Tender for special Rep/Replacement Of Ber Cooling Appliances, Certain B&R And E&M Fittings At Mes Pump House And Power House At 4Afsb Under Ge(Af) Gorakhpur.
BOQ
| Sl. No. | Item Description |
| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: Garrison Engineer (AF) Gorakhpur Name of Work: SPL REP/REPLACEMENT OF BER COOLING APPLIANCES, CERTAIN B&R AND E&M FITTINGS AT MES PUMP HOUSE AND POWER HOUSE AT 4AFSB UNDER GE(AF) GORAKHPUR. Contract No.: GE(AF)/GKP/E-66 OF 2026-27 File No.9516/E8 Serial Page No.15 Name of the Bidder/ Bidding Firm / Company : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description of items Item Code / Make Quantity Units Estimated Rate inRs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e. DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit, if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes inRs. P TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Dismantling Asbestus cement (corrugated semi corrugated,etc sheets in roof coverings complete all as specified and directed. |
| 3 | S&F pre-painted galvalume aluminium zinc coating GI based corrugated, steel sheet 0.50mm thick of any colour having tensile strength of 550 mpa as in roof covering/cladding to wall, fixed with self tapping screws as complete all as specified and directed. |
| 4 | S&F Pre-painted galvalume aluminum zinc coating GI based Plain steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws. Complete all as specified and directed. |
| 5 | M & L for Roughning and cleaning to existing RCC roof surface/Roof treatiment and removing rubbish off the premises, cleaning surfaces of entire roof area, removing all dust ,loose particle and grease with a wire brush or scrubber and preparing to receive new roof treatment. Supply and Application of 5 Layer SHR Waterproofing Coating System as per manufacturer application procedure on leaking concrete roof surface by thorough surface preparation with high pressure water jet min. 125 bars, opening the cracks, followed by one absorption coat of nano-tech enhanced elastomeric waterproofing (NEEWP) emulsion having UV resistance and min. 50% solids, filling and sealing the cracks, then over coating with 2 Coats of NEEWP + Cement mixture as waterproofing coat having +450% Elongation. The surface is then to be tested for water tightness with a ponding test for min. 2 days and then top-coated with 2 Coats of SHR Coating - pure acrylic based, UV resistant, non-yellowing, bio-organism resistant (anti-fungal, anti-bacterial) conforming to BIS STD IS 17218:2019 with Pull off Adhesion 2.8 Mpa, passes 2000 hrs accelerated durability test, suitable for all types of cementitious surfaces, white colour, matt, surface coverage 3.25 SQM/Ltr/2 Coats, DFT 100 - 120 microns using brush, roller, airless spray gun as applicable. The product should be certified by NABL Approved Lab and application is to be done by company approved applicator only.The guarantee for treatment shall be given by the contracyor in writing for a period of 5 year and security deposit @ 2.5 % of total cost of treatment shall be given for 5 year from the date of completion of work. |
| 6 | Demolition of Brickwork or stone/boulder masonry built in cement mortar compete all as specified and directed. |
| 7 | M&L for Brick work with subclass 'B'bricks, straight or curved on plan exc 6m mean radius, built in CM (1:6) compete all as specified and directed. |
| 8 | Taking down cement or cement lime plaster any description on brick or stone walls, etc including raking out joints, hacking for key scrubbing down with water etc complete all as specified as directed. |
| 9 | M&L Rendering 15mm thick in CM 1:6 on fair faces of brick work or concrete surfaces, finished even and smooth without using extra cement complete all as specified as directed. |
| 10 | M&L Rendering 15mm thick in CM 1:4 on fair faces of brick work or concrete surfaces with liquid WPC @ 150 ml per 50 kg of cement or as per manufacturer instructions ( WPC will be measured and paid separately), finished even and smooth without using extra cement complete all as specified as directed. |
| 11 | M&L Rendering 5mm thick in CM 1:3 on celing, finished even and smooth without using extra cement complete all as specified as directed. |
| 12 | M&L for two coat of oil bound distemper on walls over one coat of 1mm thick wall care putty after complete preparation on new plastered surfaces of walls compete all as specified and directed. |
