. (f) CT coil set of suitable rating -01Set. (g) ON delay timer -01 No. (h) Auto/Mannual operation selector switch -01No. (j) Aux Relay with 4No+4NC contactor -02 Nos. (k) Axial Air Flow fan 100mm sweep with thermostat - 02 Nos. (l) Control fuse of suitable size. (m) Control MCB,SP of suitable size. |
| 69 | Outgoing : (a) Auto/Mannual operation selector switch - 06 No. (b) MCCB TP 125 A, 415V rating - 01 Nos. (c) MCCB TP 63 A, 415V rating - 02 Nos. (d) MCCB TP 40 A ,415V rating - 02 Nos.(e) TP power contractor coil voltage 240 V AC AC3 duty 2 NO+2NC Aux contact of suitable size - 06 Ns. (f) Cap duty contactor for 50 KVAR-01 No,25 KVAR-02 No,12.5 KVAR-02 No (g) Capacitors type MD-XL as per IS 13585/hot I/1994/IS 13340/1993, for 150 (1x50,2x25,2x12.5) KVAR. (h) Star push button Green - 6 Nos. (j) Stop push button Red - 6 Nos. (k) Cap On indication Lamp Red - 6 Nos. (l) Cap off indication Lamp Green -6 Nos. (m) Fixed capacitor for transformer 15 KVAR with suitable rating MCB (n) Signal off delay timer 240 AC 6-60 Sec - 01 nos. Note :-(i) The equipment offered shall be complete in all respects. Any material and components not specifically stated in this specification but which is necessary for trouble free operation of the equipment and accessories specified in this specification, shall be deemed to be included unless specfically in all respects to high standards of engineering design and workmanship and shall be capable of performing in continous operation. |
| 70 | Supply,Install,Testing and Commissioning LT panel Outdoor type, dust and vermin proof totally enclosed ,with sloping canopy fabricated out of steel sections, the door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 54 standard double shutter gears front and rear frame work and 2 mm thick MS sheet duly powder coated made of 40 x 40 x 6 mm thick angle iron frame including necessary PCC work all as specfified suitable for 415 Volts, 50 Hz 3 phase and neutral system and shall be completed with Aluminium bus bar of capacity 1500 Amps with bus bar chamber,internal wiring with suitable size of PVC insulated copper cable copper lugs comprising of following accessories:-(MLTP For Offrs Qtrs) |
| 71 | Incoming:-(i) 1000 Amp 4 Pole 415 V 50 KA EDO Air Circuit Breaker Microprocessor based with O/L, S/C & E/F Protection - 01 No(ii) Indicating lamp 3 Nos(iii) LED Multifunctional meter accuracy class 1.0,0.5,input voltage measurement range 50-520 VAC(P-P),Aux supply 80-300VAC,Flush mounting 96x96mm,Site selectable 1A/5A,CT/PT site programmable with RS485 port along with Following parameters :-VA,F,PF,kW,kVA,Old energy,On and Run hours,site selectable KWH/KVAH- 01 No.Outgoing:-(i) MCCB 400 Amps,50 KA, 4 pole with adjustable thermal and fixed magnetic setting-02 No (FLP-1,FLP-2)(ii) MCCB 320 Amps,50 KA, 4 pole with adjustable thermal and fixed magnetic setting-01 No (DG set AMF Panel) |
| 72 | Supply,Install,Testing and Commissioning LT panel Outdoor type, dust and vermin proof totally enclosed ,with sloping canopy fabricated out of steel sections, the door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 54 standard double shutter gears front and rear frame work and 2 mm thick MS sheet duly powder coated made of 40 x 40 x 6 mm thick angle iron frame including necessary PCC work all as specfified suitable for 415 Volts, 50 Hz 3 phase and neutral system and shall be completed with Aluminium bus bar of capacity 600 Amps with bus bar chamber,internal wiring with suitable size of PVC insulated copper cable copper lugs comprising of following accessories:- (FLP-1 and FLP-2 for Offrs Qtrs) |
| 73 | Incoming:-(i) MCCB 400 Amps,50 KA, 4 pole with adjustable thermal and fixed magnetic setting-01 No (ii) Indicating lamp 3 Nos(iii) LED Multifunctional meter accuracy class 1.0,0.5,input voltage measurement range 50-520 VAC(P-P),Aux supply 80-300VAC,Flush mounting 96x96mm,Site selectable 1A/5A,CT/PT site programmable with RS485 port along with Following parameters :-VA,F,PF,kW,kVA,Old energy,On and Run hours,site selectable KWH/KVAH- 01 No.Outgoing:-(i) MCCB 400 Amps,50 KA, 4 pole with adjustable thermal and fixed magnetic setting-01 No |