| 13 | M&L for applying two coat of Oil bound distemper over 1mm wall care putty on ceiling after complete preparation on new plastered surfaces of ceiling compete all as specified and directed. |
| 14 | M&L for two coat of cement base paint over a coat of alkali resistant cement primer on newly plastered surface including preparation of undecorated surface complete all as specified and as directed. |
| 15 | M&L for complete removal of existing treatment on wall/roof projections for by scrapping with mechanical sander (having mechanical vaccume mechanism) with sanding pad applying one coat of100% premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489.2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Comany Depot Tinted) with silicon additives @ 1.43 Litre/10 Sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm over a coat of 1mm thick wall care putty . Note:- Primer and emulsion to be carried out through air less spray machine (Mechanical means). Complete all as specified and directed. |
| 16 | Dismantling wrought iron or mild steel work of any description not otherwise provided for . Complete all as specified and directed. |
| 17 | S&F steel work in tubular Post/ trusses including special shaped washer etc complete using ERW or induction butt welded tubes conforming to I.S. 1161-1998 grade St-240 including all necessary work as directed by Engr in Charge complete all as specified and directed. |
| 18 | S&F steel doors inculding projecting type hinges, steel handle, complete, with, glazing bars, dovetailed or welded compete all as specified and directed. |
| 19 | S&F Steel rolling shutters of 1.25 mm thick lath , with out ball bearing, as specified including top cover, anchoring rod, hasp and staple and one shop coat of primer; erected in position as indicated, gear operated type with bevel gear box and crank handle complete as specified. |
| 20 | M&L for preparation of previously untreated steel and iron surfaces of any description not otherwise decribed over 10 cm in width or girth and applying two coats of synthetic enamel paint over a coat of red oxide primer Complete all as specified and directed. |
| 21 | Taking down chowkhat or frames n.exc 1.5 sqm each with shutters (without taking off shutters from frames). complete all as specified. |
| 22 | M&L for Granite (of any type) 20mm thick machine cut bedded and jointed with grey cement slurry and pointed with white cement with admixture of pigment to match the shade of granite stone including grinding and polishing rounded edgs laid as window sill over & including15 mm thick screed bed in cm 1:6 etc, complete all as specified as directed. |
| 23 | M&L for Providing and fixing factory made uPVC white colour Sliding window Three track made of extruded profiles with wall thickness of 2.3mm (+ -0.2mm). Window profile with hollow section with multi chamber. Frame (88mm x 52mm), sliding sash (42mm x 67mm). Sliding mesh Sash (42mm x 57mm) Sliding interlock (Onevertical length in each shutters) (45.5mm x 28mm), Glazing bead (24.5mm x 16mm) will be miterd cutand fusion welded at all corners, including drilling of holes for fixing hardware and drainage of wateretc., making arrangement for fixing of hardware. EPDM gasket, 1.2+ -0.2mm thick galvanised steelFrame (30mm x 18mm) 2 nos, sliding sash (30mm x18mm), sliding mesh sash (26mm x 10mm) profile tobe inserted in required profile, frame will be fixed tothe wall with 8mm x 100mm long fasteners, Hardware[Touch Lock of zinc alloyed (white powder coated),steel roller system. Stainless steel wire cloth .36mmnominal dia of wire and average width of aperture1.40mm and required accessories (Note: The unit rate quoted by contractor excludescost of glass and includes all other connectedccessories. Net Opening will be measured lorpayment purpose.) Area not exceeding 2.00 sqm each. |
| 24 | Providing and fixing factory made uPVC white colour casement (Openable) Door made of extruded profile wilh wall thickness of 2.3mm ( + -0.2mm). Window profile with hollow section with mitlti chamber, frame (60mm x 58mm), sash (60mm x 78mm). T profile (One vertical length in between two shutters) (60mm x 74mm). Glazing bead (35mm x 20mm) will be mitered cut and fusion welded at all corners, including drilling ol holes for fixing hardware and drainage of water etc., making arrangement for fixing of hardware. EPDM gasket 1.2 + -0.2mm thick galvanized steel Frame (28mm x 21.5mm), sash (31mm x 27mm), T profile (27mm x 17mm) to be inserted in required profile, frame will be fixed to the wall wilh 8mm x 100mm long fasteners. Hardware: [casement door handle made of zinc alloyed (white powder coated). Corner striker. Secondary Strikers. Cylinder. Door transmission gear made of mild sleel with multi point locking system with strikes. 3D Hinges of zinc alloyed (white powder coated) [and 5mm thick glazing with selected quality glass.(Note: The unit rate quoted by contractor excludes cost of glass and includes all other connected accessories. Net opening will be measured for payment purpose.) |