| 74 | Supply,Install,Testing and Commissioning LT panel Outdoor type, dust and vermin proof totally enclosed ,with sloping canopy fabricated out of steel sections, the door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 54 standard double shutter gears front and rear frame work and 2 mm thick MS sheet duly powder coated made of 40 x 40 x 6 mm thick angle iron frame including necessary PCC work all as specfified suitable for 415 Volts, 50 Hz 3 phase and neutral system and shall be completed with Aluminium bus bar of capacity 500 Amps with bus bar chamber,internal wiring with suitable size of PVC insulated copper cable copper lugs comprising of following accessories:- (After DG Ser AMF 160 KVA Panel) |
| 75 | Incoming:-(i) MCCB 320 Amps,50 KA, 4 pole with adjustable thermal and fixed magnetic setting-01 No (ii) Indicating lamp 3 Nos(iii) LED Multifunctional meter accuracy class 1.0,0.5,input voltage measurement range 50-520 VAC(P-P),Aux supply 80-300VAC,Flush mounting 96x96mm,Site selectable 1A/5A,CT/PT site programmable with RS485 port along with Following parameters :-VA,F,PF,kW,kVA,Old energy,On and Run hours,site selectable KWH/KVAH- 01 No.Outgoing:-(i) MCCB 250 Amps,36 KA, 4 pole with adjustable thermal and fixed magnetic setting-01 No (ii) MCCB 125 Amps,25 KA, 4 pole with fixed thermal and fixed magnetic setting02 No (iii) MCCB 63 Amps,25 KA, 4 pole with fixed thermal and fixed magnetic setting-02 No (iv) Astronomical Time switch - 1 No & 3 pole Contactor- 1 No for street light control |
| 76 | Supply,Install,Testing and Commissioning LT panel indoor type, dust and vermin proof totally enclosed, with sloping canopy fabricated out of steel sections, the door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 54 standard double shutter gears front and rear frame work and 2 mm thick MS sheet duly powder coated made of 40 x 40 x 6 mm thick angle iron frame including necessary PCC work all as specfified suitable for 415 Volts, 50 Hz 3 phase and neutral system and shall be completed with Aluminium bus bar of capacity 150 Amps with bus bar chamber,internal wiring with suitable size of PVC insulated copper cable copper lugs comprising of following accessories (for Officer Qtrs ) |
| 77 | Incoming:-(i) MCCB 100 Amps,25 KA, 4 pole with adjustable thermal and fixed magnetic setting-01 No (ii) Indicating lamp 3 Nos(iii) LED Multifunctional meter accuracy class 1.0,0.5,input voltage measurement range 50-520 VAC(P-P),Aux supply 80-300VAC,Flush mounting 96x96mm,Site selectable 1A/5A,CT/PT site programmable with RS485 port along with Following parameters :-VA,F,PF,kW,kVA,Old energy,On and Run hours,site selectable KWH/KVAH- 01 No.Outgoing:-(i) TPN 63 Amp 10 KA ,C curve - 04 Nos(ii) Having space for three phase smart meter - 04 Nos |
| 78 | Supply,Install,Testing and Commissioning LT panel Outdoor type, dust and vermin proof totally enclosed ,with sloping canopy fabricated out of steel sections, the door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 54 standard double shutter gears front and rear frame work and 2 mm thick MS sheet duly powder coated made of 40 x 40 x 6 mm thick angle iron frame including necessary PCC work all as specfified suitable for 415 Volts, 50 Hz 3 phase and neutral system and shall be completed with Aluminium bus bar of capacity 1200 Amps with bus bar chamber,internal wiring with suitable size of PVC insulated copper cable copper lugs comprising of following accessories. (MLTP for JCOs and ORs Accn) |
| 79 | Incoming:-(i) 800 Amp 4 Pole 415 V 50 KA EDO Air Circuit Breaker Microprocessor based with O/L, S/C & E/F Protection - 01 No(ii) Indicating lamp 3 Nos(iii) LED Multifunctional meter accuracy class 1.0,0.5,input voltage measurement range 50-520 VAC(P-P),Aux supply 80-300VAC,Flush mounting 96x96mm,Site selectable 1A/5A,CT/PT site programmable with RS485 port along with Following parameters :-VA,F,PF,kW,kVA,Old energy,On and Run hours,site selectable KWH/KVAH- 01 No.Outgoing:-(i) MCCB 400 Amps,50 KA, 4 pole with adjustable thermal and fixed magnetic setting-01 No(ii) MCCB 250 Amps,50 KA, 4 pole with adjustable thermal nd fixed magnetic setting-04 Nos |