| 25 | S&F 4.00 mm thick sheet glass (Plain/Tinted in colour) in metal frame, ordinary quality n.exc 0.5sqm in each pane. Complete all as specified and directed. |
| 26 | M&L for Framed work such as grills,gratings, etc.. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe.290.Gde-E-165 |
| 27 | Dismantling floor, hearth or wall tiling/Stone slab including cement mortar bedding (but not backing), removing and rubbish off the premises compete all as specified and directed. |
| 28 | M&L for Providing and laying 60mm thick factory made chamfered edge cement concrete paver block of M-35 grade with approved colour, design & pattern as in footparth, parks, lawns, drive ways or light traffic parking etc., of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over and including 50mm thick compacted bed of fine sand, compacting and proper embedding/ laying of interlocking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand complete all as specified and directed. |
| 29 | M&L for plain cement concrete 1:2:4 type B1 (using 20mm graded crushed stone aggregate) as in coping including necessary form work all as specified. |
| 30 | Demolition of cement concrete (unreinforced) in ground floors and roof and paving not exceeding 15 cm thickness (below or above ground level) .complete all as specified and directed. |
| 31 | M&L 100 mm thick cement concrete type D2 (1:4:8) using 40 mm stone aggregate as in sub base of floor all as specified and directed. |
| 32 | S&F machine cut kota stone slab flooring 20-25mm thick over cement screed base laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing including screed bed 20mm thick in cement concrete 1:6 complete all as specified and directed. |
| 33 | S&F Kota stone slab 20-25mm thick in riser of steps, skirting, dado and pillar laid over cement screed and jointed with Complete all as specified and directed. |
| 34 | M&L for Non - skid coioured ceramic tiles 7 to 8 mm thick area of each tile exceeding 0.11 sqm but not exceeding 0.18 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match over 15mm thick screed bed in CM (1:6) set complete all as specified and as specified and directed |
| 35 | S&F Glazed ceramic coloured tiles 350x250x7mm /450x350x7mm thick in skirting dados risers to steps etc set and jointed in neat cement slurry and pointed in coloured cement to match tiles over 10 mm thick cement plaster in CM (1:3) complete all as specified as directed.. |
| 36 | M&L Light shade Vitrified Ceramic tiles 10 mm thick (square/ rectangular) polished, area of each tiles not exceeding 0.36 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match over 15 mm thick cement mortar (1:4) bedding complete all as specified and directed |
| 37 | M&L Light shade Vitrified Ceramic tiles 10 mm thick (square/ rectangular) polished, as skirting etc. set and pointed in white or coloured cement to match over 10mm thick cement plaster in CM (1:3) complete all as specified and directed |
| 38 | Dismantling wall and ceiling boards (fibre, pulp, insulation, etc.) or insulation boards/slabs/ boarding/ blankets, any thickness, including cover fillets, any description complete all as specified and directed |
| 39 | S&F for Anodised aluminium snap grid frame work of grid size 605x605mm for false ceiling complete all as specified and directed. |
| 40 | S&F for Hangers 6 mm dia. G.I. (upto 1200mm length) adjusting level fixed to roof slabs by means of ceilling cleats made out of G.I. flat 40 x 3 mm size 60mm long and expansion hold fasteners 12.5mm dia. 40mm long complete all as specified and directed. |
| 41 | M&L for 8 mm thick Non asbestos fibre cement building boards fixed or laid/ inserted to timber/GI/Aluminium framework with screws complete all as specified and directed |
| 42 | M & L in repair for Sub main wiring with approved colour coding as per IS with two single core PVC insulated FRLS cable with stranded copper conductor of size 2.5 Sq mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ ivory colour and its accessaries ISI marked heavy duty of suitable size including concealed in wall etc one run of PVC insulated with 2.5 Sqmm (nominal area) stranded copper conductor FRLS cable as earth wire complete all as specified and as directed. Note:- Two runs of 2.5 sqmm cable,one run of 2.5 sqmm cable and one run of PVC conduit will be measured as one unit |
| 43 | M & L in repair for Sub main wiring with approved colour coding as per IS with two single core PVC insulated FRLS cable with stranded copper conductor of size 4 Sq mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ ivory colour and its accessaries ISI marked heavy duty of suitable size including concealed in wall etc one run of PVC insulated with 4.0 Sqmm (nominal area) stranded copper conductor FRLS cable as earth wire complete all as specified and as directed. Note:- Two runs of 4 sqmm cable,one run of 4 sqmm cable and one run of PVC conduit will be measured as one unit |
| 44 | M & L in repair for Sub main wiring with approved colour coding as per IS with two single core PVC insulated FRLS cable with stranded copper conductor of size 6 Sq mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ ivory colour and its accessaries ISI marked heavy duty of suitable size including concealed in wall etc one run of PVC insulated with 6.0 Sqmm (nominal area) stranded copper conductor FRLS cable as earth wire complete all as specified and as directed. Note:- Two runs of 6 sqmm cable,one run of 6 sqmm cable and one run of PVC conduit will be measured as one unit |
| 45 | S & F in repair for Modular Switch piano flush type, single pole, one way, and 15/16 Amp single module complete all as specified. |
| 46 | S & F in repair for Modular Switch Socket outlet multipurpose having provision for 3 pin, 15/16 Amp and 3 pin, 5/6 Amp, 2 module piano flush type complete all as specified. |
| 47 | Supply and fixing white finished single mounting modular plates with inner & outer cover suitable for housing modular accessories suitable for 3 module box complete all as specified and directed |
| 48 | S&F sheet metal boxes concealed in wall suitable for housing modular accessories for 3 modules complete all as specified and directed. |
| 49 | S & F for metal clad box suitable for 230 volt 50 Hz AC supply three pin with MCB SP 20/32 Amps including removal of old unserviceable one complete including necessary provision for inserting in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. |
| 50 | Supply, installation, testing and commissioning of metal top deep freezer, double door, of approximately 400 Litre gross capacity, single phase, 230/240 Volt, 50 Hz, suitable for operation on 1-phase AC supply, with heavy-duty compressor, static cooling system, eco-friendly R290/R600a refrigerant, high-density PUF insulation, corrosion-resistant pre-coated metal outer body, embossed/anodized aluminium inner cabinet, two insulated top-opening hinged lids with recessed handles and lock & key arrangement, adjustable temperature control suitable for maintaining freezing temperature up to approximately -18°C to -26°C, heavy-duty castor wheels, defrost water drain, storage basket(s), condenser, thermostat, overload protection and all standard accessories, including necessary electrical connections, installation, testing, commissioning and demonstration, complete in all respects as specified and directed. |
| 51 | Supply and installation ,commissioning of water cooler, Electric driven,(single phase 230 volts) fully stainless steel body having approx storage capacity of 120 Litres and nominal cooling capacity of 60 Litres per hour complete all as specified. |
| 52 | Supply, installation, testing and commissioning of single phase, naturally air-cooled, indoor type automatic voltage stabilizer of 2 KVA capacity, suitable for input voltage variation from 170 V to 250 V AC, with stabilized output voltage of 230 V ± 2.5%, complete with automatic voltage regulating arrangement, high/low voltage protection, overload/short-circuit protection, time-delay protection, suitable input and output terminals, indicating lamps/meters, enclosure, necessary internal wiring, mounting arrangement and all accessories required for satisfactory operation, including installation, testing and commissioning, complete in all respects as specified and directed. |
| 53 | S&F flexible pipe for drainage of size 3 / 4\\" as per sample approved complete all as specified and directed. |
| 54 | Supply, fixing and clamping jointing of copper tubing of size 15 mm for suction line and for liquid discharge line including making hole in wall for passing through and making good the disturbed surface omplete all as specified and as directed. |