| 80 | Supply,Install,Testing and Commissioning LT panel Outdoor type, dust and vermin proof totally enclosed ,with sloping canopy fabricated out of steel sections, the door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 54 standard double shutter gears front and rear frame work and 2 mm thick MS sheet duly powder coated made of 40 x 40 x 6 mm thick angle iron frame including necessary PCC work all as specfified suitable for 415 Volts, 50 Hz 3 phase and neutral system and shall be completed with Aluminium bus bar of capacity 600 Amps with bus bar chamber,internal wiring with suitable size of PVC insulated copper cable copper lugs comprising of following accessories:- |
| 81 | Incoming:-(i) MCCB 400 Amps,50 KA, 4 pole with adjustable thermal and fixed thermal setting-01 No (ii) Indicating lamp 3 Nos(iii) LED Multifunctional meter accuracy class 1.0,0.5,input voltage measurement range 50-520 VAC(P-P),Aux supply 80-300VAC,Flush mounting 96x96mm,Site selectable 1A/5A,CT/PT site programmable with RS485 port along with Following parameters :-VA,F,PF,kW,kVA,Old energy,On and Run hours,site selectable KWH/KVAH- 01 No.Outgoing:-(i) MCCB 250 Amps,36 KA, 4 pole with adjustable thermal and fixed thermal setting-04 Nos(ii) MCCB 125 Amps,25 KA, 4 pole with fixed thermal and fixed thermal setting-04 Nos(iii) MCCB 63 Amps,25 KA, 4 pole fixed thermal and fixed thermal setting-01 No (iv) Astronomical Time switch - 1 No & 3 pole Contactor- 1 No |
| 82 | Supply,Install,Testing and Commissioning LT panel Outdoor type, dust and vermin proof totally enclosed ,with sloping canopy fabricated out of steel sections, the door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 54 standard double shutter gears front and rear frame work and 2 mm thick MS sheet duly powder coated made of 40 x 40 x 6 mm thick angle iron frame including necessary PCC work all as specfified suitable for 415 Volts, 50 Hz 3 phase and neutral system and shall be completed with Aluminium bus bar of capacity 400 Amps with bus bar chamber,internal wiring with suitable size of PVC insulated copper cable copper lugs comprising of following accessories:- |
| 83 | Incoming:-(i) MCCB 250 Amps,36 KA, 4 pole with adjustable thermal and fixed thermal setting-01 No (ii) Indicating lamp 3 Nos(iii) LED Multifunctional meter accuracy class 1.0,0.5,input voltage measurement range 50-520 VAC(P-P),Aux supply 80-300VAC,Flush mounting 96x96mm,Site selectable 1A/5A,CT/PT site programmable with RS485 port along with Following parameters :-VA,F,PF,kW,kVA,Old energy,On and Run hours,site selectable KWH/KVAH- 01 No. |
| 84 | Supply,Install,Testing and Commissioning of LT panel indoor type, dust and vermin proof totally enclosed ,with sloping canopy fabricated out of steel sections, the door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 54 standard double shutter gears front and rear frame work and 2 mm thick MS sheet duly powder coated made of 40 x 40 x 6 mm thick angle iron frame including necessary PCC work all as specfified suitable for 415 Volts, 50 Hz 3 phase and neutral system and shall be completed with Aluminium bus bar of capacity 125 Amps with bus bar chamber,internal wiring with suitable size of PVC insulated copper cable copper lugs comprising of following accessories:-(For JCO/OR Qtrs) |
| 85 | Incoming:-(i) MCCB 63 Amps,25 KA, 4 pole fixed thermal and fixed thermal setting-01 No (ii) Indicating lamp 3 Nos(iii) LED Multifunctional meter accuracy class 1.0,0.5,input voltage measurement range 50-520 VAC(P-P),Aux supply 80-300VAC,Flush mounting 96x96mm,Site selectable 1A/5A,CT/PT site programmable with RS485 port along with Following parameters :-VA,F,PF,kW,kVA,Old energy,On and Run hours,site selectable KWH/KVAH- 01 No.Outgoing:-(i) MCB DP 32 Amps 'C' series 10 KA AC 240 Volt - 04 Nos(ii) Having space for single phase smart meter - 04 Nos |
| 86 | M&L for SITC of IK10 Sandwich Type Rising Mains / Bus Duct Confirming to IEC 61439 part 1 & part 6 standard and Manufactured in India for use on 3 phase 4 wire , 415 volts, 50Hz A.C. supply , class F insulation, rated insulation voltage 1000V, impulse withstand voltage 12 KV, min. seismic zone 5 as per IS 1893 (Part 1), with IP-54 / IP-66 (With Canopy) enclosure made of 1.6mm thick sheet steel duly powder coated in convenient sections complete with 4 Nos aluminum (with IS 19501 or superior ) bus bars of size 400 Amps breaking capacity 50 KA, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every meter, continuous earthing with 2 Nos aluminum strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system including making opening in RCC / Brick Masonry and repairing the same etc. complete all as specified and directed. |
| 87 | M&L for SITC of IK10 Sandwich Type Rising Mains / Bus Duct Confirming to IEC 61439 part 1 & part 6 standard and Manufactured in India for use on 3 phase 4 wire , 415 volts, 50Hz A.C. supply , class F insulation, rated insulation voltage 1000V, impulse withstand voltage 12 KV, min. seismic zone 5 as per IS 1893 (Part 1), with IP-54 / IP-66 (With Canopy) enclosure made of 1.6mm thick sheet steel duly powder coated in convenient sections complete with 4 Nos aluminum (with IS 19501 or superior ) bus bars of size 250 Amps breaking capacity 25 KA, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every meter, continuous earthing with 2 Nos aluminum strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system including making opening in RCC / Brick Masonry and repairing the same etc.complete all as specified and directed. |
| 88 | M&L for SITC of Bus Rising Main OEM manufactured following capacity Plug in / Tap off Box suitable for Sandwich type bus bar trunking Confirming to IS 8623 P-II & IEC-60947-2-2000 for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision and including of MCCB 100 Amp ,35 kA with Interlocking complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required and switchgear to be installed should be of same make as of manufacturer recommendation completes all as specified and directed by Engineer in charge. |
| 89 | M&L for SITC of Bus Rising Main OEM manufactured following capacity Plug in / Tap off Box suitable for Sandwich type bus bar trunking Confirming to IS 8623 P-II & IEC-60947-2-2000 for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision and including of MCCB 63 Amp ,25 kA with Interlocking complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required and switchgear to be installed should be of same make as of manufacturer recommendation completes all as specified and directed by Engineer in charge. |
| 90 | M&L for SITC of Bus Rising Main OEM manufactured following capacity End Feed Unit Confirming to IS 8623 P-II suitable for Sandwich / Compact Air Insulated type for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision and including of MCCB of size 400 Amp 35 kA with Interlocking feature complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. All as per pre-approved by Engineer in charge. |
| 91 | M&L for SITC of Bus Rising Main OEM manufactured following capacity End Feed Unit Confirming to IS 8623 P-II suitable for Sandwich / Compact Air Insulated type for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision and including of MCCB of size 250 Amp 35 kA with Interlocking feature complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. All as per pre-approved by Engineer in charge. |
| 92 | Supply, install, testing and commissioning of HT 11KV, 3 Phase, 50Hz, totally enclosed metal clad SF6 switchgear having rupturing capacity up to 630 Amps, Outdoor Non-Extensible Fixed Type (IP54), RMU (Ring main unit) 4-way comprising of 02 Nos 630 Amps, motorized operated Load Break Switch & 02 Nos. motorized charging fixed-type Vacuum Circuit Breaker, inside robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank having min. thickness 2.5 mm with IP 67 Degree of Protection and enhanced BIL of 95kVp internally to manage voltage surges. RMU should be provided with internal busbars, as well as earthing busbars of electrolytic grade copper, padlock provisions & complete with all accessories. The RMU shall be type tested for Internal arc test of AFL 21kA/1 sec for tank as per IEC62271-200. RMU shall have on-site-reparability features such as site replaceable bushing/coupling/mechanism and gas refilling at site. The earthing busbar shall be provided inside each cable compartment for solid earthing of Cable shields. The outer hinged main door should cover entire front of switchgear including cable doors for providing fail-safe protection. The unit shall include the following with all necessary standards fitting as required at site:- |
| 93 | 02 Nos.Incoming Load Break Switch module consisting of following accessories:-11kV, 630A Load Break Switch module and integrated earthing switch, both with full making capacity.Short time current - 21kA/3-sec, Making Capacity - 52kApAuxiliary contacts - 1NO + 1NCFault Pass Indicator - 1 No for Incoming LBSSpring-assisted snap-action mechanism driven via motor and manual operation.Cable boxes with double-door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access to 3Cx300sqmm XLPE AL cable termination in live-condition, Right angle boots (push on type)Suitable site replaceable Cable bushings situated not beyond 300mm from cable-cover to allow ease of access for installation/testing/replacement purposes. Cable covers with self-Interlocking mechanism with earth switch Capacitive voltage indication fixed type system as per IEC61243 |
| 94 | 02 Nos. Outgoing Breaker module consisting of following accessories:11kV, 630A fixed-type Vacuum Circuit Breaker module for making and breaking of fault current along with disconnector Earth Switch of full making capacityShort time current - 21KA/ 3 sec, Making Capacity - 52kApAuxiliary contacts - 1NO + 1NCStored Energy mechanism with manual and motorized spring-charging, associated closing/tripping coils, integrated non-removable spring-charging operating handle and ON/OFF push buttons mechanically latched to the mechanism Interlocked Cable box for front termination of the cable suitable up to 3 core 300 Sqmm, 11 KV XLPE cable with double-door arrangement (IP54+IP3X). Safety interlocked to prevent access to cable termination in live-condition. Right angle boots (push on type)Numerical based self-powered OC+EF Protection Relay with three nos high and low setting, providing Over Current (min. setting 20%), Earth-Fault (min. setting: 10%)03 Nos 200/1, 2.5VA epoxy insulated, Ring Core CTs for protection (Acc.Cl.5P10), installed away from bushings to prevent saturation of core. |
| 95 | Suitable site replaceable Cable bushings situated not beyond 300mm from cable-cover to allow ease of access for installation/testing/replacement purposes.Cable covers with self-Interlocking mechanism between doors, earth switch, disconnected & VCBCapacitive voltage indication fixed type system Mechanical Indications for breaker ON, OFF, EARTH, TRIP, Spring Charged-Discharged.Battery (24V DC) and battery charger (7.5A, 230V AC/24V DC)Capacitive voltage indication fixed type VPIS 9-15 kVNecessary interlocking arrangement for safety and operationsOne No. Operation Handle for Manual Operation and one no. manometerSafety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturer’s directions.Above switchgear shall confirm to all relevant IEC/IS Standards.Vacuum interrupter should be of same make as RMUCable bushing should be replaceable at site.Minimum 5 modules should accommodate in one tank to avoid multiple coupling at site.Note: -(i) The rate quoted by the tender is deemed to include the cost of provision of PCC/RCC foundation including excavation and earth work all as per manufacturers’ instructions and as directed.(ii) The RMU shall be compatible for SCADA online monitoring system. |
| 96 | Advanced metering infrastructure (AMI)Design, Supply, installation, commissioning, integration and testing of the advanced metering infrastructure (AMI) including procurement of all necessary hardware, software, programming licenses, documentation with having specifications and comprising following: Please Enable Macros to View BoQ information |
| 97 | Advanced metering infrastructure (AMI)Design, Supply, installation, commissioning, integration and testing of the advanced metering infrastructure (AMI) including procurement of all necessary hardware, software, programming licenses, documentation with having specifications and comprising following: Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 23, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 28, 2026
17:00 IST