| 55 | Supply, fixing and clamping jointing of copper tubing of size 12 mm for suction line and for liquid discharge line including making hole in wall for passing through and making good the disturbed surface omplete all as specified and as directed. |
| 56 | Supply, fixing and clamping jointing of copper tubing of size 10 mm for suction line and for liquid discharge line including making hole in wall for passing through and making good the disturbed surface omplete all as specified and as directed. |
| 57 | Supply and fixing insulation foam material suitable for A/C copper pipe omplete all as specified and as directed. |
| 58 | Supply, installation, testing and commissioning of single phase, naturally air-cooled, indoor type automatic voltage stabilizer of 5 KVA capacity, suitable for input voltage variation from 170 V to 250 V AC, with stabilized output voltage of 230 V ± 2.5%, complete with automatic voltage regulating arrangement, high/low voltage protection, overload/short-circuit protection, time-delay protection, suitable input and output terminals, indicating lamps/meters, enclosure, necessary internal wiring, mounting arrangement and all accessories required for satisfactory operation, including installation, testing and commissioning, complete in all respects as specified and directed. |
| 59 | Making hole for installation of Windows AC of size as per sample required by OEM rep. including demolishing of brick work manually/by mechanical means including disposal of debris/malba within 50 meters lead and making good the wall by plastering etc. as required as per specified and directed by Enginner-in-charge. |
| 60 | Supply and installation of AC Bracket made up of GI with powder coated for fixing of outdoor unit of split type and grouting with nut , bolts & Fastenar on the wall and make good the disturbed surface complete all as specified and directed . |
| 61 | Supplying , Installation, Testing and Commissioning of 1.5 TR with Inverter 5 Star BEE rating Window type Air conditioners complete with copper power cable upto 3 Mtr, wireless Remote, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing, cooling, dehumidification, air circulation, R-32/R-410A /R-407B Green Refrigerant with Scroll / rotary compressor with min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB), antifreeze thermostat on the coil as a safety feature, complete with fixing including T&P & labour etc as required complete in all respect as specified of following capacity. Sound level of up to 50dB inside the room is acceptable. The unit shall be in confirmation with IS 1391 Part-I 2023 and CPWD Specification. The system shall be able to deliver 100% of the rated capacity upto 42 0C. The system shall be able to operate up to 50 0C (out door ambient temperature). Inverter Type |
| 62 | Supplying , Installation, Testing and Commissioning of 1.5 TR capacity with 5 Star Rating and EER 3.2 Natural Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, and plasma filter for better indoor air quality with suitable for working between 180V- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB) with temperature sensing control device and the system to be operate up to 50 0C (out door ambient temperature). |
| 63 | Supplying , Installation, Testing and Commissioning of 2.0 TR capacity with 5 Star Rating and EER 3.2 Natural Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, and plasma filter for better indoor air quality with suitable for working between 180V- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB) with temperature sensing control device and the system to be operate up to 50 0C (out door ambient temperature). |
| 64 | Taking down carefully copper / aluminium point wiring (light, fan, switch,socket or power, Bell & Two way point) complete with fitting such as switches, sockets, ceiling rose,sketch light fittings etc, and making good the disturbed surface of walls and floors etc complete all as specified and directed. |
| 65 | Taking down carefully main switches DB's/ MCB DB's and making good the disturbed surfaces of walls etc complete all as specified and directed. |
| 66 | Taking down carefully copper / aluminium sub main wiring including teak wood batten / conduit and making good the disturbed surface of walls as directed. |
| 67 | M & L for Point wiring with PVC insulated PVC unsheathed electric FRLS cable 1100V grade single core having multi stranded copper conductor of size 1.5 Sqmm nominal cross sectional area in & including non metallic rigid PVC conduit ISI marked medium grade not less than 20 mm dia with all conduit accessories in concealed wiring system by cutting of wall and making good disturbed surface of wall (cutting except on ceiling and paneling on this PVC conduit/casing caping on surface will be used) & 1.5 sqmm green PVC insulated unsheathed copper conductor as a earth wire connected to earth dolly by providing lugs including MS boxes for mounting switches, sockets, fan regulators etc for one light/fan point controlled by one switch complete all as specified and as directed. |
| 68 | All as per item above but one 5 Amps socket out let point controlled by one switch on same board with other switches. |
| 69 | All as per item above but one 5 Amps socket out let point on independent board controlled by one switch. |
| 70 | All as per item no above but wiring with 2.5 sq mm single core copper conductor for one socket out let 15/16 amps point on the independent board. Make of cable: Polycab/Havell's/Finolex and Make of PVC conduit: Plaza/Harsh/Kalinga Premium/AKG. |
| 71 | S & F for Modular Switch piano flush type, single pole, one way, and 5/6 Amp single module complete all as specified. |
| 72 | S & F for Modular Switch piano flush type, single pole, one way, and 15/16 Amp single module complete all as specified. |
| 73 | S & F for Modular Socket outlet multipurpose having provision for 3 pin, 5/6 Amp and 2 pin, 5/6 Amp, 2 module piano flush type complete all as specified. |
| 74 | S & F for Modular Switch Socket outlet multipurpose having provision for 3 pin, 15/16 Amp and 3 pin, 5/6 Amp, 2 module piano flush type complete all as specified. |
| 75 | S & F for Ceiling rose, surface Bakelite with 3 terminals, ISI marked for batten fitting complete all as specified |
| 76 | S & F for Modular blanker in suitable size as per site requirement complete all as specified and as directed. |
| 77 | Supply and fixing for batten/angular fittings complete all as specified and directed. |
| 78 | Supply and fix LED Lamp 7/8 watt complete all as specified and directed. |
| 79 | Supply and fixing in repair modular fan regulator 120 Watt step type complete all as specified and directed . |
| 80 | S & F for sheet metal enclosure MCB DB TPN 4 way Vertical/ horizontal type as required with 200 Amps rated bus bar 415 volts double door with magnitic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. |
| 81 | S & F for MCB tripple pole and neutral rated capacity 63 Amps, 415 Volts breaking capacity 10 KA, 'C' curve complete all as specified and as directed. |
| 82 | S & F for sheet metal enclosure MCB DB SPN 8 way with 200 Amps rated bus bar 240 volts double door with magnitic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. |
| 83 | S & F for sheet metal enclosure MCB DB SPN 12 way with 200 Amps rated bus bar 240 volts double door with magnitic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. |
| 84 | S & F for MCB Single pole and neutral rated capacity 40 Amps, 240 Volts breaking capacity 10 KA, 'C' curve complete all as specified and as directed. |
| 85 | S & F for MCB Single pole rated capacity 5 to 32 Amps, 240 Volts breaking capacity 10 KA, 'C' curve complete all as specified and as directed. |
| 86 | M & L for Sub main wiring with approved colour coding as per IS with two single core PVC insulated FRLS cable with stranded copper conductor of size 2.5 Sq mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ ivory colour and its accessaries ISI marked heavy duty of suitable size including concealed in wall etc one run of PVC insulated with 2.5 Sqmm (nominal area) stranded copper conductor FRLS cable as earth wire complete all as specified and as directed. Note:- Two runs of 2.5 sqmm cable,one run of 2.5 sqmm cable and one run of PVC conduit will be measured as one unit |
| 87 | M & L for Sub main wiring with approved colour coding as per IS with two single core PVC insulated FRLS cable with stranded copper conductor of size 4.0 Sq mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ ivory colour and its accessaries ISI marked heavy duty of suitable size including concealed in wall etc one run of PVC insulated with 4.0 Sqmm (nominal area) stranded copper conductor FRLS cable as earth wire complete all as specified and as directed. Note:- Two runs of 4.0 sqmm cable,one run of 4.0 sqmm cable and one run of PVC conduit will be measured as one unit |
| 88 | M & L for Sub main wiring with approved colour coding as per IS with two single core PVC insulated FRLS cable with stranded copper conductor of size 6 Sq mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ ivory colour and its accessaries ISI marked heavy duty of suitable size including concealed in wall etc one run of PVC insulated with 6.0 Sqmm (nominal area) stranded copper conductor FRLS cable as earth wire complete all as specified and as directed. Note:- Two runs of 6 sqmm cable,one run of 6 sqmm cable and one run of PVC conduit will be measured as one unit |
| 89 | M & L for Sub main wiring with approved colour coding as per IS with four single core PVC insulated FRLS cable with stranded copper conductor of size 6 Sq mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ ivory colour and its accessaries ISI marked heavy duty of suitable size including concealed in wall etc one run of PVC insulated with 6.0 Sqmm (nominal area) stranded copper conductor FRLS cable as earth wire complete all as specified and as directed. Note:- Four runs of 6 sqmm cable,one run of 6 sqmm cable and one run of PVC conduit will be measured as one unit |
| 90 | S & F for metal clad box suitable for 230 volt 50 Hz AC supply three pin with MCB SP 20/32 Amps including removal of old unserviceable one complete all as specified and as directed complete all as specified and as directed |
| 91 | Supply and fixing LED tube light batten box type with decorative end caps suitable single tube 1x 18/20 watt type complete internally pre wired and fixed to wall/ceiling incl fittings accessories connecting up with twin core twisted flexible copper conductor cable suitable size all as specified. Make- Havells/ Bajaj/Philips/ CG. |
| 92 | Supply and fixing round shape 12 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete |
| 93 | Supply and fixing LED bulk head 10 watt fittings environmental friendly ultra modern energy saving surface mounted decorataive bulk head fitting with electronic driver and prewired and necessary electric connection with PVC insulated twin twisted flexible copper wire of size 0.75 Sqmm complete all as specified and as directed. Make: Crompton/Bajaj/Havells. |
| 94 | Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type for bldg security lighting energy saving & environmental friendly long life versatile with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection suitable for 40 mm dia GI pipe bracket complete all as specified and directed. Make: Havells /CG/PHILIPS/BAJAJ |
| 95 | M & L for security wall light bracket made out of GI pipe light grade 25/40 mm dia as required length as per site and bent to shape and well finishing including MS clamp of flat iron of size 40x6 suitable length 2 sets complete with drilling, hole, fixing with nuts bolts and washers including painted with two coats of aluminium paints over a coat of red oxide primer including dismantling one complete all as specified and as directed. |
| 96 | Supply and fixing LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. |
| 97 | Taking down fan, ceiling fan and dismantling blades and removing fan and blades to store and after cleaning Refixing of refixing the same with replacement of multistranded copper conductor cable of size 23/ 0.193 from ceiling rose to fan terminal complete all as specified and as directed. |
| 98 | Supply and fix exhaust fan, Steel body AC single Phase. 230V of size 300 mm sweep with, blades, and frame and grouting with nut , bolts & Fastenar on the wall and making the hole in existing wall of specified size also make good the disturbed surface and electric connection with 1.5 Sqmm three core PVC insulated round flexible copper wire upto ceiling rose complete all as specified and directed .Make: Crompton/ Bajaj/Havells/Usha. |
| 99 | Supply and fixing of Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge not less than 1.25 Metres below ground level connected with earthing lead of 4mm dia by means of bolts, nut, check nuts and washers of galvanized iron or steel wire all as shown in Plate No. 2 to the earthing test point all as specified and indicated including testing on completion including excavation in any type of soil,returning filling, disposal of soil, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion complete Total in Figures 23 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 23, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedOct 13, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysOct 15, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender